Security Camera User Manual

- 4 -
WJ-HD316A
WU-CU650
Wiring Color Code
Power and Control Inputs
1 24 VAC Live Black
2 24 VAC Live White
3 Green Green
4 Not Used
1 24 VAC Live Red
2 24 VAC Live White
3 Green Green
4 Not Used
1 Ground Brown
2 TXB (RS485) Red
3 TXA (RS485) Orange
4 RXB (RS485) Yellow
5 RXB (RS485) Green
CAMERA POWER [13 watts WV-CS954 / WV-CS574]
CONNECTOR B
ACCESSORY POWER [52 watts Heater/Blower]
CONTROL
POD9C
CONNECTOR A
Pan/Tilt Unit Only
1 Alarm In 1 Black
2 Ground Brown
3 Alarm In 2 Red
4 Ground Orange
5 Alarm In 3 Yellow
6 Ground Light blue or green
7 Alarm In 4 Blue
8 Ground Purple
ALARM IN (8-pin)
1 Alarm Out 1 Gray
2 Ground White
3 Alarm Out 2 Pink
4 Ground Yellow, Green, or Light blue
ALARM OUT (4-pin)
Approx. 0.1"
Wire
Insert
Up
Contact
Wire
Up
Contact
1
2
4
3
HOW TO ASSEMbLE THE CONNECTOR
Strip back the cable jacket approximately 0.1 inch
(3 mm) and separate the individual conductors.
Prepare the individual conductors for clamping. If
clamping, use Molex brand tool part number 57027-
5000 (for UL-listed-style cable UL1015) or 57026-5000
(for UL-listed-style cable UL1007).
After clamping the contacts, push them into the
proper holes in the connector housing until they
snap in place.
CAUTIONS
Shrinking the cable-entry seal is a onetime
procedure. Do not shrink the cable-entry seal
until it has been determined that the unit is
functioning.
CONNECT THIS TO A 24 VAC CLASS 2 POWER
SUPPLY ONLY.
CAUTION: TO PREVENT FIRE OR SHOCK HAZARD, THE
UL-LISTED WIRE VW-1, STYLE 1007, SHOULD BE USED
FOR THE CABLE FOR 24 VAC INPUT TERMINALS.
OPERATING DISTANCES
Awg Size Impedance Max Distance
Awg #12 1.71 ohm/1000 ft. 440 ft.
Awg #14 2.73 ohm/1000 ft. 270 ft.
Awg #16 4.35 ohm/1000 ft. 170 ft.
Awg #18 6.92 ohm/1000 ft. 100 ft.
CAUTION: For lightning protection of the camera
and heater/blower, the pin 3 of the connector
must be connected to real electrical ground.