Datasheet

7
3-2
Mounting interval (thru-beam type NX5-M□)
In case mounting two sets or more of the this product close together, mount them as
drawing left indicates (typical example)
Find out the operating point ℓ on the parallel deviation diagram for the setting distance L.
Separate sensors by 2 × ℓ or more.
NX5-M10R□ parallel deviation diagram (typical)
1,000 500 0 500
0
10
5
CenterLeft
Right
Operational point ℓ(mm)
(ℓ1)
(L1)
Sensing distance L (m)
1,000
<Installation interval for NX5-M10R□>
In case using at sensing distance (L1) 10m, the
operation point (ℓ1) is approx. 444mm according
to diagram left.
The installation interval is
Approx. 444mm × 2 = 888mm
Thus, install another NX5-M10R□ to 888mm or
more away.
NX5-M30 parallel deviation diagram (typical)
0
40
20
30
10
2,000 1,000 0 1,000 2,000
(ℓ2)
(L2)
CenterLeft
Right
Operational point ℓ (mm)
Sensing distance L (m)
<Installation interval for NX5-M30□>
In case using at sensing distance (L2) 30m, the
operation point (ℓ2) is approx. 1,200mm accord-
ing to diagram left.
The installation interval is
Approx. 1,200mm × 2 = 2,400mm
Thus, install another NX5-M30□ to 2,400mm or
more away.