MINI VRF System U-36LE1U6 U-36LE1U6E * U-52LE1U6 U-52LE1U6E * Section 1 1 Section 2 2 Model No. Outdoor Unit Class Model Name 36 U-36LE1U6 U-36LE1U6E* 3 3 52 U-52LE1U6 U-52LE1U6E* Refrigerant R410A is used in the outdoor units. * Salt-Air Damage Resistant Specifications.
IMPORTANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes.
When Servicing CAUTION • Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. • Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. • Keep your fingers and clothing away from any moving parts.
Precautions for Installation Using New Refrigerant 1.Care regarding tubing 1-1.Process tubing Material:Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.” Tubing size:Be sure to use the sizes indicated in the table below. Use a tube cutter when cutting the tubing, and be sure to remove any flash.This also applies to distribution joints (optional).
3-2.Use R410A exclusive cylinder only. Valve Single-outlet valve (with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown. Liquid New refrigerant R410A cannot be used for earlier models 1.Compressor specifications are different. If recharging a R22 or R407C compressor with R410A, durability will significantly decrease since some of the materials used for compressor parts are different. 2.Existing tubing cannot be used (especially R22).
Contents Section 1: OUTLINE OF MINI VRF SYSTEM .........................................................................1-1 1. Line-up ............................................................................................................ 1-2 2. Salt-Air Damage Resistant Specifications .......................................................1-4 Section 2: DESIGN OF MINI VRF SYSTEM .......................................................................... 2-1 1. Model Selecting and Capacity Calculator ..
Outline of Mini VRF SYSTEM Contents 1. OUTLINE OF MINI VRF SYSTEM 1. Line-up .................................................................................................................................1-2 2. Salt-Air Damage Resistant Specifications.........................................................................1-4 1 2 3 4 5 6 7 8 1-1 TD831156-00_MINI_VRF_SYS.
Outline of Mini VRF SYSTEM 1.
Outline of Mini VRF SYSTEM 1. Line-up Indoor units DC inverter unit Type 36 52 Capacity: BTU/h (kW) 38,200 (11.2) 52,900 (15.5) Cooling / Heating / 42,700 (12.5) / 60,000 (17.
Outline of Mini VRF SYSTEM 2. Salt-Air Damage Resistant Specifications Specifications Relevant Parts Material Standard Specifications Salt-Air Damage Resistant Specifications Outdoor unit model name ended with letters "U6E".
Design of Mini VRF SYSTEM Contents 2. DESIGN OF MINI VRF SYSTEM 1. Model Selecting and Capacity Calculator ......................................................................... 2-2 1-1. Operating Range ........................................................................................................... 2-2 1-2. Procedure for Selecting Models and Calculating Capacity ........................................... 2-3 1-3. Calculation of Actual Capacity of Indoor Unit .................................
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator 1-1. Operating Range Heating Cooling 77 113 1 104 68 95 59 Outdoor air intake temp. °F (WB) Outdoor air intake temp. °F (DB) 109 86 77 Operating range 68 59 50 41 Operating range 32 23 14 5 41 –4 32 50 14 50 59 68 77 86 95 Indoor air intake temp. °F (DB) 23 2 50 57 59 68 77 86 Indoor air intake temp. °F (WB) 3 4 5 6 7 8 2-2 TD831156-00_MINI_VRF_SYS.
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator 1-2. Procedure for Selecting Models and Calculating Capacity ■ Model Selection Procedure Select the model and calculate the capacity for each refrigerant system according to the procedure shown below. Calculation of the indoor air-conditioning load ● Calculate the maximum air-conditioning load for each room or zone.
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator 1-3. Calculation of Actual Capacity of Indoor Unit ■ Calculating the actual capacity of each indoor unit Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference and other factors, select the correct model after taking into account the various correction values. When selecting the model, calculate the corrected capacities of the outdoor unit and each indoor unit.
Design of Mini VRF SYSTEM 1.
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator Indoor unit capacity correction coefficient Refer to the graph below for the correction coefficients for Ruc and Ruh. Indoor unit capacity correction coefficient for Ruc (cooling) Indoor unit capacity correction coefficient for Ruh (heating) 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Corrected indoor/outdoor capacity ratio (Ruc or Ruh) 1.8 1.9 2.
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator Outdoor unit heating capacity characteristics U-52LE1U6, U-52LE1U6E 130 120 110 100 90 80 70 60 50 0 40 –4 (°F DB) 59 Capacity ratio (%) Capacity ratio (%) U-36LE1U6, U-36LE1U6E 68 77 5 14 23 32 41 50 59 Outdoor air intake temp. (°F DB) 130 120 110 100 90 80 70 60 50 40 0 –4 (°F DB) 59 68 77 5 14 23 32 41 50 59 Outdoor air intake temp.
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator ■ Graph of indoor unit capacity characteristics (2 – (1)) indicates the rating point. 120 110 100 90 80 57 59 60 62 64 66 68 69 71 73 75 77 Indoor air intake temp. (˚F WB) Indoor unit heating capacity characteristics Rate of heating capacity change (%) Rate of cooling capacity change (%) Indoor unit cooling capacity characteristics indicates the rating point.
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator 1-4. Capacity Correction Graph According to Temperature Condition ■ Capacity characteristics (The corrected capacity for specific temperature conditions can be found from the graphs below and next page.) Capacity ratio (%) 120 (1) U-36LE1U6, U-36LE1U6E 71°F WB 100 104 (1) 100 (2) 90 (1) 80 (2) 66°F WB 80 60°F WB 14 95 100 (2) U-52LE1U6, U-52LE1U6E 109 Outdoor air intake temp.
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator U-52LE1U6, U-52LE1U6E 1 130 120 110 100 90 80 70 60 50 40 130 120 110 100 90 80 70 60 50 –4 Capacity ratio (%) (°F DB) 59 68 77 Input ratio (%) Input ratio (%) Capacity ratio (%) U-36LE1U6, U-36LE1U6E 59 68 77 5 14 23 32 41 50 59 Outdoor air intake temp. (°F DB) 130 120 110 100 90 80 70 60 50 40 (°F DB) 59 68 77 130 120 110 100 90 80 70 60 50 –4 59 68 77 5 14 23 32 41 50 59 Outdoor air intake temp.
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator ● Inverter model rated performance values Cooling Item Model U-36LE1U6, U-36LE1U6E U-52LE1U6, U-52LE1U6E Heating Cooling capacity BTU/h(kW) Power consumption BTU/h(kW) Heating capacity BTU/h(kW) Power consumption BTU/h(kW) 38,200 (11.2) 52,900 (15.5) 9,400 (2.76) 16,600 (4.57) 42,700 (12.5) 60,000 (17.6) 9,800 (2.88) 15,600 (4.
Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator For U-36LE1U6(E) units ■ If the maximum tubing length (L1) exceeds 295 ft. (equivalent length), increase the tubing size of the main gas tube (LM) by one rank. * The size increase is applied to the gas tube only. In addition, for a 6 HP unit it is not necessary to increase the tubing size. ■ Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Design of Mini VRF SYSTEM 2. System Design 2-3. Type of Copper Tube and Insulation Material 2-1. Tools Required for Installation (not supplied) 1. Flathead screwdriver 2. Phillips head screwdriver 3. Knife or wire stripper 4. Tape measure 5. Carpenter’s level 6. Sabre saw or key hole saw 7. Hack saw 8. Core bits 9. Hammer 10. Drill 11. Tube cutter 12. Tube flaring tool 13. Torque wrench 14. Adjustable wrench 15.
Design of Mini VRF SYSTEM 2. System Design 2-5. Tubing Size Table 2-3 Main Tubing Size (LA) BTU/h (kW) 38,200 (11.2) 52,900 (15.5) 4 6 ø5/8" (ø15.88) ø 3/4" (ø19.05) System horsepower Gas tubing Liquid tubing ø 3/8" (ø9.52) Unit: in. (mm) Note: If the system consists of only one indoor unit with an outdoor 6HP (Type 52), the main tube of the unit (LA) should be ø19.05. Convert ø19.05 to ø15.88 using a reducer (field supply) close to the indoor unit and then make the connection.
Design of Mini VRF SYSTEM 2. System Design 2-7. Additional Refrigerant Charge Additional refrigerant charge amount is calculated from the liquid tubing total length as follows. Table 2-8 Amount of Refrigerant Charge Per Feet, According to Liquid Tubing Size Liquid tubing size (in. (mm)) Amount of refrigerant charge (oz/ft.) ø1/4” (ø6.35) 0.279 ø3/8” (ø9.52) 0.602 Required amount of charge = (Amount of refrigerant charge per ft. of each size of liquid tube × its tube length) + (...) + (...
Design of Mini VRF SYSTEM 2. System Design Table 2-11 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights Items Marks Contents L1 Allowable tubing length Max. tubing length L (L2 – L3) LA 1 1 Allowable elevation difference , 2... + 2 +... H1 H2 n n-1 +L1 Actual length Equivalent length Length (ft.) > 492 > 574 Difference between max. length and min. length from the No.1 distribution joint > 131 Max. length of main tubing (at max.
Design of Mini VRF SYSTEM 2. System Design 2-11. System Example (1) Below are the tables created using the “PAC System Diagram Software.” Details of the calculations are shown in (2). Outdoor unit 131 ft. Elevation difference: 33 ft. 33 ft. 33 ft. 49 ft. 33 ft. 33 ft. 33 ft. Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Selection conditions Assumes that installation is in a 60 Hz region.
Design of Mini VRF SYSTEM 2. System Design Indoor unit changes The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is increased by one rank.
Design of Mini VRF SYSTEM 2. System Design 2-12. Example of Tubing Size Selection and Refrigerant Charge Amount Additional refrigerant charging Based on the values in Tables 2-3, 2-4, 2-5 and 2-8, use the liquid tubing size and length, and calculate the amount of additional refrigerant charge using the formula below. Required additional = 0.602 × (a) + 0.279 × (b) refrigerant charge (oz) (a): Liquid tubing ● Total length of ø3/8” (ø9.52) (ft.) (b): Liquid tubing Total length of ø1/4” (ø6.35) (ft.
Design of Mini VRF SYSTEM 2. System Design Example: L1 L2 LA LB Main tube of unit LC LN n 1st branch Unit distribution tube 1 model 7 model 9 n–1 model 12 model 18 Example of each tubing length Main tubing Distribution joint tubing LA = 131 ft. Indoor side LB = 16 ft. 1 = 16 ft. 4 = 20 ft. LC = 16 ft. 2 = 16 ft. 5 = 16 ft. LD = 49 ft. 3 = 7 ft. ● Obtain charge amount for each tubing size Note that the charge amounts per 3.3 ft. are different for each liquid tubing size. ø3/8" (ø9.
Design of Mini VRF SYSTEM 2. System Design Tube branching methods (horizontal use) 2-13. Installing Distribution Joint (1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit (CZ-P160BK1U). (2) In order to prevent accumulation of refrigerant oil in stopped units, if the main tubing is horizontal then each branch tubing length “B” should be at an angle that is greater than horizontal.
Design of Mini VRF SYSTEM 3. Electrical Wiring 3-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (7) Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before beginning.
Design of Mini VRF SYSTEM 3. Electrical Wiring 3-3.Wiring System Diagram L1 Power supply 208 / 230V, 60Hz, 1-PH L2 Remote Controller WHT 1 BLK 2 Outdoor unit INV unit L1 L2 Ground B * A U1 1 U2 2 L1 L2 L1 L2 Power supply 208 / 230V, 60Hz, 1-PH Ground R1 1 2 R2 L1 Power supply 208 / 230V, 60Hz, 1-PH L2 Remote Controller WHT 1 BLK 2 Indoor unit (No. 1) * * Disconnect switch (Field Supply) A Indoor unit (No. 2) * * NOTE: Disconnect Switch may be needed by the National/Local code.
Design of Mini VRF SYSTEM 3. Electrical Wiring CAUTION (1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no connection wiring between outdoor units), do not remove the short plug. (2) Do not install the inter-unit control wiring in a way that forms a loop.
Design of Mini VRF SYSTEM 3. Electrical Wiring Stranded wire Strip 3/8" WARNING Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected. Ring pressure terminal When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the terminal” and fasten the wire securely with the fixing screw of the terminal plate. Fig.
Design of Mini VRF SYSTEM 3. Electrical Wiring 3-4. Important Note When Wiring for Common Type U1 Type Connect the wires referring to the diagram. Note that the control wirings (Low voltages) shall be segregated from the power supply wires (High voltage) as follows: 1. Connect the Inter-unit control wiring to U1/U2 terminals and the remote control wire to R1/R2. (excepting K1 type). Earth screw 2. Connect the power supply wires to “L1, L2” of the terminal block.
Design of Mini VRF SYSTEM 3.
Design of Mini VRF SYSTEM 3.
Design of Mini VRF SYSTEM 3. Electrical Wiring 3-5. Important Note When Wiring for Y1 Type Connect the wires referring to the diagram. Note that the control wirings (Low Voltages) shall be segregated from the power supply wires (High Voltage) as follows: 1. Connect the Inter-unit control wiring to U1/U2 terminals and the remote control wire to R1/R2.
Design of Mini VRF SYSTEM 4. Installation Instructions 4-1. Selecting the Installation Site for Outdoor Unit Exhaust fan AVOID: Hot air heat sources, exhaust fans, etc.(Fig.2-6) damp, humid or uneven locations Heat source Outdoor unit DO: choose a place as cool as possible. choose a place that is well ventilated and outside air temperature does not exceed maximum 113°F constantly. Fig. 2-6 allow enough room around the unit for air intake/ exhaust and possible maintenance.(Fig.
Design of Mini VRF SYSTEM 4. Installation Instructions 4-2. Air Discharge Chamber for Top Discharge Be sure to install an air discharge chamber (field supply) in the field when: it is difficult to keep a space of min.20 in.between the air discharge outlet and an obstacle. Air discharge the air discharge outlet is facing a sidewalk and discharged hot air may annoy passers-by. Refer to Fig.2-10. 4-3.
Design of Mini VRF SYSTEM 4. Installation Instructions Unit front, air discharge chamber 2 Unit left side, air discharge chamber 3 Unit right side, air discharge chamber 4 Reinforcement brackets, 4 locations 9-7/16 3 4 1 21-5/32 Rectangular hole 9-27/32 22-13/32 21-13/32 1 Unit:in.
Design of Mini VRF SYSTEM 4. Installation Instructions Reference for air-discharge chamber (field supply) Required space around outdoor unit If an air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. Min. 39-3/8 Min. 7-7/8 (1) Single-unit installation Unit:in. CAUTION The top and both sides must remain open.
Design of Mini VRF SYSTEM 4. Installation Instructions 4-7. Dimensions of Snow Ducting Reference diagram for snow-proof ducting (field supply) Fastened by screws at 13 locations 30-3/32 1 Unit top, snow-proof vent 2 Unit left side 3 Unit right side 4 Unit reverse side 4 Unit: in.
Design of Mini VRF SYSTEM 4. Installation Instructions Reference diagram for snow-proof ducting – 1 Space requirements for setting – (1) [Obstacle to the front of unit] [Obstacle to the rear of unit] Top is open: (1) Single-unit installation Min. D Min. A Min. H Top is open: (1) Single-unit installation (2) Obstacles on both sides Min. B Min. C (2) Multiple-unit installation (2 or more units) 1 Min. I Min. G Min. I Min. J (3) Multiple-unit installation (2 or more units) H Min. E Min.
Design of Mini VRF SYSTEM 4. Installation Instructions Reference diagram for snow-proof ducting – 2 Space requirements for setting – (2) [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit. Q Min. O Min. P (1) Single-unit installation Dimension Q If a snow protection duct is attached after the unit is installed, verify that dimension Q is 19-11/16" or more.
Design of Mini VRF SYSTEM 4. Installation Instructions 4-9. Installing the Outdoor Unit 33/64 4-3/8 25/32 25/64 25-63/64 8-5/8 5-29/32 33/64 14-61/64 15-15/16 33/64 33/64 3/4 19/32 Be sure to anchor the feet with the anchor bolts (M10 or 3/8"). In addition, use anchoring washers on the top side. (Use large square 1-1/4"×1-1/4" SUS washers with diameters of 3/8".
Design of Mini VRF SYSTEM 5. HOW TO PROCESS TUBING 5. HOW TO PROCESS TUBING Deburring 5-1. Connecting the Refrigerant Tubing After Before Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units.In this method, the copper tubes are flared at each end and connected with flare nuts. Flaring Procedure with a Flare Tool (1) Cut the copper tube to the required length with a tube cutter.
Design of Mini VRF SYSTEM 5. HOW TO PROCESS TUBING Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. Apply refrigerant lubricant (2) Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig.2-18) Fig.
Design of Mini VRF SYSTEM 5. HOW TO PROCESS TUBING 5-3. Insulating the Refrigerant Tubing Tubing Insulation Thermal insulation must be applied to all unit tubing, including distribution joint (purchased separately). * For gas tubing, the insulation material must be heat resistant to 248°F or above. For other tubing, it must be heat resistant to 176°F or above. Insulation material thickness must be 25/64" or greater.
Design of Mini VRF SYSTEM 5. HOW TO PROCESS TUBING 5-4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent the condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing. Clamp Insulated tubes Drain hose (2) Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall.
Design of Mini VRF SYSTEM 6. AIR PURGING 6. AIR PURGING Manifold gauge Air and moisture in the refrigerant system may have undesirable effects as indicated below. pressure in the system rises operating current rises cooling (or heating) efficiency drops moisture in the refrigerant circuit may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant system Fig.
Design of Mini VRF SYSTEM 6. AIR PURGING (3) Do a leak test of all joints of the tubing (both indoor and outdoor) and both gas tube and liquid tube service valves. Bubbles indicate a leak. Wipe off the soap with a clean cloth after the leak test. (4) After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Design of Mini VRF SYSTEM 6. AIR PURGING CAUTION Use a cylinder designed for use with R410A. Manifold valve Pressure gauge Charging additional refrigerant Lo Hi Charging additional refrigerant (calculated from the liquid tube length as shown in Section 2-7 “Additional Refrigerant Charge”) using the liquid tube service valve. (Fig. 2-29) Valve Use a balance to measure the refrigerant accurately.
Design of Mini VRF SYSTEM 7. Optional Parts 7-1. Distribution Joint Kits CZ-P160BK1U (for R410A) Size of connection point on each part (Shown are inside diameters of tubing) How to Attach Distribution Joint 1. Accompanying Parts Check the contents of your distribution joint kit. 2. Distribution Joint Kits (with insulation) Parts Kit 1 Parts Kit 2 4-21/64 4-21/64 3-13/16 3-13/16 C A B B unit : inch C DE mm Inch Part A o19.05 3/4 Part B o15.88 5/8 Part C o12.7 1/2 Part D o9.
– MEMO – 2 - 46 TD831156-00_MINI_VRF_SYS.
Control of Mini VRF SYSTEM Contents 3. CONTROL OF MINI VRF SYSTEM 1. Main Operating Functions 2. Wireless Remote Controller 3. Timer Remote Controller 4. Simplified Remote Controller 5. System Controller 6. Schedule Timer 7. Intelligent Controller (CZ-256ESMC1U) 8. Communication Adaptor (CZ-CFUNC1U) 9. Remote Sensor 10. LonWorks Interface (CZ-CLNC1U) * Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157) 1 2 3 4 5 6 7 8 3-1 TD831156-00_MINI_VRF_SYS.
– MEMO – 3-2 TD831156-00_MINI_VRF_SYS.
Mini VRF SYSTEM Unit Specifications Contents 4. MINI VRF SYSTEM UNIT SPECIFICATIONS 1. Outdoor Unit ..................................................................................................................... 4-2 1-1. Specifications ............................................................................................................. 4-2 1-2. AHRI Registration Values .......................................................................................... 4-4 1-3. Dimensional Data .......
Mini VRF SYSTEM Unit Specifications 1. Outdoor Unit 1-1. Specifications Unit specifications (A) MODEL No. 1 Outdoor Unit U-36LE1U6, U-36LE1U6E* POWER SOURCE 208 - 230 V / 1ø / 60 Hz PERFORMANCE Capacity Air circulation (Hi) Cooling Heating BTU / h 38,200 42,700 kW 11.2 12.5 CFM 3,530 ELECTRICAL RATINGS 1 Voltage rating V Available voltage range V 208 Running amperes A 14.6 13.6 14.6 13.6 Max. running amperes * A 23.6 23.6 – – Power input kW 2.76 2.76 2.88 2.88 Max.
Mini VRF SYSTEM Unit Specifications 1. Outdoor Unit Unit specifications (B) MODEL No. 1 Outdoor Unit U-52LE1U6, U-52LE1U6E* POWER SOURCE 208 - 230 V / 1ø / 60 Hz PERFORMANCE Capacity Air circulation (Hi) Cooling Heating BTU / h 52,900 60,000 kW 15.5 17.6 CFM 3,530 ELECTRICAL RATINGS Voltage rating V Available voltage range V 208 230 208 Running amperes A 23.5 21.9 23.5 21.9 Max. running amperes * A 28.0 28.0 – – Power input kW 4.57 4.57 4.58 4.58 Max.
Mini VRF SYSTEM Unit Specifications 1. Outdoor Unit 1-2. AHRI Registration Values Cooling Capacity EER BTU/h 95°F Ducted 37,000 9.60 13.1 38,500 7.8 Non Ducted 39,000 11.50 17.0 43,000 9.8 Mixed Non-Ducted and Duced 38,000 10.55 15.05 40,750 8.8 Ducted 51,500 9.40 14.6 57,500 7.7 Non Ducted 52,000 10.20 17.4 58,500 9.6 Mixed Non-Ducted and Duced 51,750 9.80 16.0 58,000 8.
Unit: inch Auxiliary connection tube ø5/8'' to ø3/4'' (ø15.88 to ø19.
Mini VRF SYSTEM Unit Specifications 1. Outdoor Unit 1-4. Refrigerant Flow Diagram U-36LE1U6 U-36LE1U6E U-52LE1U6 U-52LE1U6E Suction 1 2 3 4 5 6 7 8 4-6 TD831156-00_MINI_VRF_SYS.
Mini VRF SYSTEM Unit Specifications 1. Outdoor Unit 1-5. Sound Data (1) Sound Power Level U-36LE1U6, U-36LE1U6E Model U-36LE1U6, U-36LE1U6E Sound Power Level 67 dB (A) Cooling Condition 90 80 NC – 70 Sound Power Level (dB) 70 60 NC – 60 50 NC – 50 40 NC – 40 30 NC – 30 20 1 2 3 4 5 NC – 20 6 10 63 125 250 500 1000 2000 4000 Frequency at center of sound pressure band (Hz) 8000 7 NOTE 1. dBA = A – weighted sound power level (A – scale according to IEC) 2.
Mini VRF SYSTEM Unit Specifications 1. Outdoor Unit U-52LE1U6, U-52LE1U6E Model U-52LE1U6, U-52LE1U6E Sound Power Level 68 dB (A) Cooling Condition 90 80 NC – 70 1 2 3 Sound Power Level (dB) 70 60 NC – 60 50 NC – 50 40 4 30 5 20 10 6 NC – 40 NC – 30 NC – 20 63 125 250 500 1000 2000 4000 8000 Frequency at center of sound pressure band (Hz) NOTE 7 1. dBA = A – weighted sound power level (A – scale according to IEC) 2.
Mini VRF SYSTEM Unit Specifications 1. Outdoor Unit (2) Sound Pressure Level U-36LE1U6, U-36LE1U6E Model U-36LE1U6, U-36LE1U6E Sound Pressure Level Cooling Front 51 dB (A) Quiet Mode 48 dB (A) Condition 3.3 ft. in front at height of 4.9 ft.
Mini VRF SYSTEM Unit Specifications 1. Outdoor Unit U-52LE1U6, U-52LE1U6E Model U-52LE1U6, U-52LE1U6E Sound Pressure Level Cooling Front 52 dB (A) Quiet Mode 49 dB (A) Condition 3.3 ft. in front at height of 4.9 ft.
Test Run Contents 5. TEST RUN 1. Preparing for Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 2. Test Run Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3 3. Outdoor Unit PCB Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test Run 1. Preparing for Test Run ● Before attempting to start the air conditioner, check the following. (1) All loose matter is removed from the cabinet, especially steel filings, bits of wire, and clips. ON (2) The control wiring is correctly connected and all electrical connections are tight. (Power must be turned ON at least 5 hours before attempting test run) (3) The transportation pads for the indoor fan have been removed. If not, remove them now.
Test Run 2. Test Run Procedure Items to Check Before the Test Run 1. Turn the remote power switch on at least 5 hours before the test, in order to energize the crankcase heater. 2. Turn the outdoor service valves (2 locations) to the full-open positions. Recheck the items to check before the test run. ● Unit No. setting switch (S004) Set the No. of indoor units. ● (Check the link wiring.
Test Run 3. Outdoor Unit PCB Setting 1 2 CN33 3 4 CN51 5 CN50 S003 S002 6 D043 (LED2) S004 D042 (LED1) 7 8 Fig. 5-4 5-4 TD831156-00_MINI_VRF_SYS.
Test Run 3. Outdoor Unit PCB Setting Examples of the No. of indoor units settings No. of indoor units Indoor unit setting (S004) (Rotary switch, red) 1 Set to 1 1 unit (factory setting) Set to 2 9 9 units 2 2 units Set to 9 Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) System address No.
Test Run 4. Auto Address Setting Basic wiring diagram: Example (1) • If link wiring is not used (The inter-unit control wires are not connected to multiple refrigerant systems.) Indoor unit addresses can be set without operating the compressors. No. 1 unit settings (S004) System address (system 1 setting) (S003) ON 1 2 No. of indoor units (8 units setting) (S004) (S002) ON 1 8 OFF Unit No.
Test Run 4. Auto Address Setting Basic wiring diagram: Example (2) • If link wiring is used No. 1 unit settings System address (system 1 setting) (S003) No. of indoor units (6 units setting) (S004) (S002) ON ON * When multiple outdoor units exist, remove the socket that is used to short-circuit the terminal plug (CN33) from all outdoor unit PCBs except for 1. Alternatively, move the sockets to the “OPEN” side .
Test Run 4. Auto Address Setting Case 1 Automatic Address Setting (no compressor operation) ● Indoor and outdoor unit power can be turned ON for each system separately. Indoor unit addresses can be set without operating the compressors. Automatic Address Setting from Outdoor Unit 1. On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the ON (These are the settings at the time of factory shipment.) DIP switch (S003) is set to “0.” ON 1 2 OFF 2.
Test Run 4. Auto Address Setting Case 2 Automatic Address Setting in Heating Mode ● Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work. Automatic Address Setting from Outdoor Unit 1. Perform steps 1 and 2 in the same way as for Case 1 . 2.
Test Run 4. Auto Address Setting Case 3 Automatic Address Setting in Cooling Mode ● Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work. Automatic address setting can be performed during Cooling operation. Automatic Address Setting from Outdoor Unit 1.
Test Run 4. Auto Address Setting Display during automatic address setting ● On outdoor unit PCB LED 2 1 Blink alternately * Do not short-circuit the automatic address setting pin (CN51) again while automatic address setting is in progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn OFF. * When automatic address setting has been successfully completed, both LEDs 1 and 2 turn OFF. * LED 1 is D042. LED 2 is D043.
Test Run 4. Auto Address Setting 5. Remote Controller Test Run Settings Request concerning recording the indoor/outdoor unit combination Nos. After automatic address setting has been completed, be sure to record them for future reference. List the outdoor unit system address and the addresses of the indoor units in that system in an easily visible location (next to the nameplate), using a permanent marking pen or similar means that cannot be erased easily.
Test Run 6. Caution for Pump Down 7. Meaning of Alarm Messages 6. Caution for Pump Down Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be moved, or before servicing the refrigerant circuit. ● This outdoor unit cannot collect more than the rated refrigerant amount as shown by the nameplate on the back. ● If the amount of refrigerant is more than that recommended, do not conduct pump down.
Test Run 7. Meaning of Alarm Messages Alarm message Possible cause of malfunction Serial communication errors Mis-setting Improper setting. This alarm message shows when the indoor unit for multiple-use is not connected to the outdoor unit. L02 Duplication of main indoor unit address setting in group control. Duplication of outdoor R.C. address setting. There are 2 or more indoor units Priority set remote controller controllers which have operation mode priority in 1 refrigerant circuit.
Electrical Data Contents 6. ELECTRICAL DATA 1. Outdoor Unit ...................................................................................................................... 6-2 (1) Electric Wiring Diagram U-36LE1U6, U-36LE1U6E .................................................. 6-2 (2) Electric Wiring Diagram U-52LE1U6, U-52LE1U6E .................................................. 6-4 2.
Electrical Data 1. Outdoor Unit (1) Electric Wiring Diagram U-36LE1U6, U-36LE1U6E 1 2 3 4 5 6 7 8 6-2 TD831156-00_MINI_VRF_SYS.
Electrical Data 1. Outdoor Unit Schematic Diagram U-36LE1U6, U-36LE1U6E 1 2 3 4 5 6 7 8 6-3 TD831156-00_MINI_VRF_SYS.
Electrical Data 1. Outdoor Unit (2) Electric Wiring Diagram U-52LE1U6, U-52LE1U6E 1 2 3 4 5 6 7 8 6-4 TD831156-00_MINI_VRF_SYS.
Electrical Data 1. Outdoor Unit Schematic Diagram U-52LE1U6, U-52LE1U6E 1 2 3 4 5 6 7 8 6-5 TD831156-00_MINI_VRF_SYS.
– MEMO – 6-6 TD831156-00_MINI_VRF_SYS.
PCB and Functions Contents 7. PCB AND FUNCTIONS 1. Outdoor Unit Control PCB ................................................................................................ 7-2 1-1. Outdoor Unit Control PCB CR-CHX06052 .................................................................... 7-2 1-2. Outdoor Unit HIC Board HIC-CHDX14053 ....................................................................7-3 1-3. Functions (for CR-CHX06052) .......................................................................
PCB and Functions 1. Outdoor Unit Control PCB 1-1. Outdoor Unit Control PCB CR-CHX06052 1 2 3 4 5 6 7 8 7-2 TD831156-00_MINI_VRF_SYS.
PCB and Functions 1. Outdoor Unit Control PCB 1-2. Outdoor Unit HIC Board HIC-CHDX14053 1 2 3 4 5 6 7 8 7-3 TD831156-00_MINI_VRF_SYS.
PCB and Functions 1. Outdoor Unit Control PCB 1-3. Functions (for CR-CHX06052) CN51 2P plug (black): Automatic address setting pin • If the system address switch (S002: Factory setting is 0) is set to other than 0 (centralized control), press this switch once to automatically set the address of the indoor unit to the connected outdoor unit within the same system. While the automatic address setting is in progress, 2 LEDs (red) on the outdoor unit control PCB blinks alternately.
PCB and Functions 1. Outdoor Unit Control PCB CN15 The control operations that are shown below are when you short-circuit this cooling inspection pin located on the outdoor unit control PCB. 1.Thermistor inspection Thermistor Discharge temperature (TD) Outdoor temperature (TO) Heat exchanger temperature (C1) Heat exchanger temperature (C2) Air inlet temperature (TS) Detection results Normal Error LED1 lights up LED2 lights up LED1, 2 turns off LED1 lights up LED2 lights up LED1 lights up ↓ 2.
PCB and Functions 1. Outdoor Unit Control PCB Table 7-1. Setting the System Address [S002: Rotary switch (black), S003: 2P DIP (green or blue)] Outdoor system address No.
Capacity Table Contents 8. CAPACITY TABLE 1. Capacity Ratio of Outdoor Unit ........................................................................................ 8-2 1-1. U-36LE1U6, U-36LE1U6E (Cooling) ............................................................................ 8-2 1-2. U-36LE1U6, U-36LE1U6E (Heating) ............................................................................8-4 1-3. U-52LE1U6, U-52LE1U6E (Cooling) .....................................................................
Capacity Table 1. Capacity Ratio of Outdoor Unit 1-1. U-36LE1U6, U-36LE1U6E (Cooling) MINI VRF Capacity Ratio 50-130% Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 130% -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.0 Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 120% 1 2 3 4 Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 110% 100% 6 8 -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.
Capacity Table 1. Capacity Ratio of Outdoor Unit MINI VRF Capacity Ratio 50-130% Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 80% -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.0 Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 70% -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.0 Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 60% -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.
Capacity Table 1. Capacity Ratio of Outdoor Unit 1-2. U-36LE1U6, U-36LE1U6E (Heating) MINI VRF Capacity Ratio 50-130% Combination(%): Indoor/outdoor capacity ratio 130% Combination(%): Indoor/outdoor capacity ratio 120% 1 2 3 4 Combination(%): Indoor/outdoor capacity ratio 110% Combination(%): Indoor/outdoor capacity ratio 5 100% 6 7 Combination(%): Indoor/outdoor capacity ratio 90% 8 Outdoor air temp. DB -19.8 -14.7 -9.6 -4.4 -1.8 0.8 2.8 6.0 7.0 8.6 11.2 16.4 WB -20.0 -15.0 -10.0 -5.0 -2.
Capacity Table 1. Capacity Ratio of Outdoor Unit MINI VRF Capacity Ratio 50-130% Combination(%): Indoor/outdoor capacity ratio 80% Combination(%): Indoor/outdoor capacity ratio 70% Combination(%): Indoor/outdoor capacity ratio 60% Combination(%): Indoor/outdoor capacity ratio 50% Outdoor air temp. DB -19.8 -14.7 -9.6 -4.4 -1.8 0.8 2.8 6.0 7.0 8.6 11.2 16.4 WB -20.0 -15.0 -10.0 -5.0 -2.5 0.0 2.0 5.0 6.0 7.5 10.0 15.0 Outdoor air temp. DB -19.8 -14.7 -9.6 -4.4 -1.8 0.8 2.8 6.0 7.0 8.6 11.2 16.
Capacity Table 1. Capacity Ratio of Outdoor Unit 1-3. U-52LE1U6, U-52LE1U6E (Cooling) MINI VRF Capacity Ratio 50-130% Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 130% -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.0 Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 120% 1 2 3 4 Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 110% 100% 6 8 -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.
Capacity Table 1. Capacity Ratio of Outdoor Unit MINI VRF Capacity Ratio 50-130% Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 80% -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.0 Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 70% -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.0 Combination(%): Outdoor Indoor/outdoor air temp. capacity ratio °CDB 60% -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 43.
Capacity Table 1. Capacity Ratio of Outdoor Unit 1-4. U-52LE1U6, U-52LE1U6E (Heating) MINI VRF Capacity Ratio 50-130% Combination(%): Indoor/outdoor capacity ratio 130% Combination(%): Indoor/outdoor capacity ratio 120% 1 2 3 4 Combination(%): Indoor/outdoor capacity ratio 110% Combination(%): Indoor/outdoor capacity ratio 5 100% 6 7 Combination(%): Indoor/outdoor capacity ratio 90% 8 Outdoor air temp. DB -19.8 -14.7 -9.6 -4.4 -1.8 0.8 2.8 6.0 7.0 8.6 11.2 16.4 WB -20.0 -15.0 -10.0 -5.0 -2.
Capacity Table 1. Capacity Ratio of Outdoor Unit MINI VRF Capacity Ratio 50-130% Combination(%): Indoor/outdoor capacity ratio 80% Combination(%): Indoor/outdoor capacity ratio 70% Combination(%): Indoor/outdoor capacity ratio 60% Combination(%): Indoor/outdoor capacity ratio 50% Outdoor air temp. DB -19.8 -14.7 -9.6 -4.4 -1.8 0.8 2.8 6.0 7.0 8.6 11.2 16.4 WB -20.0 -15.0 -10.0 -5.0 -2.5 0.0 2.0 5.0 6.0 7.5 10.0 15.0 Outdoor air temp. DB -19.8 -14.7 -9.6 -4.4 -1.8 0.8 2.8 6.0 7.0 8.6 11.2 16.
Capacity Table 2. Cooling Capacity of Indoor Unit 2-1. 4-Way Cassette Type (U1 Type), 4-Way Cassette 60×60 Type (Y1 Type) S-12MU1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 15.5 m3/min 3.6 kW TC 15 2.6 17 2.6 19 2.6 21 2.6 23 2.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.6 2.6 2.6 2.6 21 23 25 27 SHC SHC SHC SHC TC 2.4 2.6 2.6 2.6 2.9 2.4 2.6 2.6 2.6 2.9 2.4 2.6 2.6 2.6 2.9 2.4 2.6 2.6 2.6 2.9 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-18MU1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 16.0 m3/min 5.6 kW TC 15 4.1 17 4.1 19 4.1 21 4.1 23 4.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 4.1 4.1 4.1 4.1 21 23 25 27 SHC SHC SHC SHC TC 3.3 3.8 4.1 4.1 4.5 3.3 3.8 4.1 4.1 4.5 3.3 3.8 4.1 4.1 4.5 3.3 3.8 4.1 4.1 4.5 3.3 3.8 4.1 4.1 4.5 3.3 3.8 4.1 4.1 4.5 3.3 3.8 4.1 4.1 4.5 3.3 3.8 4.1 4.
Capacity Table 2. Cooling Capacity of Indoor Unit S-24MU1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 20.0 m3/min 7.3 kW TC 15 5.4 17 5.4 19 5.4 21 5.4 23 5.4 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 5.4 5.4 5.4 5.4 21 23 25 27 SHC SHC SHC SHC TC 4.1 4.7 5.4 5.4 5.8 4.1 4.7 5.4 5.4 5.8 4.1 4.7 5.4 5.4 5.8 4.1 4.7 5.4 5.4 5.8 4.1 4.7 5.4 5.4 5.8 4.1 4.7 5.4 5.4 5.8 4.1 4.7 5.4 5.4 5.8 4.1 4.7 5.4 5.
Capacity Table 2. Cooling Capacity of Indoor Unit S-36MU1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 28.0 m3/min 10.6 kW TC 15 7.8 17 7.8 19 7.8 21 7.8 23 7.8 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 7.8 7.8 7.8 7.8 21 23 25 27 SHC SHC SHC SHC TC 5.7 6.5 7.4 7.8 8.5 5.7 6.5 7.4 7.8 8.5 5.7 6.5 7.4 7.8 8.5 5.7 6.5 7.4 7.8 8.5 5.7 6.5 7.4 7.8 8.5 5.7 6.5 7.4 7.8 8.5 5.7 6.5 7.4 7.8 8.5 5.7 6.5 7.
Capacity Table 2. Cooling Capacity of Indoor Unit S-12MY1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 3.6 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 9.0 m3/min TC 15 2.6 17 2.6 19 2.6 21 2.6 23 2.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.6 2.6 2.6 2.6 21 23 25 27 SHC SHC SHC SHC TC 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-18MY1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 12.5 m3/min 5.6 kW TC 15 4.1 17 4.1 19 4.1 21 4.1 23 4.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 4.1 4.1 4.1 4.1 21 23 25 27 SHC SHC SHC SHC TC 3.2 3.7 4.1 4.1 4.5 3.2 3.7 4.1 4.1 4.5 3.2 3.7 4.1 4.1 4.5 3.2 3.7 4.1 4.1 4.5 3.2 3.7 4.1 4.1 4.5 3.2 3.7 4.1 4.1 4.5 3.2 3.7 4.1 4.1 4.5 3.2 3.7 4.1 4.
Capacity Table 2. Cooling Capacity of Indoor Unit 2-2. 1-Way Cassette Type (D1 Type) S-07MD1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 2.2 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 8.0 m3/min TC 15 1.6 17 1.6 19 1.6 21 1.6 23 1.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 1.6 1.6 1.6 1.6 21 23 25 27 SHC SHC SHC SHC TC 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.
Capacity Table 2. Cooling Capacity of Indoor Unit S-09MD1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 2.8 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 8.0 m3/min TC 15 2.1 17 2.1 19 2.1 21 2.1 23 2.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.1 2.1 2.1 2.1 21 23 25 27 SHC SHC SHC SHC TC 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-12MD1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 3.6 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 9.0 m3/min TC 15 2.6 17 2.6 19 2.6 21 2.6 23 2.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.6 2.6 2.6 2.6 21 23 25 27 SHC SHC SHC SHC TC 2.0 2.3 2.6 2.6 2.9 2.0 2.3 2.6 2.6 2.9 2.0 2.3 2.6 2.6 2.9 2.0 2.3 2.6 2.6 2.9 2.0 2.3 2.6 2.6 2.9 2.0 2.3 2.6 2.6 2.9 2.0 2.3 2.6 2.6 2.9 2.0 2.3 2.6 2.
Capacity Table 2. Cooling Capacity of Indoor Unit 2-3. Wall Mounted Type (K1 Type) S-07MK1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 10.0 m3/min 2.2 kW TC 15 1.6 17 1.6 19 1.6 21 1.6 23 1.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 1.6 1.6 1.6 1.6 21 23 25 27 SHC SHC SHC SHC TC 1.4 1.6 1.6 1.6 1.8 1.4 1.6 1.6 1.6 1.8 1.4 1.6 1.6 1.6 1.8 1.4 1.6 1.6 1.6 1.8 1.4 1.6 1.6 1.6 1.8 1.4 1.6 1.6 1.6 1.8 1.
Capacity Table 2. Cooling Capacity of Indoor Unit S-09MK1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 10.0 m3/min 2.8 kW TC 15 2.1 17 2.1 19 2.1 21 2.1 23 2.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.1 2.1 2.1 2.1 21 23 25 27 SHC SHC SHC SHC TC 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-12MK1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 10.0 m3/min 3.6 kW TC 15 2.6 17 2.6 19 2.6 21 2.6 23 2.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.6 2.6 2.6 2.6 21 23 25 27 SHC SHC SHC SHC TC 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-18MK1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 16.0 m3/min 5.3 kW TC 15 3.9 17 3.9 19 3.9 21 3.9 23 3.9 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 3.9 3.9 3.9 3.9 21 23 25 27 SHC SHC SHC SHC TC 3.1 3.6 3.9 3.9 4.2 3.1 3.6 3.9 3.9 4.2 3.1 3.6 3.9 3.9 4.2 3.1 3.6 3.9 3.9 4.2 3.1 3.6 3.9 3.9 4.2 3.1 3.6 3.9 3.9 4.2 3.1 3.6 3.9 3.9 4.2 3.1 3.6 3.9 3.
Capacity Table 2. Cooling Capacity of Indoor Unit S-19MS1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 16.0 m3/min 5.6 kW TC 15 4.1 17 4.1 19 4.1 21 4.1 23 4.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 4.1 4.1 4.1 4.1 21 23 25 27 SHC SHC SHC SHC TC 3.2 3.8 4.1 4.1 4.5 3.2 3.8 4.1 4.1 4.5 3.2 3.8 4.1 4.1 4.5 3.2 3.8 4.1 4.1 4.5 3.2 3.8 4.1 4.1 4.5 3.2 3.8 4.1 4.1 4.5 3.2 3.8 4.1 4.1 4.5 3.2 3.8 4.1 4.
Capacity Table 2. Cooling Capacity of Indoor Unit S-24MK1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 16.0 m3/min 7.3 kW TC 15 5.4 17 5.4 19 5.4 21 5.4 23 5.4 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 5.4 5.4 5.4 5.4 21 23 25 27 SHC SHC SHC SHC TC 3.7 4.2 4.7 5.1 5.8 3.7 4.2 4.7 5.1 5.8 3.7 4.2 4.7 5.1 5.8 3.7 4.2 4.7 5.1 5.8 3.7 4.2 4.7 5.1 5.8 3.7 4.2 4.7 5.1 5.8 3.7 4.2 4.7 5.1 5.8 3.7 4.2 4.7 5.
Capacity Table 2. Cooling Capacity of Indoor Unit 2-4. Ceiling Type (T1 Type) S-12MT1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 12.0 m3/min 3.6 kW TC 15 2.6 17 2.6 19 2.6 21 2.6 23 2.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.6 2.6 2.6 2.6 21 23 25 27 SHC SHC SHC SHC TC 1.9 2.2 2.5 2.6 2.9 1.9 2.2 2.5 2.6 2.9 1.9 2.2 2.5 2.6 2.9 1.9 2.2 2.5 2.6 2.9 1.9 2.2 2.5 2.6 2.9 1.9 2.2 2.5 2.6 2.9 1.9 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-18MT1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 13.0 m3/min 5.6 kW TC 15 4.1 17 4.1 19 4.1 21 4.1 23 4.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 4.1 4.1 4.1 4.1 21 23 25 27 SHC SHC SHC SHC TC 2.8 3.2 3.5 3.8 4.5 2.8 3.2 3.5 3.8 4.5 2.8 3.2 3.5 3.8 4.5 2.8 3.2 3.5 3.8 4.5 2.8 3.2 3.5 3.8 4.5 2.8 3.2 3.5 3.8 4.5 2.8 3.2 3.5 3.8 4.5 2.8 3.2 3.5 3.
Capacity Table 2. Cooling Capacity of Indoor Unit S-24MT1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 18.5 m3/min 7.3 kW TC 15 5.4 17 5.4 19 5.4 21 5.4 23 5.4 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 5.4 5.4 5.4 5.4 21 23 25 27 SHC SHC SHC SHC TC 3.8 4.3 4.9 5.4 5.8 3.8 4.3 4.9 5.4 5.8 3.8 4.3 4.9 5.4 5.8 3.8 4.3 4.9 5.4 5.8 3.8 4.3 4.9 5.4 5.8 3.8 4.3 4.9 5.4 5.8 3.8 4.3 4.9 5.4 5.8 3.8 4.3 4.9 5.
Capacity Table 2. Cooling Capacity of Indoor Unit 2-5. Low Silhouette Ducted Type (F1 Type), Slim Low Static Ducted Type (M1 Type) S-07MF1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 10.0 m3/min 2.2 kW TC 15 1.6 17 1.6 19 1.6 21 1.6 23 1.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 1.6 1.6 1.6 1.6 21 23 25 27 SHC SHC SHC SHC TC 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.
Capacity Table 2. Cooling Capacity of Indoor Unit S-09MF1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 10.0 m3/min 2.8 kW TC 15 2.1 17 2.1 19 2.1 21 2.1 23 2.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.1 2.1 2.1 2.1 21 23 25 27 SHC SHC SHC SHC TC 1.6 1.8 2.1 2.1 2.2 1.6 1.8 2.1 2.1 2.2 1.6 1.8 2.1 2.1 2.2 1.6 1.8 2.1 2.1 2.2 1.6 1.8 2.1 2.1 2.2 1.6 1.8 2.1 2.1 2.2 1.6 1.8 2.1 2.1 2.2 1.6 1.8 2.1 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-12MF1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 10.0 m3/min 3.6 kW TC 15 2.6 17 2.6 19 2.6 21 2.6 23 2.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.6 2.6 2.6 2.6 21 23 25 27 SHC SHC SHC SHC TC 1.9 2.2 2.4 2.6 2.9 1.9 2.2 2.4 2.6 2.9 1.9 2.2 2.4 2.6 2.9 1.9 2.2 2.4 2.6 2.9 1.9 2.2 2.4 2.6 2.9 1.9 2.2 2.4 2.6 2.9 1.9 2.2 2.4 2.6 2.9 1.9 2.2 2.4 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-15MF1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 12.0 m3/min 4.5 kW TC 15 3.3 17 3.3 19 3.3 21 3.3 23 3.3 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 3.3 3.3 3.3 3.3 21 23 25 27 SHC SHC SHC SHC TC 2.4 2.8 3.1 3.3 3.6 2.4 2.8 3.1 3.3 3.6 2.4 2.8 3.1 3.3 3.6 2.4 2.8 3.1 3.3 3.6 2.4 2.8 3.1 3.3 3.6 2.4 2.8 3.1 3.3 3.6 2.4 2.8 3.1 3.3 3.6 2.4 2.8 3.1 3.
Capacity Table 2. Cooling Capacity of Indoor Unit S-18MF1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 12.0 m3/min 5.6 kW TC 15 4.1 17 4.1 19 4.1 21 4.1 23 4.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 4.1 4.1 4.1 4.1 21 23 25 27 SHC SHC SHC SHC TC 2.9 3.3 3.7 4.1 4.5 2.9 3.3 3.7 4.1 4.5 2.9 3.3 3.7 4.1 4.5 2.9 3.3 3.7 4.1 4.5 2.9 3.3 3.7 4.1 4.5 2.9 3.3 3.7 4.1 4.5 2.9 3.3 3.7 4.1 4.5 2.9 3.3 3.7 4.
Capacity Table 2. Cooling Capacity of Indoor Unit S-24MF1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 19.0 m3/min 7.3 kW TC 15 5.4 17 5.4 19 5.4 21 5.4 23 5.4 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 5.4 5.4 5.4 5.4 21 23 25 27 SHC SHC SHC SHC TC 3.7 4.1 4.6 5.0 5.8 3.7 4.1 4.6 5.0 5.8 3.7 4.1 4.6 5.0 5.8 3.7 4.1 4.6 5.0 5.8 3.7 4.1 4.6 5.0 5.8 3.7 4.1 4.6 5.0 5.8 3.7 4.1 4.6 5.0 5.8 3.7 4.1 4.6 5.
Capacity Table 2. Cooling Capacity of Indoor Unit S-36MF1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 30.0 m3/min 10.6 kW TC 15 7.8 17 7.8 19 7.8 21 7.8 23 7.8 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 7.8 7.8 7.8 7.8 21 23 25 27 SHC SHC SHC SHC TC 5.7 6.4 7.2 7.8 8.5 5.7 6.4 7.2 7.8 8.5 5.7 6.4 7.2 7.8 8.5 5.7 6.4 7.2 7.8 8.5 5.7 6.4 7.2 7.8 8.5 5.7 6.4 7.2 7.8 8.5 5.7 6.4 7.2 7.8 8.5 5.7 6.4 7.
Capacity Table 2. Cooling Capacity of Indoor Unit S-48MF1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 33.0 m3/min 14.0 kW TC 15 10.3 17 10.3 19 10.3 21 10.3 23 10.3 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 10.3 10.3 10.3 10.3 21 23 25 27 SHC SHC SHC SHC TC 7.2 8.2 9.2 10.1 11.2 7.2 8.2 9.2 10.1 11.2 7.2 8.2 9.2 10.1 11.2 7.2 8.2 9.2 10.1 11.2 7.2 8.2 9.2 10.1 11.2 7.2 8.2 9.2 10.1 11.2 7.2 8.2 9.
Capacity Table 2. Cooling Capacity of Indoor Unit S-54MF1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 33.0 m3/min 16.0 kW TC 15 11.7 17 11.7 19 11.7 21 11.7 23 11.7 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 11.7 11.7 11.7 11.7 21 23 25 27 SHC SHC SHC SHC TC 8.0 9.0 10.0 11.0 12.8 8.0 9.0 10.0 11.0 12.8 8.0 9.0 10.0 11.0 12.8 8.0 9.0 10.0 11.0 12.8 8.0 9.0 10.0 11.0 12.8 8.0 9.0 10.0 11.0 12.8 8.0 9.
Capacity Table 2. Cooling Capacity of Indoor Unit S-07MM1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 2.2 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 8.0 m3/min TC 15 1.6 17 1.6 19 1.6 21 1.6 23 1.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 1.6 1.6 1.6 1.6 21 23 25 27 SHC SHC SHC SHC TC 1.6 1.6 1.6 1.6 1.8 1.6 1.6 1.6 1.6 1.8 1.6 1.6 1.6 1.6 1.8 1.6 1.6 1.6 1.6 1.8 1.6 1.6 1.6 1.6 1.8 1.6 1.6 1.6 1.6 1.8 1.6 1.6 1.6 1.6 1.8 1.6 1.6 1.6 1.
Capacity Table 2. Cooling Capacity of Indoor Unit S-09MM1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 2.8 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 8.5 m3/min TC 15 2.1 17 2.1 19 2.1 21 2.1 23 2.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.1 2.1 2.1 2.1 21 23 25 27 SHC SHC SHC SHC TC 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.1 2.2 1.8 2.1 2.1 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-12MM1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 3.6 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 9.0 m3/min TC 15 2.6 17 2.6 19 2.6 21 2.6 23 2.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.6 2.6 2.6 2.6 21 23 25 27 SHC SHC SHC SHC TC 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.6 2.9 2.2 2.5 2.6 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-15MM1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 10.5 m3/min 4.5 kW TC 15 3.3 17 3.3 19 3.3 21 3.3 23 3.3 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 3.3 3.3 3.3 3.3 21 23 25 27 SHC SHC SHC SHC TC 2.3 2.6 3.0 3.2 3.6 2.3 2.6 3.0 3.2 3.6 2.3 2.6 3.0 3.2 3.6 2.3 2.6 3.0 3.2 3.6 2.3 2.6 3.0 3.2 3.6 2.3 2.6 3.0 3.2 3.6 2.3 2.6 3.0 3.2 3.6 2.3 2.6 3.0 3.
Capacity Table 2. Cooling Capacity of Indoor Unit S-18MM1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 12.5 m3/min 5.6 kW TC 15 4.1 17 4.1 19 4.1 21 4.1 23 4.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 4.1 4.1 4.1 4.1 21 23 25 27 SHC SHC SHC SHC TC 3.1 3.6 4.1 4.1 4.5 3.1 3.6 4.1 4.1 4.5 3.1 3.6 4.1 4.1 4.5 3.1 3.6 4.1 4.1 4.5 3.1 3.6 4.1 4.1 4.5 3.1 3.6 4.1 4.1 4.5 3.1 3.6 4.1 4.1 4.5 3.1 3.6 4.1 4.
Capacity Table 2. Cooling Capacity of Indoor Unit 2-6. High Static Pressure Ducted Type (E1 Type) S-36ME1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 30.0 m3/min 10.6 kW TC 15 7.8 17 7.8 19 7.8 21 7.8 23 7.8 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 7.8 7.8 7.8 7.8 21 23 25 27 SHC SHC SHC SHC TC 6.3 7.4 7.8 7.8 8.5 6.3 7.4 7.8 7.8 8.5 6.3 7.4 7.8 7.8 8.5 6.3 7.4 7.8 7.8 8.5 6.3 7.4 7.8 7.8 8.5 6.3 7.
Capacity Table 2. Cooling Capacity of Indoor Unit S-48ME1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 36.0 m3/min 14.0 kW TC 15 10.3 17 10.3 19 10.3 21 10.3 23 10.3 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 10.3 10.3 10.3 10.3 21 23 25 27 SHC SHC SHC SHC TC 8.2 9.6 10.3 10.3 11.2 8.2 9.6 10.3 10.3 11.2 8.2 9.6 10.3 10.3 11.2 8.2 9.6 10.3 10.3 11.2 8.2 9.6 10.3 10.3 11.2 8.2 9.6 10.3 10.3 11.2 8.2 9.
Capacity Table 2. Cooling Capacity of Indoor Unit 2-7. Floor Standing Type (P1 Type) S-07MP1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 2.2 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 7.0 m3/min TC 15 1.6 17 1.6 19 1.6 21 1.6 23 1.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 1.6 1.6 1.6 1.6 21 23 25 27 SHC SHC SHC SHC TC 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.
Capacity Table 2. Cooling Capacity of Indoor Unit S-09MP1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 2.8 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 7.0 m3/min TC 15 2.1 17 2.1 19 2.1 21 2.1 23 2.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.1 2.1 2.1 2.1 21 23 25 27 SHC SHC SHC SHC TC 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-12MP1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 3.6 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 9.0 m3/min TC 15 2.6 17 2.6 19 2.6 21 2.6 23 2.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.6 2.6 2.6 2.6 21 23 25 27 SHC SHC SHC SHC TC 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-15MP1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 12.0 m3/min 4.5 kW TC 15 3.3 17 3.3 19 3.3 21 3.3 23 3.3 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 3.3 3.3 3.3 3.3 21 23 25 27 SHC SHC SHC SHC TC 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.
Capacity Table 2. Cooling Capacity of Indoor Unit S-18MP1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 15.0 m3/min 5.6 kW TC 15 4.1 17 4.1 19 4.1 21 4.1 23 4.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 4.1 4.1 4.1 4.1 21 23 25 27 SHC SHC SHC SHC TC 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.
Capacity Table 2. Cooling Capacity of Indoor Unit S-24MP1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 17.0 m3/min 7.1 kW TC 15 5.2 17 5.2 19 5.2 21 5.2 23 5.2 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 5.2 5.2 5.2 5.2 21 23 25 27 SHC SHC SHC SHC TC 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.
Capacity Table 2. Cooling Capacity of Indoor Unit 2-8. Concealed Floor Standing Type (R1 Type) S-07MR1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 2.2 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 7.0 m3/min TC 15 1.6 17 1.6 19 1.6 21 1.6 23 1.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 1.6 1.6 1.6 1.6 21 23 25 27 SHC SHC SHC SHC TC 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.6 1.6 1.8 1.3 1.5 1.
Capacity Table 2. Cooling Capacity of Indoor Unit S-09MR1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 2.8 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 7.0 m3/min TC 15 2.1 17 2.1 19 2.1 21 2.1 23 2.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.1 2.1 2.1 2.1 21 23 25 27 SHC SHC SHC SHC TC 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.1 2.2 1.6 1.9 2.1 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-12MR1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: 3.6 kW TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 9.0 m3/min TC 15 2.6 17 2.6 19 2.6 21 2.6 23 2.6 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 2.6 2.6 2.6 2.6 21 23 25 27 SHC SHC SHC SHC TC 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.6 2.9 2.1 2.4 2.6 2.
Capacity Table 2. Cooling Capacity of Indoor Unit S-15MR1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 12.0 m3/min 4.5 kW TC 15 3.3 17 3.3 19 3.3 21 3.3 23 3.3 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 3.3 3.3 3.3 3.3 21 23 25 27 SHC SHC SHC SHC TC 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.3 3.6 2.6 3.1 3.3 3.
Capacity Table 2. Cooling Capacity of Indoor Unit S-18MR1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 15.0 m3/min 5.6 kW TC 15 4.1 17 4.1 19 4.1 21 4.1 23 4.1 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 4.1 4.1 4.1 4.1 21 23 25 27 SHC SHC SHC SHC TC 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.1 4.5 3.3 3.9 4.1 4.
Capacity Table 2. Cooling Capacity of Indoor Unit S-24MR1U6 Power supply : 208 – 230V 1phase-60Hz RATING CAPACITY: TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) AIR FLOW 17.0 m3/min 7.1 kW TC 15 5.2 17 5.2 19 5.2 21 5.2 23 5.2 CONDENSER AMBIENT TEMP. (oC) 25 27 29 31 5.2 5.2 5.2 5.2 21 23 25 27 SHC SHC SHC SHC TC 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.2 5.7 4.1 4.7 5.2 5.
201201 TD831156-00_MINI_VRF_SYS.