Datasheet

19
LT4H
Operation type
Pulse One-shot
Explanation Time chart
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
Time delay starts and output control ON at
start ON.
Turns output control OFF and clears elapsed
time value at time-up.
• Ignores start input during time delay.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
In order to have the time delay start at power
ON or reset at power OFF, short out the start
input beforehand.
D
Pulse On delay
E
Signal Flicker
F
Totalizing On delay
G
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
T T
t1
t2
ta
T=t1+t2
T>ta
t
Stop
Start
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Tt2
T=t1+t2
T Tt1
Stop
Start
Reset
Output
Power supply
T>ta
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
t1 t1
T=t1+t2
T=t1+t2
tat2
t2
T
T T
Stop
Start
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
T
t1
t2 t3 ta
T=t1+t2+t3
T>ta
Stop
Start
Reset
Output
Power supply
123
ON ON OFF
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
• Time delay starts at start ON.
• Ignores start input during time delay.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
In order to have the time delay start at power
ON or reset at power OFF, short out the start
input beforehand.
123
OFF OFF ON
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
• Time delay starts at start ON.
• Ignores start input during time delay.
Output control reverses, elapsed time value
clears, and timer delay starts at timer comple-
tion.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
In order to have the time delay start at power
ON or reset at power OFF, short out the start
input beforehand.
123
ON OFF ON
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
Elapsed time value does not clear at power
ON. (power outage countermeasure function)
The output remains ON even after the power
is off and restarted.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
123
OFF ON ON
Notes: 1) Each signal input (start, reset, stop, and lock) is applied by shorting their input terminal to the common terminal (terminal Q for the 8-pin type, terminal E for
the 11-pin type, and ter- minal
6
for the screw terminal type).
2) The 8-pin type does not have a stop input or lock input.
6
Digital
Timers