LT4H
Operation mode
T: Set time t1, t2, t3, ta<T
Operation type
Power on delay (1)
Explanation Time chart
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
Clears elapsed time value and starts time
delay at power ON.
After timer completion, stops at the display of
the set value (addition), or stops at “0” (sub-
traction).
• Ignores start input.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
A
Power on delay (2)
A2
Signal on delay
B
Signal off delay
C
Stop
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Tt1
t2
t1+t2=T
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Tt1t2
t1+t2=T
Stop
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
T
t1
t2 t1+t2=T
Stop
Start
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
T
ta tb t
T>ta+tb T>t
Stop
Start
Reset
Output
Power supply
123
ON ON ON
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
Elapsed time value does not clear at power
ON. (power outage countermeasure function)
The output remains ON even after the power
is cut and restarted.
After timer completion, stops at the display of
the set value (addition), or stops at “0” (sub-
traction).
• Ignores start input.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
123
OFF OFF OFF
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
Time delay starts at start ON and elapsed
time value or output resets at start OFF.
Instantaneous time delay start at reset OFF
and power ON while start is ON.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
In order to have the time delay start at power
ON or reset at power OFF, short out the start
input beforehand.
123
ON OFF OFF
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
Output control ON at start ON and time delay
start at start OFF.
Elapsed time value clears when start goes ON
again during time delay.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
123
OFF ON OFF
Notes: 1) Each signal input (start, reset, stop, and lock) is applied by shorting their input terminal to the common terminal (terminal Q for the 8-pin type, terminal E for
the 11-pin type, and terminal for the screw terminal type).
2) The 8-pin type does not have a stop input or lock input.