Datasheet
80
Valve Regulated Lead-Acid Batteries
81
Valve Regulated Lead-Acid Batteries
Individual Data Sheets
11
5.21
M5
M5
8.11
Nominal voltage
12V
Nominal capacity (20 hour rate)
17Ah
Dimensions
Length
181mm
Width
76mm
Height
167mm
Total Height
167mm
Approx. mass
6.5kg
Terminal
M5 Bolt and Nut type/
M5 threaded post
Specifications
Dimensions (mm)
Duration of discharge vs Discharge current
1
3
5
10
30
60
3
5
10
20
30
Discharge current (A)
egrahcsid fo noitaruD
)etunim(
)ruoh(
40 °C
25 °C
0 °C
-15 °C
0.3 1 3 10 30 100
Capacity
(25°C)
20 hour rate
10 hour rate
5 hour rate
1 hour rate
17Ah
15Ah
13Ah
10Ah
Internal resistance
Fully charged battery
(25°C)
12mΩ
Temperature dependency
of capacity (20 hour rate)
40°C
25°C
0°C
-15°C
102%
100%
85%
65%
Self discharge
(25°C)
After 3 months
After 6 months
After 12 months
91%
82%
64%
Characteristics
For standby power supplies. Expected trickle design life:
10 – 12 years at 20°C according to Eurobat.
LC-XD1217PG/APG
Terminal type
(option):
LC-XD1217PG:
M5 bolt and nut
LC-XD1217APG:
M5 threaded post
Battery case resin:
standard (UL94HB)
Individual Data Sheets
Contents indicated (including the recycle marking, etc.)
are subject to change without notice.
(Wattage/Battery)
Cut-off V 3min 5min 10min 15min 20min 30min 45min 1h 1.5h 2h 3h 4h 5h 6h 10h 20h 24h
9.6V 1021 806 526 402 337 251 177 142 97.6 75.5 56.2 43.2 35.6 28.6 19.0 10.3 8.58
9.9V 948 756 516 399 331 249 176 142 95.6 74.9 55.9 42.9 35.4 28.5 18.9 10.3 8.56
10.2V 874 708 502 391 326 246 175 139 93.7 73.0 55.4 42.6 35.1 28.3 18.7 10.2 8.53
10.5V 777 634 465 364 309 240 172 136 91.7 70.4 54.5 42.3 34.8 28.0 18.6 10.2 8.50
10.8V 656 561 415 339 301 232 169 134 89.2 67.1 53.4 41.8 33.9 27.5 18.4 10.1 8.44
(Ampere/Battery)
Cut-off V 3min 5min 10min 15min 20min 30min 45min 1h 1.5h 2h 3h 4h 5h 6h 10h 20h 24h
9.6V 91.8 72.2 47.0 34.9 29.0 21.5 15.1 12.0 8.26 6.37 4.72 3.61 2.97 2.39 1.58 0.86 0.72
9.9V 85.2 67.8 46.0 34.7 28.6 21.2 15.0 12.0 8.10 6.33 4.70 3.59 2.95 2.38 1.57 0.85 0.71
10.2V 78.6 63.5 44.9 34.0 28.1 21.0 14.9 11.8 7.93 6.16 4.65 3.57 2.93 2.36 1.56 0.85 0.71
10.5V 69.9 56.9 41.6 31.6 26.7 20.5 14.6 11.6 7.77 5.95 4.58 3.54 2.90 2.33 1.55 0.85 0.71
10.8V 59.0 50.3 37.1 29.5 26.0 19.8 14.4 11.3 7.56 5.67 4.49 3.49 2.83 2.29 1.53 0.85 0.70
Watt Table
Ampere Table
Charging Method
Trickle use
Control voltage: 13.6 - 13.8V;
Initial current: 2.55A or smaller
Influence of Temperature on Trickle life
0
20
40
60
80
100
120
0 2 4 6 8 101214161820
Storage Period (Month)
)%(oitaR noitneteR yticapaC
5 °C
(41 °F)
25 °C
(77 °F)
30 °C
(86 °F)
40 °C
(104 °F)
Cut off voltage
Discharge current
0.85A -
3.4A
3.4A -
8.5A
8.5A -
17A
17A -
34A
34A -
51A
Cut off voltage (V) 10.5 10.2 9.9 9.3 8.7
Residual capacity vs storage period
0
20
40
60
80
100
120
140
160
048121620
Charge Time (h)
)%( ytitnauQ egrahC
0
2
4
6
8
10
12
14
16
)V( egatloV yrettaB
Discharge
100 % (0.05 CA*20H)
50 % (0.05 CA*10H)
Charge
Charge Voltage 13.65 V
(2.275 V / Cell)
Charge Current 0.15 CA
Temperature 25 °C (77 °F)
0.3
0.2
0.1
0
Battery Voltage
Charge Current
Charge Quantity (to-Discharge Quantity)
)AC( tnerruC egrahC
1
2
3
Constant-voltage and constant-current charge
characteristics for Trickle use
0
20
40
60
80
100
120
-20 -10 0 10 20 30 40 50
)%(yticapaC
Battery temperature (°C)
0.05 CA
0.1 CA
0.2 CA
0.5 CA
1 CA
2 CA
3 CA
Discharge capacity by temperature
and by discharge current
5
6
7
8
9
10
11
12
13
14
15
(minute) (hour)
Duration of discharge
)V(egatlov lanimreT
0
1
20104
2
40
60
2
468
10 20
40
68
0.85 A
1.7 A
4.25 A
8.5 A
51 A
17 A
Discharge characteristics
VdS
G104101
0.1
1
10
100
10 20 30 40 50060
Temperature (°C)
)sraeY( efiL ecivreS
Charging Voltage
䚭㻃
2.275 V / Cell