Datasheet
№SR-ZSV00039 - 5 -
Motor Business Unit, Appliances Company, Panasonic Corporation
2-3 Input/Output Signal Allocation
The assignment of the input/output signals can be changed from the default setting.
2-3-1 Allocation of Input Signal
An input signal that you wish can be assigned to an input pin of the I/F connectors. It is also possible to change the
logic.
Note that for some signals, assignment is limited. For details, see (2) "Change the default assignment for input
signals."
(1) Use the default signal assignment
The following table shows the default setting for the signal assignment.
Default status
Input signals*2
Corresponding
parameter
Default value
(): Decimal
number
Signal Logic *1
SI1 input Pr4.00
00000003h
(3)
SRV-ON a connect
SI2 input Pr4.01
00000004h
(4)
A-CLR a connect
SI3 input Pr4.02
00000007h
(7)
CL a connect
SI4 input Pr4.03
00000088h
(136)
INH b connect
SI5 input Pr4.04
00000082h
(130)
NOT b connect
SI6 input Pr4.05
00000081h
(129)
POT b connect
*1 "a connect" and "b connect" represent the following respectively:
a connect : A signal input is open with COM-, and thus the function is invalid (OFF state).
A signal input is connected with COM-, and thus the function is valid (ON state).
b connect : A signal input is open with COM-, and thus the function is valid (ON state).
A signal input is connected with COM-, and thus the function is invalid (OFF state).
In this specification, a signal input is defined ON when its function is valid; OFF when the function is invalid.
*2 For pin numbers assigned as input signals SI1 – SI10, see Specifications.
*3 The mark "-" displays that there is no function assigned.