8-2 Timing Chart
8-2-1 Timing Chart of Operations After Turning Power On
Control power
(L1C, L2C)
OFF ON
Internal control
power
OFF Established
Approx 1.5s *1
Micro computer
operation
Reset Initialization
Error
check start
Normal operation
Alarm output
(
ALM
)
Output Tr OFF Output T r ON
Main power
(
L
1
,
L
2
,
L
3
)
OFF ON
*3
Servo ready
output
(
S
-
RDY
)
Output Tr OFF Output T r ON
*5
Servo on input
(
SRV
-
ON
)
Input Couple OFF Input Couple ON
Dynamic brake
*4
Operation (Pr5.07) (Pr5.06) Released
Power to the
motor
No power
Power to the motor
Brake release
output(BRK-OFF)
Output Tr OFF
(brake applied)
Out put Tr ON
(brak e released)
Position/velocit
y/torque command
No command
There is comm and
0s upwards
Approx 60ms
0s upwards
Approx 2ms
Approx 4ms
Approx 100ms
upwards *6
Approx 2s * 2
Approx 100ms upwards
Approx 100-300 ms
• The above chart shows the timing of actions from the time when the control power is turned on until a com-
mand is entered.
Enter the servo-on signal and the position/velocity/torque commands according to the above chart.
*1. When the internal control power has been established, the protective functions get activated approximately
1.5 s after the start of the micro computer initialization. To design your system, keep in mind that all the
input/output signals connected to the driver should be established before the protective functions start get-
ting activated; use special care for signals that can trigger the protective functions such as positive/negative
overtravel limits and external scale input. Also, this time can be extended using Pr6.18 “Power-up wait
time”
*2. After microcomputer initializing,and no errer,the output of ALM is on.
*3. S-RDY output is turned on only when the two conditions are met: initialization of the microcomputer has been
complete, and the main power has been established.
*4. As SRV-OFF,until initialize ending,dynamic brake action is according to Pr5.07” Sequence at main power
OFF”,after main power establish,according to Pr5.06”SRV-OFF sequence”.
*5. After the output of SRV-READY is affirmed,please start the input of SRV-ON。
*6. The signal of SRV-ON from on to the fact of position instruction,the waiting time please
set about 100ms at least.Because from SRV-ON to the fact of power to motor need to consume some time,It is
possibility the position command cann’t be accepted.