Specification Sheet
/ Panasonic ERV
(Continued)
Panasonic Life Solutions Company of America
IAQ Division
Two Riverfront Plaza
Newark, NJ 07102
us.panasonic.com/ventfans
IAQ21056ST
Canada and is ENERGY STAR
®
FV-20VEC1
Energy Recovery Ventilator
Intelli-Balance
™
200
FV-20VEC1
Characteristics COLD/TEMPERATE CLIMATE
Static pressure in inches w.g. 0.4
Net Exhaust Air Volume (CFM) 200
Net Supply Air Volume (CFM) 200
Power Consumption (Watts) 129
Power Rating (V/Hz) 120/60
ENERGY STAR
®
Certified Yes*
Energy Performance
MODE
Supply Temperature Net Air Flow
Power
Consumed
(Watts)
Sensible
Recovery
Efficiency
Apparent
Sensible
Effectiveness
Net
Moisture
Transfer
°F °C L/S CFM
Heating
32 0 32 67 22 83% 86% 81%
32 0 59 124 46 77% 79% 73%
32 0 80 170 92 73% 77% 78%
-13 -25 31 66 46 67% 69% 70%
-13 -25 50 107 104 61% 64% 64%
Cooling
Total Recovery Efficiency
95 35 34 71 25 70%
95 35 64 135 56 61%
ERV Wall Control Panel
The all-new LCD Wall Control puts total control and
monitoring of Intelli-Balance 200 at your fingertips.
Easy operation from nine push buttons and an LCD
display gives homeowners instant access to custom
ventilation control settings and real-time air flow and
temperature monitoring.
Functions & Settings
• Power on/off
• Air volume for supply and exhaust
• ASHRAE intermittent timer and air volume
• BOOST mode control
- Sets supply and exhaust air to constant 200 CFM
- Timer for BOOST activation adjustable from
10-60 minutes
• Reset filter maintenance reminder
Display Information
• Indoor/outdoor temperature and humidity
• Filter maintenance reminder
• ASHRAE air volume and boost timer
• Defrost mode indicator
• Supply and exhaust air volume
• System fault codes
LCD Wall Control
FV-20VEC1 200 CFM 6" Ducts
Static Pressure (inch w.g.)
Airflow (CFM)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
0
0 20 40 60 80 100 120
140 160 180 200 220
Net Supply Air
Net Exhaust Air
r4