Dimensions Guide
Specication Submittal Data / Panasonic ERV
(Continued)
Panasonic Eco Solutions North America
Eco Products Division
Two Riverfront Plaza
Newark, NJ 07102
us.panasonic.com/ventfans
VF17024SS-10VEC1
22-1/2 in.
5 in.
10-3/4 in.
3-3/8 in.
5-9/16 in.
8-5/8 in.
8-1/2 in.
4-1/2 in.
Optional Exterior Wall Cap
Exterior Wall Cap
FV-WC04VE1 polypropylene wall cap with styrofoam adaptor allows both
exhaust (from the right) and supply (from the left) airow through a 5.5"-5.75"
hole in the building envelope. The dividers inside the bottom portion of the Y
shape chamber and the new wall cap help prevent cross contamination.
NOTE: FV-WC04VE1 is NOT recommended for use at CFM settings
higher than 50 CFM.
Optional Accessory
Specications: Intelli-Balance 100 FV-10VEC1
Static Pressure in inches w. g. 0.1 0.4
Net Exhaust Air Volume (CFM) 96 95
Net Supply Air Volume (CFM) 98 96
Power Consumption (watts) 64.0 84.0
Power Rating (V/Hz) 120/60
ENERGY STAR
®
Certied Yes
Energy Performance: Intelli-Balance 100 FV-10VEC1
Supply
Temperature
Net Air Flow
Power
Consumed
(Watts)
Sensible Apparent Net
Recovery Sensible Moisture
°C °F L/S CFM Efciency Effectiveness Transfer
Heating
0 32 25 53 24 81 88 0.8
0 32 31 67 34 77 86 0.76
0 32 40 86 54 75 83 0.72
-25 -13 27 57 66 65 85 0.7
-25 -13 32 68 84 64 80 0.7
Cooling Total Recovery Efciency
35 95 23 48 16 65
Performance Curve 4" or 6" duct
*This product meets strict energy efciency guidelines set by Natural Resources
Canada and is ENERGY STAR
®
certied for the Canadian market only.
B
E
S
T
E
N
E
R
G
Y
E
F
F
I
C
I
E
N
T
P
R
O
D
U
C
T
B
E
S
T
O
F
I
B
S
A
W
A
R
D
S
W
I
N
N
E
R
FV-10VEC1
Cold Climate ERV
Energy Recovery Ventilator
FV-10VEC1 50-80-100 CFM 4 x 4" or 6" Ducts FV-10VE1 50-80-100 CFM 4 x 4" or 6" Ducts
Static Pressure (inch w.g.)
Airflow (CFM)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0
0 20 40 60 80 100 120
Net Supply Air
Net Exhaust Air
Static Pressure (inch w.g.)
Airflow (CFM)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0
0 20 40 60 80 100 120
Net Supply Air
Net Exhaust Air
FV-10VEC1 50-80-100 CFM 4 x 4" or 6" Ducts FV-10VE1 50-80-100 CFM 4 x 4" or 6" Ducts
Static Pressure (inch w.g.)
Airflow (CFM)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0
0 20 40 60 80 100 120
Net Supply Air
Net Exhaust Air
Static Pressure (inch w.g.)
Airflow (CFM)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0
0 20 40 60 80 100 120
Net Supply Air
Net Exhaust Air