Specification Sheet

ASHRAE 62.2 TIMING FUNCTION
The adjustable Minutes Per Hour (Min/Hr) timer allows the user to set the number
of minutes per hour the ERV should run. This ensures consistent and controlled
ventilation throughout the day for compliance with ASHRAE 62.2. Factory default
setting is 60 Min/Hr.
FILTERS & MAINTENANCE
Intelli-Balance 100 has two filters that clean the exhaust and supply air before
passing through the ERV core, extending the life of the core. A hinged access panel
allows for quick and easy product maintenance and filter checks. Convenient light
indicator and unobtrusive alarm signal on the access panel will help inform the
homeowner when its time to check and clean the filters. Both filters should be
vacuumed with a soft brush attachment every 2-3 months or as needed, and the
supply air filter should be inspected every 90 days and replaced every 6 months to
maintain the ERV’s peak performance.
EXCHANGE CAPILLARY CORE
Indoor and outdoor air pass through Panasonic’s patented capillary core designed
to transfer heat and moisture. This process tempers supply air while transferring
moisture. The core’s high latent energy (moisture) transfer makes Intelli-Balance
100 ideal for use in most climate zones, as it helps expel moisture during incidences
of high relative humidity (RH) and helps return moisture back inside during the
winter for a healthier, more comfortable living environment.
WHOLE HOUSE ERV
Intelli-Balance 100 is a ceiling or wall mount Energy Recovery Ventilator (ERV) thats
ideal for meeting whole house ventilation requirements under ASHRAE 62.2. Intelli-
Balance 100 is also an ideal choice when partnered with mini-splits or VRF Heat
Pumps for fresh, balanced air with energy recovery which makes it a very affordable,
cost-effective IAQ solution.
Ideal for: Single Family Homes (≤ 3,000 sq. ft., up to 7 bedrooms) / Condominiums /
Apartments / Housing Authority Properties / Hotels / Studio apartments.
ASHRAE 62.2 2010 AND 2013 STANDARD
The American Society of Heating, Refrigerating and Air Conditioning Engineers
(ASHRAE) set a standard for whole house ventilation, requiring that continuous
mechanical ventilation be 7.5 CFM per bedroom (master bedroom X 2) plus 1 CFM per
100 square feet, with sone not to exceed 1.0. ASHRAE 62.2-2013 requires a ventilation
rate of 7.5 CFM per person plus 3 CFM per 100 square feet. Please check with your
local code to determine which ventilation standard you should follow. Panasonic Intelli-
Balance 100 ERV is an affordable, efficient way to meet the ASHRAE 62.2 standard.
OPERATION
FV-10VEC1 is recommended for areas where temperatures can drop as low as
-22°F (-30°C). When the outdoor temperature is < -22°F (-30°C), the defrost cycle
is initiated and the product will stop operating for 47 minutes, then operate in heat
exchange mode for 4 minutes in order to sample the outdoor temperature. It then
operates in circulation mode for 9 minutes in order to defrost (exhaust and supply air
are 50 CFM). Defrost cycle overrides the ASHRAE 62.2 timing function.
FV-10VE1 is recommended for areas where temperatures can drop as low as
14°F (-10°C). When the outdoor temperature is < 14°F (-10°C), the defrost cycle
is initiated and the product will stop operating for 56 mins, then operate in heat
exchange mode for 4 minutes in order to sample the outdoor temperature (exhaust
and supply air are 50 CFM). Defrost cycle overrides the ASHRAE 62.2 timing function.
Supply Air Filter (MERV 8
included, MERV 13 Optional)
Return Air Filter
Exchange Capillary Core