ARCHITECTURAL SPECIFICATIONS
PANASONIC ADVANCED VENTILATION SERIES
FV-10NLF1E WhisperLine Remote Mount, Inline Fan 120 CFM.
Ventilation fan shall be remote mount, ENERGY STAR® certified, with no less than 120 CFM as certified
by the HVI at .2 static pressure in inches water gauge. Power consumption shall be no greater than 27.5
Watts and energy efficiency rating shall be no less than 4.4 CFM/Watt. The motor shall be totally
enclosed, four pole condenser type engineered to run continuously. Power rating shall be 120v/60Hz.
Housing shall be insulated to reduce condensation. Duct diameter shall be no less than 4". Fan shall be
UL and cUL listed for tub/shower enclosure when GFCI protected. Brackets shall be provided for joist,
truss or suspension installations. Can be used to comply with ASHRAE 62.2, LEED, CA Title 24,
EarthCraft and WA Ventilation Code.