Specification

Specification Submittal Data / Panasonic Ventilation Fan
Description:
Ventilating fan shall be Low Noise ceiling or wall
mount type rated for continuous run. Fan shall
be ENERGY STAR
®
rated and certified by the
Home Ventilation Institute (HVI). Evaluated by
Underwriters Laboratories and conform to both
UL and cUL safety standards.
Motor/Blower:
• Enclosed brushless ECM motor technology
rated for continuous run.
• Fan ventilation rates shall be manually
adjustable for 50-80-100 CFM.
• Power rating shall be 120 volts and 60 Hz.
• Fan shall be UL and cUL listed for tub/shower
enclosure when GFCI protected and used in
insulated ceiling (TYPE I.C.).
• PCB board equipped with thermal–cutoff fuse.
• Removable with permanently lubricated plug-
in motor.
Housing:
• 26 gauge galvanized steel body.
• Built-in 4" Oval duct collar. Also compatible
with 4" round duct.
• Optional 24 gauge steel, fire code rated
4" oval to 3" round duct adaptor sold
separately (Model # FV-VS43R).
• Built in backdraft damper.
• Built-in metal flange provides blocking for
penetrations through drywall as an Air Barrier,
and assists with the decrease in leakage in the
Building Envelope during blower door testing.
• Unique L-shaped bracket simplifies installation
and provides strong support.
Ceiling Radiation Damper:
• WhisperValue DC is UL listed for use with the
Panasonic Ceiling Radiation Damper (Model #:
PC-RD05C5, sold separately).
Grille:
• Attractive design using Poly Pro material.
• Attaches directly to housing with torsion
springs.
Warranty:
• ECM Motor: 6 Years from original purchase
date.
• ALL Parts: 3 Years from original purchase
date.
Architectural Specifications:
Ventilation fan shall be UL and cUL listed for
ceiling or wall mount and tub/shower enclosure
when GFCI protected. Fan shall also be
ENERGY STAR
®
certified, with a condensation
sensor that shall be built-in and able to detect
relative humidity and temperature to anticipate
dew point. Fan shall also incorporate a built-
in speed selector. Choose from 50-80-100
CFM and no more than <0.3/0.4/0.9 sone as
certified by the Home Ventilating Institute (HVI)
at 0.1 static pressure in inches water gauge
(w.g.) with no less than 52/81/101 CFM and
no more than 0.5/0.8/1.3 sone as certified by
HVI at 0.25 w.g. Power Consumption shall be
no greater than 4.5/8.5/12.4 watts at 0.1 w.g.
and 7.7/13.2/18.0 watts at 0.25 w.g., with
efficiency of no less than 12.1/10.0/8.2 CFM/
watt at 0.1 w.g. and 7.3/6.5/5.7 CFM/watt at
0.25 w.g. The motor shall be totally enclosed
with a brushless ECM motor engineered to
run continuously. ECM motor speed shall
automatically increase when the fan senses
static pressure to maintain selected CFM.
Power rating shall be 120V/60Hz. Duct
diameter shall be no less than 4". Optional
24 gauge steel, fire code rated 4" oval to 3"
round duct adaptor sold separately (Model #
FV-VS43R). Fan can be used to comply with
ASHRAE 62.2, CALGreen, LEED, EarthCraft,
California Title-24 and WA Ventilation Code.
FV-0510VSC1
For complete Installation Instructions visit us.panasonic.com/ventfans
Model Quantity Comments Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
FV-0510VSC1
FV-0510VSC1
4″oval duct
4" Oval duct
Performance Curve 4" Oval duct
0.0 0
0.1 0
0.2 0
0.3 0
0.4 0
0.5 0
0.6 0
0.7 0
0.8 0
0 10 20 30 40 50 60 70 80 90 100 110
Static Pressure (inch w.g.)
Airflow (CFM)
FV-0510VSC1
100CFM
80CFM
50CFM
4" 20ft duct
4" 40ft duct
4" 60ft duct
4" 80ft duct
4" 100ft duct
Specifications and additional features
on following page.

Summary of content (2 pages)