Datasheet
FIBER
SENSORS
LASER
SENSORS
PHOTO-
ELECTRIC
SENSORS
MICRO
PHOTO-
ELECTRIC
SENSORS
AREA
SENSORS
SAFETY
COMPONENTS
PRESSURE
SENSORS
INDUCTIVE
PROXIMITY
SENSORS
PARTICULAR
USE
SENSORS
SENSOR
OPTIONS
WIRE-
SAVING
SYSTEMS
MEASURE-
MENT
SENSORS
STATIC
CONTROL
DEVICES
LASER
MARKERS
PARTICULAR
USE
SENSORS
EX-F70 /
EX-F60
Selection
Guide
Wafer
Detection
HD-T1
M-DW1
EX-F1
LX-100
FZ-10
NA1-11
Metal-sheet
Double-feed Detection
GD
Other
Products
Liquid Leak
Detection
Liquid Level
Detection
Color Mark
Detection
Small / Slim
Object Detection
EX-F70 /
EX-F60
Liquid Leak
Detection
Leak Detection Sensor EX-F70 SERIES EX-F60 SERIES
740
SPECIFICATIONS
Simple wire-saving unit
Designation Simple wire-saving unit for leak detection sensor
Item Model No. EX-FC1
Applicable connector SL-CP1
Supply voltage 12 to 24 V DC ± 10 % Ripple P-P 10 % or less
Current consumption
50 mA or less (for the unit itself),
135 mA or less (including the sensor input current when all outputs of sensors are ON)
Output
Relay contact 1a
Switching capacity: 30 V 1 A DC (resistive load)
Min. applied load: 10 mV 10 µA DC
Electrical lifetime: 100,000 switching operations or more (rated load, switching frequency 20 operations/min.)
Mechanical lifetime: 50 million switching operations or more (switching frequency 180 operations/min.)
•
•
•
•
Utilization category DC-12 or DC-13
Output operation The output relay is ON when the input signal from the sensor is ON (Note 2)
Response time 5 ms or less (excluding the response time of the sensor)
Input No. 8 Nos.
Indicators
Normal Green LED × 8 (light up when the sensor is connected to each channel and the connection setting switch is set to ON)
Error
Red LED × 8 (light up when the leak liquid is detected by a sensor connected to each channel or a sensor is mounted improperly)
Output Orange LED [lights up when the output relay is ON (normal)]
Pollution degree 3 (Industrial environment)
Ambient temperature –10 to +60 °C +14 to +140 °F (No dew condensation or icing allowed), Storage: –20 to +70 °C –4 to +158 °F
Ambient humidity 35 to 85 % RH, Storage: 35 to 85 % RH
Material Enclosure: ABS, Unit mounting base: POM, Terminal part: PBT
Cable 0.2 mm
2
4-core cabtyre cable, 2 m 6.562 ft long
Cable extension Extension up to total less than 10 m 32.808 ft is possible, with 0.3 mm
2
, or more, cable.
Weight Net weight: 85 g approx.
Accessories SL-CP1 (Snap male connector): 8 pcs., MS-SL-2 (Unit mounting base): 1 pc., SC-PK (Connector end cap) : 8 pcs.
Notes: 1) Where measurement conditions have not been specied precisely, the conditions used were an ambient temperature of +20 °C
+68 °F.
2) Even with only one leak detection sensor connected, an OFF signal is output if the sensor detects liquid leakage, or if the unit has been installed
incorrectly.