FX-301 SERIES Digital Fiber Sensor Superior performance and advanced user-friendly multi-functionality enables expert usage on the very first day * Passed the UL 991 Environment Test http://www.fiber-sensor.com * UL 61010C-1 compatible, Passed the UL 991 Environment Test based on SEMI S2-0200.
FX-301 Easy maintenance, as main and sub units are identical Wiring- and labor-saving design allows sideby-side configuration for up to sixteen units Both main and sub units utilize the same amplifier body. This feature allows for easy mounting in the side-by-side configuration. The main and sub unit functions are distinguished only by the proper use of 3-core main cable and the 1-core sub cable.
FX-301 4 types of light sources available In addition to our red LED (four-chemical emitting element) type, the blue, green, and infrared LED types are also provided to correspond to your specific application. Optical communication function lets multiple sensors be adjusted all at once The optical communication function allows the data that is currently set to be copied and saved all at once for all amplifiers connected together from the right side.
FX-301 Optional units for greater freedom and control when installing Sensor-PLC connection system SC SERIES Bank selection unit This wire-saving system enables the collective connection of up to 16 I/O devices with an MIL connector. Scattered installation is also possible with the help of a sensor separate unit. FX-CH SERIES Without directly manipulating the sensor itself, you can simultaneously switch up to 16 fiber sensors’ settings using an exter nal emitted signal.
FX-301 ORDER GUIDE Amplifiers Quick-connection cable is not supplied with the amplifier. Please order it separately.
FX-301 LIST OF FIBERS Standard fibers [Thru-beam type (one pair set)] Type Shape of fiber head (mm in) Long sensing range With lens With lens Lens mountable Lens mountable :LONG :STD Red LED :FAST :S-D Min. sensing object Fiber cable Allowable under the optimum length bending Blue LED Green LED Infrared LED condition (Note 2) :Free-cut radius Sensing range (mm in ) (Note 1) 19,500 767,715 5,400 212.598 2,800 2.400 94.488 "0.4 mm 14,000 551.180 2,700 106.299 110.236 1,200 47.244 10 m 10,000 393.
FX-301 LIST OF FIBERS Sharp bending fibers / Flexible fibers [Thru-beam type (one pair set)] Long sensing range Narrow beam Sharp bending Rectangular head Wide beam Type Shape of fiber head (mm in) Wide area sensing Sensing width 32 mm 1.260 in W5 H69 D20 W0.197 H2.717 D0.787 Wide area sensing Sensing width 11 mm 0.433 in W4.2 H31 D13.5 W0.165 H1.220 D0.531 Easy mounting Top sensing W3 H8 D12 W0.118 H0.315 D0.472 Easy mounting Side sensing W3 H12 D8 W0.118 H0.472 D0.
FX-301 LIST OF FIBERS Special use fibers [Thru-beam type (one pair set)] Narrow beam Tough flexible Ultra-small diameter Special use Array Wide beam Type Shape of fiber head (mm in) Sensing range (mm in) (Note 1) Red LED W5 H69 D20 W0.197 H2.717 D0.787 Side sensing W5 H15 D15 W0.197 H0.591 D0.591 Side-view Side-view W2 H1.5 D20 W0.079 H0.059 D0.787 Beam diameter: "0.125 mm "0.005 in Sleeve part cannot be bent. Beam diameter: "0.25 mm "0.010 in Sleeve part cannot be bent.
FX-301 LIST OF FIBERS Environment resistant fibers [Thru-beam type (one pair set)] Type Shape of fiber head (mm in) Sensing range (mm in) (Note 1) Red LED Min. sensing object Fiber cable Allowable under the optimum length bending Blue LED Green LED Infrared LED condition (Note 2) :Free-cut radius :LONG :STD 350 C 662 F Lens mountable Heat-resistant 350 C 662 F Sleeve 60 mm 2.
FX-301 LIST OF FIBERS Standard fibers (Reflective type) Shape of fiber head (mm in) Long sensing range Type Min. sensing object Fiber cable Allowable at the maximum length bending Blue LED Green LED Infrared LED sensitivity (Note 3) :Free-cut radius :LONG :STD :FAST :S-D 80 3.150 40 1.575 26 1.024 46 1.811 23 0.906 15 0.591 46 1.811 23 0.906 15 0.591 42 1.654 21 0.827 14 0.551 24 0.945 12 0.472 8 0.315 24 0.945 12 0.472 8 0.315 26 1.654 13 0.827 9 0.551 90 3.543 45 1.772 30 1.
FX-301 LIST OF FIBERS Sharp bending fibers / Flexible fibers (Reflective type) Long sensing range Type Shape of fiber head (mm in) Long sensing range Rectangular head Min. sensing object Fiber cable Allowable bending at the maximum length Blue LED Green LED Infrared LED sensitivity (Note 3) :Free-cut radius :LONG :STD :FAST :S-D 23 0.906 11 0.433 8 0.315 14 0.551 7 0.276 4 0.157 11 0.433 5.5 0.217 3 0.118 5 0.197 2.5 0.098 1.5 0.059 3 0.118 1.5 0.059 1 0.
FX-301 LIST OF FIBERS Special use fibers (Reflective type) Array Wide beam Type Shape of fiber head (mm in) Min. sensing object Fiber cable Allowable at the maximum length bending Blue LED Green LED Infrared LED sensitivity (Note 3) :Free-cut radius Red LED W7 H15 D30 W0.276 H0.591 D1.181 25 0.984 15 0.591 "0.02 mm "0.0008 in gold wire R25 mm 2m R0.984 in 6.562 ft 220 8.661 110 4.331 78 3.071 40 1.575 20 0.787 13 0.512 18 0.709 9 0.354 5 0.197 12 0.472 6 0.236 4 0.
FX-301 LIST OF FIBERS Environment resistant fibers (Reflective type) Type Shape of fiber head (mm in) Min. sensing object Fiber cable Allowable bending at the maximum length Blue LED Green LED Infrared LED sensitivity (Note 3) :Free-cut radius :LONG :STD Sensing range (mm in) (Note 1, 2) Red LED :FAST :S-D Model No. 350 C 662 F Coaxial 350 C 662 F Sleeve 60 mm 2.362 in 270 10.630 140 5.512 100 3.937 47 1.850 36 1.417 18 0.709 12 0.472 20 0.787 10 0.394 7 0.276 140 5.512 70 2.756 45 1.
FX-301 FIBER OPTIONS Lens (For thru-beam type fiber) Designation Model No. Description Sensing range (mm) [Lens on both sides] (Note 2) Increases the sensing range by 5 times or more. Expansion lens FX-LE1 (Note 1) Fiber • Ambient temperature: 60 to 350 C 76 to 662 F For thru-beam type fiber Fiber • Ambient temperature: 60 to 350 C 76 to 662 F Beam axis is bent by 90 .
FX-301 FIBER OPTIONS Others Protective tube Designation Model No. FTP-500 (0.5 m 1.640 ft) FTP-1000 (1 m 3.281 ft) ( ) FTP-1500 (1.5 m 4.921 ft) For M4 thread FTP-N500 (0.5 m 1.640 ft) For FTP-N1000 (1 m 3.281 ft) M3 thread FTP-N1500 (1.5 m 4.921 ft) FDP-500 (0.5 m 1.640 ft) FDP-1000 (1 m 3.281 ft) Protective tube For reflective type fiber ( ) FDP-1500 (1.5 m 4.921 ft) FDP-N500 (0.5 m 1.640 ft) For M6 thread For FDP-N1000 (1 m 3.281 ft) M4 FDP-N1500 (1.5 m 4.
FX-301 SPECIFICATIONS Amplifiers NPN output Type Model No.
FX-301 SPECIFICATIONS Fibers Item Type Allowable bending radius Standard Flexible R25 mm R0.984 in or more [Sleeve of a head with sleeve:R10 mm R0.394 in or more (Note 1)] R4 mm R0.157 in or more 1 million times or more (at R10 mm R0.394 in, FT-P40/P2 and FD-P40/P2: at R4 mm R0.
FX-301 SPECIFICATIONS Fibers Type Item Special use Fixed-focus reflective Ultra-small diameter Tough flexible Allowable bending radius FT-E12/E22: R5 mm R0.197 in or more (Note 1) FD-E12: R10 mm R0.394 in or more (Note 1) FD-E22/EN500S1/ENM1S1: R25 mm R0.
FX-301 I/O CIRCUIT AND WIRING DIAGRAMS NPN output type I/O circuit diagram Wiring diagram Note: The quick-connection sub cable does not have brown lead wire and blue lead wire. Notes: 1) The quick-connection sub cable does not have V (brown) and 0 V (blue). Notes: 2) 50 mA max., if five amplifiers, or more, are connected together.
FX-301 SENSING CHARACTERISTICS (TYPICAL) Parallel deviation FT-FM10L Thru-beam type FT-SFM2L Thru-beam type FT-B8 Thru-beam type FT-NB8 Thru-beam type FT-FM2 FT-FM2S FT-FM2S4 FT-T80 FT-SFM2 Thru-beam type FT-N8 Thru-beam type FT-NFM2 FT-NFM2S FT-NFM2S4 FT-SNFM2 Thru-beam type FT-R80 Thru-beam type L FT-V10 Horizontal direction FT-V22 Horizontal direction FT-SFM2SV2 Thru-beam type Thru-beam type Vertical direction Horizontal direction FT-V41 Thru-beam type Vertical direction Horizont
FX-301 SENSING CHARACTERISTICS (TYPICAL) Parallel deviation FT-WA30 FT-A30 FT-WA8 FT-A8 Thru-beam type Vertical direction Horizontal direction Thru-beam type Vertical direction Horizontal direction L FT-WZ8H Vertical direction Horizontal direction FT-WZ8 FZ-WZ8E Thru-beam type Thru-beam type Vertical direction Horizontal direction FT-WKV8 Thru-beam type Thru-beam type Vertical direction Horizontal direction FT-WS8L 88 Thru-beam type FT-W8 FT-WS8 Thru-beam type 08/2005 FT-WS3 Thru-
FX-301 SENSING CHARACTERISTICS (TYPICAL) Parallel deviation FT-WV42 Thru-beam type Horizontal direction FT-Z8H Thru-beam type FT-Z8E Thru-beam type Thru-beam type FT-P40 Thru-beam type Vertical direction FT-Z8 Thru-beam type FT-P80 Thru-beam type FT-P60 FT-P2 Thru-beam type FT-PS1 Thru-beam type FT-AFM2 Thru-beam type Horizontal direction FT-AFM2E Horizontal direction FT-K8 Thru-beam type Vertical direction Thru-beam type Vertical direction L 08/2005 89
FX-301 SENSING CHARACTERISTICS (TYPICAL) Parallel deviation FT-KV1 Thru-beam type Horizontal direction FT-KV8 Vertical direction Thru-beam type Horizontal direction FT-E12 Thru-beam type FT-E22 Thru-beam type Thru-beam type FT-H20-M1 Thru-beam type Vertical direction FT-P81X Thru-beam type FT-H35-M2 FT-H35-M2S6 Thru-beam type FT-H20W-M1 FT-H20W-M2 FT-H13-FM2 Thru-beam type FT-L8Y Thru-beam type FT-V8Y Horizontal direction 90 08/2005 Thru-beam type Vertical direction
FX-301 SENSING CHARACTERISTICS (TYPICAL) Parallel deviation FT-Z802Y FT-6V Thru-beam type Thru-beam type FT-60V Thru-beam type Thru-beam type FT-H35-M2 Thru-beam type Thru-beam type FT-H35-M2 Thru-beam type Parallel deviation with FX-LE1 (expansion lens) applied on both sides FT-B8 Thru-beam type FT-H20W-M2 Thru-beam type FT-W8 Thru-beam type FT-H20-M1 Thru-beam type FT-P80 Parallel deviation with FX-LE2 (super-expansion lens) applied on both sides FT-B8 Thru-beam type FT-W8 Thru-b
FX-301 SENSING CHARACTERISTICS (TYPICAL) Parallel deviation with FX-LE2 (super-expansion lens) applied on both sides FT-H20W-M2 Thru-beam type FT-H20-M1 Thru-beam type FT-H13-FM2 Thru-beam type Parallel deviation with FX-SV1 (side-view lens) applied on both sides FT-B8 Horizontal direction FT-P80 Horizontal direction FT-W8 Thru-beam type Vertical direction Horizontal direction FT-H35-M2 Thru-beam type Vertical direction Horizontal direction FT-H20W-M2 Thru-beam type Horizontal direction 92
FX-301 SENSING CHARACTERISTICS (TYPICAL) Sensing fields FD-T40 FD-NFM2 FD-NFM2S FD-NFM2S4 FD-SNFM2 FD-B8 Reflective type FD-5 FD-FM2 Reflective type FD-T80 FD-S80 FD-FM2S FD-FM2S4 Reflective type FD-N8 Reflective type FD-N4 Reflective type FD-R80 Reflective type FD-V41 Reflective type FD-SFM2SV2 Reflective type Horizontal direction FD-WKZ1 Horizontal direction Vertical direction Horizontal direction FD-W8 FD-WT8 FD-WS8 Reflective type Reflective type Vertical direction Reflective type
FX-301 SENSING CHARACTERISTICS (TYPICAL) Sensing fields FD-WG4 FD-WSG4 Reflective type FD-WV42 Reflective type Horizontal direction FD-P60 Reflective type FD-A15 Reflective type Horizontal direction FD-G4 94 FD-P50 FD-P40 Reflective type FD-AFM2 FD-AFM2E FD-G6 Reflective type FD-P2 Reflective type Vertical direction Vertical direction Reflective type FD-P80 Reflective type Reflective type Horizontal direction Reflective type 08/2005 FD-EG1 Vertical direction Reflective type
FX-301 SENSING CHARACTERISTICS (TYPICAL) Sensing fields FD-EG3 Reflective type FD-E12 Reflective type FD-E22 Reflective type FD-EN500S1 Reflective type FD-ENM1S1 Reflective type FD-P81X Reflective type FD-G6X Reflective type FD-H35-M2 FD-H35-M2S6 Reflective type FD-H20-M1 Reflective type FD-H35-20S Reflective type FD-H20-21 Reflective type FD-H30-L32 FD-H18-L31 Reflective type FD-6V Reflective type FD-H13-FM2 Reflective type 08/2005 95
FX-301 PRECAUTIONS FOR PROPER USE Amplifier This product is not a safety sensor. Its use is not intended or designed to protect life and prevent body injury or property damage from dangerous parts of machinery. It is a normal object detection sensor. Mounting How to mount the amplifier 1 Fit the rear part of the amplifier on a 35 mm 1.378 in width DIN rail. 2 Press down the front part of the mounting section of the amplifier on the 35 mm 1.378 in width DIN rail. 35 mm 1.
FX-301 PRECAUTIONS FOR PROPER USE Amplifier Teaching • The threshold values can be set by 2-level teaching, limit teaching or fullauto teaching, when the MODE indicator / TEACH (yellow) lights up. In case of 2-level teaching • This is the method of setting the threshold value by teaching two levels, corresponding to the object present and object absent conditions. Normally, setting is done by this method. Step Description Display Set the fiber within the sensing range.
FX-301 PRECAUTIONS FOR PROPER USE Amplifier Threshold value fine adjustment Step Description Key-lock function • With the FX-301B(P)/G(P)/H(P), if jog switch and MODE key are pressed for more than 3 sec. at the same time in ‘RUN’ mode condition, the key operations are locked, and only the threshold value confirmation function or the adjust function (valid only when the adjust lock function is canceled) is valid. • To cancel the lock function, press both the keys for more than 3 sec. once again.
FX-301 PRECAUTIONS FOR PROPER USE Amplifier PRO mode • Refer to the ‘Fiber Sensor Guide Book’ for more details pertaining to the PRO mode settings and procedures. • The above can also be download from ‘SUNX fiber sensor homepage’ (http://www.fiber-sensor.com) • PRO settings can be done when MODE indicator / PRO (yellow) lights up.
FX-301 PRECAUTIONS FOR PROPER USE Fiber Mounting • The tightening torque must not exceed the values given below. Mounting array fiber • Using M3 screws, the tightening torque should be 0.58 N m or less. Mounting with a nut (threaded head type) Tightening torque M3 0.39 N·m M4 0.58 N·m 350 °C 662 °F heat-resistant fiber and FT-H20W-M : 0.98 N m, FD-H35-20S: 0.58 N m ( M5 M6 ( 0.98 N·m 350 °C 662 °F heat-resistant fiber: 1.96 N m M14 ) • Using M2.6 (length 12 mm 0.
FX-301 PRECAUTIONS FOR PROPER USE Fiber Mounting FT-Z8 and FT-WZ8 • Mount the fiber head by using the enclosed set of screws. The tightening torque should be 0.15 N m or less • If the fiber head is mounted in places subject to vibrations or shocks, use a screw-locking adhesive, etc. • Mount each fiber head as given below.
FX-301 PRECAUTIONS FOR PROPER USE. Fiber Narrow beam type fiber mounting • Take care that, since the aperture angle of this product is very narrow, the beam may not be received depending upon the setting. At the time of installation, determine a reference plane, as shown in the figure below, and taking sufficient care against beam misalignment or tilt, install the emitting and receiving fibers so that they are parallel.
FX-301 PRECAUTIONS FOR PROPER USE. Fiber Fiber attachments (FX-AT ) Mounting Product outline • When the beam-emitting and beam-receiving fiber cables are inserted into the fiber sensor amplifier (FX-301/302/303/311 series etc.), the enclosed fiber attachment (FX-AT2/AT3/AT4/AT5/AT6) facilitates insertion of the fiber cables and reduces the possibility of incorrect fiber cable insertion. 1 Mount the plug part of the fiber cables in FX-AT2, as shown in the figure below.
FX-301 PRECAUTIONS FOR PROPER USE. Fiber Fiber cutter (FX-CT2) • To cut the fiber cables, insert them from the direction shown below. Vacuum type fiber Configuration (Fiber cable insertion direction) How to use fiber cutter (FX-CT2) 1 Slide part A of the fiber cutter fully upward till it stops. 2 Insert the fiber cables, mounted in the attachment, till they stop. Take care that there are separate fiber insertion cable holes for "2.2 mm "0.087 in and "1.0 mm "0.039 in or "1.3 mm "0.051 in fiber cables.
FX-301 PRECAUTIONS FOR PROPER USE. Fiber FT-L8Y/V8Y chemical-resistant type fiber • Do not use it in the following chemicals: Dissolved alkali metals (Natrium, Potassium or Lithium), Fluorine gas (F2), CIF3, OF2 (including gaseous state). • The beam axis mark is indicated on the side-view fiber. Perform the beam alignment with the beam axis marks, on the receiver and the emitter, facing each other. Mounting • Use a commercial Fluorine resin joint to mount the fiber.
FX-301 PRECAUTIONS FOR PROPER USE. Fiber FD-F4 and FD-F9 liquid level sensing fiber Cautions Mounting • Mount the fiber head on a pipe with the attached tying bands and anti-slip tubes as shown in the figure below. Make sure that the release lever is retracted (position as in the fig.) before mounting. Fasten two tying bands, as shown, and cut off the excess portions. • If other tying bands are to be used, the dimension A shown in the figure below should be 2.5 mm 0.098 in or less.
FX-301 PRECAUTIONS FOR PROPER USE. Fiber Cautions for FX-MR5 side-view zoom lens usage • The spot diameter and the sensing range are adjustable by the screw-in depth as follows. Others • Do not use the fiber at places having intense vibrations, as this can cause malfunction. • Keep the fiber head surface intact. If it is scratched or spoiled, the detectability will deteriorate. • Do not expose the fiber cable to any organic solvents.
FX-301 DIMENSIONS (Unit: mm in) FX-301 FX-301 P CN-73-C1 CN-73-C2 CN-73-C5 Amplifier CN-71-C1 CN-71-C2 CN-71-C5 Main cable (Optional) • Length (L) • Length (L) Model No. Length (mm in) MS-DIN-2 Model No. Length (mm in) CN-73-C1 1,000 39.370 CN-71-C1 1,000 39.370 CN-73-C2 2,000 78.740 CN-71-C2 2,000 78.740 CN-73-C5 5,000 196.850 CN-71-C5 5,000 196.
FX-301 DIMENSIONS (Unit: mm in) Thru-beam type fibers FT-FM10L Free-cut With FX-AT3 FT-SFM2L Free-cut With FX-AT3 Toothed lock washer "23 "0.906 FT-B8 Free-cut With FX-AT3 FT-NB8 Free-cut FT-FM2 Free-cut With FX-AT3 FT-FM2S FT-FM2S4 Free-cut With FX-AT3 Toothed lock washer "8.5 "0.335 FT-T80 Free-cut FT-N8 Free-cut FT-NFM2S FT-NFM2S4 Free-cut With FX-AT5 With FX-AT4 FT-SFM2 Free-cut With FX-AT3 FT-NFM2 Free-cut With FX-AT4 FT-SNFM2 Free-cut With FX-AT4 (20) (0.
FX-301 DIMENSIONS (Unit: mm in) Thru-beam type fibers FT-R80 Free-cut FT-V10 With FX-AT3 Free-cut With FX-AT3 FT-SFM2SV2 Free-cut With FX-AT3 FT-V41 Free-cut With FX-AT4 Details of screw tightening range FT-V22 With FX-AT2 15 0.591 FT-WA30 Free-cut With FX-AT3 FT-WA8 Free-cut With FX-AT3 FT-WZ8H Free-cut With FX-AT5 FT-WZ8E Free-cut With FX-AT5 FT-WZ8 Free-cut With FX-AT5 FT-WKV8 Free-cut With FX-AT3 Note: The emiter and receiver are symmetric.
FX-301 DIMENSIONS (Unit: mm in) Thru-beam type fibers FT-WS8L Free-cut With FX-AT3 FT-W8 Free-cut With FX-AT3 Free-cut With FX-AT3 Free-cut With FX-AT4 Details of sensing part FT-WS3 Free-cut With FX-AT3 Details of sensing part Details of sensing part FT-W4 FT-WS8 Free-cut With FX-AT3 Details of sensing part FT-WS4 Details of sensing part FT-WV42 Free-cut With FX-AT4 FT-Z8H Free-cut With FX-AT5 FT-Z8E Free-cut With FX-AT5 FT-Z8 Free-cut With FX-AT5 Free-cut With FX-AT5 N
FX-301 DIMENSIONS (Unit: mm in) Thru-beam type fibers FT-P40 Free-cut FT-P2 With FX-AT4 With FX-AT2 Details of sensing part Details of sensing part FT-PS1 With FX-AT2 FT-A30 Free-cut With FX-AT3 Details of sensing part FT-A8 Free-cut With FX-AT3 FT-AFM2 Free-cut With FX-AT3 FT-AFM2E Free-cut With FX-AT3 FT-K8 Free-cut With FX-AT3 FT-KV8 Free-cut With FX-AT3 FT-KV1 Free-cut With FX-AT4 With FX-AT2 FT-E22 Details of screw tightening range FT-E12 112 08/2005 With FX-AT2
FX-301 DIMENSIONS (Unit: mm in) Thru-beam type fibers FT-P81X With FX-AT2 FT-H35-M2 19.5 0.768 FT-H35-M2S6 Details of sensing part Toothed lock washer"8.5 "0.335 [Stainless steel (SUS)] FT-H20W-M1 FT-H20W-M2 FT-H13-FM2 Free-cut With FX-AT2 FT-H20-M1 With FX-AT3 FT-Z802Y Free-cut With FX-AT3 15 0.
FX-301 DIMENSIONS (Unit: mm in) Reflective type fibers FD-B8 Free-cut FD-5 With FX-AT3 With FX-AT2 Details of sensing part Details of sensing part FD-FM2 Free-cut FD-FM2S FD-FM2S4 With FX-AT3 Free-cut With FX-AT3 Free-cut With FX-AT4 Details of sensing part Details of sensing part FD-T80 Free-cut FD-T40 With FX-AT5 Details of sensing part Details of sensing part FD-S80 Free-cut Details of sensing part FD-N4 Free-cut FD-NFM2 With FX-AT10 Free-cut With FX-AT4 Free-cut With FX-AT
FX-301 DIMENSIONS (Unit: mm in) Reflective type fibers FD-R80 Free-cut FD-V41 With FX-AT3 Free-cut With FX-AT4 Details of sensing part Details of sensing part "4 "0.
FX-301 DIMENSIONS (Unit: mm in) Reflective type fibers FD-WL42 Free-cut FD-P80 Free-cut With FX-AT4 FD-WV42 Free-cut With FX-AT4 FD-P60 Free-cut With FX-AT5 Details of sensing part Details of sensing part 12 0.
FX-301 DIMENSIONS (Unit: mm in) Reflective type fibers FD-EG1 With FX-AT2 FD-EG2 With FX-AT2 Details of sensing part FD-E12 With FX-AT2 Details of sensing part Details of sensing part FD-E22 With FX-AT2 FD-EG3 With FX-AT2 Details of sensing part ("3.2) ("0.126) Model No. tube (PVC) FD-EN500S1 Details of sensing part 15 0.591 15 0.
FX-301 DIMENSIONS (Unit: mm in) Reflective type fibers FD-L41 Free-cut With FX-AT4 FD-L42 Free-cut With FX-AT4 FD-L4 Free-cut With FX-AT4 FD-F41 FD-F91 FD-F4 FD-F9 Free-cut With FX-AT4 FD-F8Y Free-cut With FX-AT3 FD-G6X Free-cut With FX-AT6 FD-P81X With FX-AT2 Toothed lock washer "11 "0.
FX-301 DIMENSIONS (Unit: mm in) Reflective type fibers FD-H35-M2 FD-H35-M2S6 Details of sensing part Details of sensing part FD-H30-L32 FD-H20-M1 Details of sensing part FD-H20-21 Details of sensing part FD-H18-L31 FD-H35-20S Free-cut With FX-AT3 Details of sensing part FD-H13-FM2 Free-cut With FX-AT3 Details of sensing part FD-6V FX-LE1 Expansion lens (Optional) Details of sensing part Material: Enclosure ......Brass (Nickel plated) Lens ..............
FX-301 DIMENSIONS (Unit: mm in) FX-LE2 FX-SV1 Super-expansion lens (Optional) Material: Enclosure ......Stainless steel (SUS303) Lens ..............Glass FV-LE1 Side-view lens (Optional) Material: Enclosure ......Brass (Nickel plated) Lens ..............Glass FV-BR1 Expansion lens (For vacuum type fiber Optional) Photo-terminal (For vacuum type fiber Optional) Mounting hole Material: Enclosure ......Aluminum alloy (A6061-T6) Lens ..............
FX-301 DIMENSIONS (Unit: mm in) MS-EX-3 FTP- FDP- Mounting bracket for FX-MR2 (Accessory for FX-MR2) Protective tube (Optional) FTP- , FDP-N 16 0.630 Material: Brass (Nickel plated) FTP-N Mounting bracket Accessory for FD-WKZ1 for FD-WKZ1 FDP-N Material: SPCC-SD (Zinc chromate plated) FB-1 Fiber bender (Optional) Model No. Length L (mm in) 500 100 19.685 0.3940 FTP-1000, FTP-N1000, FDP-N1000, FDP-1000 1,000 100 39.37 0.3940 FTP-1500, FTP-N1500, FDP-N1500, FDP-1500 1,500 10 59.055 0.
FX-301-F Digital Fiber Sensor for Leak Detection / Liquid Detection Fibers Only Easy operation even for beginners! Optimum settings can be realized with simple operations * Passed the UL 991 Environment Test * UL 61010C-1 compatible, Passed the UL 991 Environment Test based on SEMI S2-0200.
FX-301-F Wiring- and labor-saving design allows sideby-side configuration for up to sixteen units Up to sixteen amplifiers can be connected in a side-byside configuration. As the sub cable contains only one output line, a great amount of wiring and space can be saved. Also, special ‘sliding’ connectors have been provided for all main and sub cables, which can be detached merely by releasing the lock and pulling directly back, without having to slide the main amplifier body to the side.
FX-301-F ORDER GUIDE End plates End plates are not supplied with the amplifier. Please order it separately when the amplifiers are mounted in cascade. Appearance Model No. MS-DIN-E Description When cascading multiple amplifiers, or when it moves depending on the way it is installed on a DIN rail, these end plates ensure that all amplifiers are mounted together in a secure and fully connected manner. Two pcs. per set OPTIONS Designation Model No.
FX-301-F Symbols … D : Reverse supply polarity protection diode ZD: Surge absorption zener diode Tr : NPN output transistor Symbols … D : Reverse supply polarity protection diode ZD: Surge absorption zener diode Tr : PNP output transistor 08/2005 521
FX-301-F PRECAUTIONS FOR PROPER USE This product is not a safety sensor. Its use is not intended or designed to protect life and prevent body injury or property damage from dangerous parts of machinery. It is a normal object detection sensor. Mounting How to mount the amplifier 1 Fit the rear part of the mounting section of the amplifier on a 35 mm 1.378 in width DIN rail. 2 Press down the front part of the mounting section of the amplifier on the 35 mm 1.378 in width DIN rail.
FX-301-F PRECAUTIONS FOR PROPER USE Part description Individual teaching mode • The sensitivity selection function is set to the automatic sensitivity setting ( ) at the time of factory shipment. In case sensitivity selection setting is done, make sure to carry out ‘teaching’ after the sensitivity selection setting. • For the sensitivity selection setting, refer to ‘Sensitivity selection function’ on p.525. 1 Operation indicator (Orange)… Lights up when output is ON.
FX-301-F PRECAUTIONS FOR PROPER USE Collective teaching mode Threshold value fine adjustment mode • When MODE indicator / ALL (yellow) lights up, a threshold value can be collectively set to amplifiers mounted in cascade. • When MODE indicator / ADJ (yellow) lights up, the set threshold value can be fine adjusted. Step Step Description 1 Insert Leak detection fiber (FD-F7 ) or Liquid detection fiber (FT-F9 ). Press MODE key to light up MODE indicator / ALL (yellow).
FX-301-F PRECAUTIONS FOR PROPER USE Forced output mode Timer function [Liquid (F9) mode only] • When MODE indicator / OUT (yellow) lights up, the output can be compulsory changed to ON or OFF regardless of the incident light intensity. • The timer setting can be done by pressing the jog switch for 3 sec., or more, when Liquid (F9) mode ( ) has been set and MODE indicator / DISP (yellow) lights up. In case of Leak (F7) mode ( ), the display does not change to the timer function.
FX-301-F PRECAUTIONS FOR PROPER USE NO / NC selection function [Liquid (F9) mode only] Wiring • The NO / NC selection can be done by pressing the jog switch for 3 sec., or more, when Liquid (F9) mode ( ) has been set and MODE indicator / DISP (yellow) lights up. In case of Leak (F7) mode ( ), the display does not change to NO / NC selection function. For the selection method of Leak (F7) mode / Liquid (F9) mode, refer to ‘Individual teaching mode’ on p.603 or ‘Collective teaching mode’ on p.604.
FX-301-F 08/2005 527
FX-305 SERIES Digital Fiber Sensor Digital Fiber Sensor with 2 independent outputs APC circuit Four-chemical emitting element Double coupling lens New Advanced sensor with Visible Indicator Industry first! Light-emitting amount selection function Industry’s largest display 9999 If the light-receiving level becomes saturated during close-range sensing or when sensing transparent or ultra-small objects, you can adjust the light-emitting amount of the sensor to stabilize sensing without needing to chang
FX-305 SPECIFICATIONS Supply voltage PNP output FX-305P FX-305 Thru-beam type (FT-B8): 1,700 (U-LG), 1,100 (LONG), 730 (STDF) 530 (STD), 400 (FAST), 200 (H-SP) Reflective type (FD-B8): 600 (U-LG), 480 (LONG), 280 (STDF) 220 (STD), 160 (FAST), 85 (H-SP) 12 to 24 V DC 10 % Ripple P-P 10 % or less Power consumption Normal operation: 960 mW or less (Current consumption 40 mA or less at 24 V supply voltage) ECO mode: 600 mW or less (Current consumption 25 mA or less at 24 V supply voltage) Output (Output