[nv7] Option 1 setting command
[nv9] Option 2 setting command
network input SNVT_switch nviOption1_00;
network input SNVT_switch nviOption1_01;
network input SNVT_switch nviOption1_02;
network input SNVT_switch nviOption1_03;
network input SNVT_switch nviOption2_00;
network input SNVT_switch nviOption2_01;
network input SNVT_switch nviOption2_02;
network input SNVT_switch nviOption2_03;
These input network variables are used to make the indoor unit
option settings.
Two of the following 4 option settings can be selected:
remote-controller prohibit, fan speed setting, air direction
setting, and fi lter sign reset.
Make changes using the DIP switches on the main circuit board.
When option settings are not made from the LonWorks, it is not
necessary to use these network variables.
Remote-
controller
prohibit
State Value
Start/stop
operation
Temp.
setting
Operating
mode
0 (Not used) O
O
O
1
100 ×
120 O
×
140 ×
150 O
O
×
160 ×
180 O
×200
×
Other
O :Permitted
× :Prohibited
Fan speed
setting
(Not
used)
120 Auto
200 High
150 Medium
100
Low
Other
Air
direction
setting
(Not
used)
200 Swing
170 F1
140 F2
110 F3
80 F4
50 F5
Other Swing
Filter
sign
Filter sign is reset when
data is updated.
[nv8] Option 1 setting status notifi cation
[nv10] Option 2 setting status notifi cation
network output SNVT_switch nvoOption1_00;
network output SNVT_switch nvoOption1_01;
network output SNVT_switch nvoOption1_02;
network output SNVT_switch nvoOption1_03;
network output SNVT_switch nvoOption2_00;
network output SNVT_switch nvoOption2_01;
network output SNVT_switch nvoOption2_02;
network output SNVT_switch nvoOption2_03;
These output network variables provide notifi cation of changes
in the status of the indoor unit option settings.
Two of the following 4 option settings can be selected:
remote-controller prohibit, fan speed setting, air direction
setting, and fi lter sign reset.
Make changes using the DIP switches on the main circuit
board.
They are output when the LonWorks Interface or A/C unit
power is reset.
Remote-
controller
prohibit
State Value
Start/stop
operation
Temp.
setting
Operating
mode
00 O
O
O
1
100 ×
120 O
×
140 ×
150 O
O
×
160 ×
180 O
×
200 ×
O :Permitted
× :Prohibited
Fan speed
setting
1
120 Auto
200 High
150 Medium
100 Low
50 Very
0 Stop
Air
direction
setting
1
200 Swing
170 F1
140 F2
110 F3
80 F4
50 F5
0 Stop
Filter
sign
0
0
OFF
1ON
(
(
(
(
(
* Positions F4
and F5 can not
be set for cool-
and dry-mode
operation.