Installation Manual

11
6. List of LonWorks Network Variables
A/C unit Input/output Item Variable name Variable type
Indoor group 0
Input
Start/stop nviOnOff_00 SNVT_switch
Temp. setting nviSetPoint_00 SNVT_temp_p
Operating mode nviHeatCool_00 SNVT_hvac_mode
Option 1 setting nviOption1_00 SNVT_switch
Option 2 setting nviOption2_00 SNVT_switch
Output
Start/stop status nvoOnOff_00 SNVT_switch
Temp. setting nvoSetPoint_00 SNVT_temp_p
Operating mode nvoHeatCool_00 SNVT_hvac_mode
Option 1 status nvoOption1_00 SNVT_switch
Option 2 status nvoOption2_00 SNVT_switch
Alarm status nvoAlarm_00 SNVT_switch
Indoor units with active alarms
nvoAlarmIn_00 SNVT_switch
Room temp. nvoSpaceTemp_00 SNVT_temp_p
Indoor unit status nvoInState_00 SNVT_count
Indoor group 1
Input
Start/stop nviOnOff_01 SNVT_switch
Temp. setting nviHeatCool_01 SNVT_temp_p
Operating mode nviSetPoint_01 SNVT_hvac_mode
Option 1 setting nviOption1_01 SNVT_switch
Option 2 setting nviOption2_01 SNVT_switch
Output
Start/stop status nvoOnOff_01 SNVT_switch
Temp. setting nvoSetPoint_01 SNVT_temp_p
Operating mode nvoHeatCool_01 SNVT_hvac_mode
Option 1 status nvoOption1_01 SNVT_switch
Option 2 status nvoOption2_01 SNVT_switch
Alarm status nvoAlarm_01 SNVT_switch
Indoor units with active alarms
nvoAlarmIn_01 SNVT_switch
Room temp. nvoSpaceTemp_01 SNVT_temp_p
Indoor unit status nvoInState_01 SNVT_count
Indoor group 2
Input
Start/stop nviOnOff_02 SNVT_switch
Temp. setting nviHeatCool_02 SNVT_temp_p
Operating mode nviSetPoint_02 SNVT_hvac_mode
Option 1 setting nviOption1_02 SNVT_switch
Option 2 setting nviOption2_02 SNVT_switch
Output
Start/stop status nvoOnOff_02 SNVT_switch
Temp. setting nvoSetPoint_02 SNVT_temp_p
Operating mode nvoHeatCool_02 SNVT_hvac_mode
Option 1 status nvoOption1_02 SNVT_switch
Option 2 status nvoOption2_02 SNVT_switch
Alarm status nvoAlarm_02 SNVT_switch
Indoor units with active alarms
nvoAlarmIn_02 SNVT_switch
Room temp. nvoSpaceTemp_02 SNVT_temp_p
Indoor unit status nvoInState_02 SNVT_count
Indoor group 3
Input
Start/stop nviOnOff_03 SNVT_switch
Temp. setting nviHeatCool_03 SNVT_temp_p
Operating mode nviSetPoint_03 SNVT_hvac_mode
Option 1 setting nviOption1_03 SNVT_switch
Option 2 setting nviOption2_03 SNVT_switch
Output
Start/stop status nvoOnOff_03 SNVT_switch
Temp. setting nvoSetPoint_03 SNVT_temp_p
Operating mode nvoHeatCool_03 SNVT_hvac_mode
Option 1 status nvoOption1_03 SNVT_switch
Option 2 status nvoOption2_03 SNVT_switch
Alarm status nvoAlarm_03 SNVT_switch
Indoor units with active alarms
nvoAlarmIn_03 SNVT_switch
Room temp. nvoSpaceTemp_03 SNVT_temp_p
Indoor unit status nvoInState_03 SNVT_count
Indoor groups 0 – 3 Input Emergency stop nviAllInOff SNVT_switch
Transmission intervals settings nciSndHrtBt SNVT_time_sec
Minimum time secured for transmission nciMinOutTm SNVT_time_sec
Pana_CZ-CLNC1U_Eng.indd 11Pana_CZ-CLNC1U_Eng.indd 11 2011/11/11 12:23:442011/11/11 12:23:44