Installation Manual

27
6 USING THE SYSTEM
B
Touch a distribution group. A keyboard window like the one shown above appears. Use the
keyboard to enter a distribution group number and to select the product type from among PAC,
GHP and HOT.
Select “Simple” or “Load” in the distribution methods.
* Refer to “10. Calculating air conditioner distribution” for details.
The tenant set at “Load” distribution will have its “No” box display in light blue.
* The distribution group number range is from 1 to 8.
* This button is invalid when “No Distrib.” has been set. (Refer to
Main
Sub
1
1
5
5
)
* The distribution group column set at loaded distribution has no product type such as “PAC” and “GHP”
displayed.
* Make manual cut-off in advance to change the distribution method.
C
Press the Type button to select “PAC” or “GHP” for the following unit that is unable to
automatically recognize product type.
- Interface adaptor
This is only for “Simple distribution” setting.
D
Specify which distribution method, “Simple” or “Load,” to apply to the selected distribution
group.
E
Touch Set to con rm the setting, or Cancel to cancel it.
PAC, GHP, and HOT cannot be mixed in the same group. Set up a separate distribution group for each
type.
HOT multi units cannot be recognized automatically (they are recognized as PAC). Manually set the
product type to HOT.
HOT Tenants cannot be set at the “Load” distribution.
“Load” distribution tenants cannot be set at “HOT”.
Air conditioners unadaptable to loaded distribution cannot be set at “Load” Distribution.
Interface adaptors are also unadaptable to loaded distribution.
Main
Sub
3
3
5
5