Datasheet

8
Item Unit
Single
V 230
Power Source (Phase, Voltage,
Cycle)
Hz 50
Input Power COOLING W 1060(170~1200)
HEATING W 1170(150~1320)
Starting Current A 5.20
Running Current COOLING A 4.70
HEATING A 5.20
Maximum Current A 6.80
Power Factor COOLING 98
HEATING % 98
Power factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Number of core
3 (1.5mm)
Power Cord
Length m
1.3
Thermostat
Electronic Control
Protection Device
Electronic Control
Note
z Specification is subject to change without prior notice for further improvement.
z Operational temperature range:
Indoor Outdoor
Temperature °C
* DBT *WBT *DBT *WBT
Maximum 32 23 43 26
COOLING
Minimum 16 11 16 11
Maximum 30 - 24 18
HEATING
Minimum 16 - -5 -6
NOTICE: This model is not suitable for 24 hours non-stopping operation in heating mode below -5°C. If this model
is used out of above conditions, the outdoor unit might be frozen up and stop operation for protection
control.
*DBT: Dry bulb temperature
*WBT: Wet bulb temperature