Datasheet
32
12.1.6 Low pressure Prevention control (Gas Leakage Detection)
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes.
2. If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
Comp Frequency 45 Hz or above 64 Hz or above 58 Hz or above 73 Hz or above
Total Outdoor Current
1b≤1<3 1b≤1<1.6 1b≤1<1.3 1b≤1<1.6
Indoor Piping Temp
20 ℃ or above 25 ℃ or less 20 ℃ or above 25 ℃ or less
Operation Mode Cool/Dry Heat Cool/Dry Heat
Model UE9JKE UE12JKE
12.1.7 Low Operation Frequency Protection Control
If all following conditions exists, the compressor will run with the frequency of 40 Hz (UE9JKE, UE12JKE) or 30Hz
(RE15JKE)
Models UE9JKE, UE12JKE
Intake Air Temp.
≥30 ℃ or <15 ℃
-------------------
Outdoor Temp.
≥38 ℃ or <16 ℃ ≥24 ℃ or <4 ℃
Indoor Piping Temp.
<30 ℃ ≥0 ℃
Operation Mode Cool / Dry Heat
12.1.8 Compressor Tank Temperature Rise Protection Control
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4℃.
Indoor temperature and outdoor temperature is 30±5℃.
Remote Control setting 16℃ and Hi Fan Speed.
• During Heating operations:
Indoor piping temperature - indoor suction is under 5℃.
Indoor temperature and outdoor temperature is 20 ± 2℃.
Remote control setting 30℃ and Hi Fan Speed.
b. Control contents
• Compressor stops (and restart after 3 minutes)
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
12.2 Protection Control for Cooling and Soft Dry Operation
12.2.1 Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
• This control will begin 1 minute after the compressor starts.
• Compressor frequency will adjust base on outdoor air temperature.
Outdoor air tem
p
.
(
℃.
)
38
25
18
11
free
Free
38
26
16
37
22
15
8
Outdoor air tem
p
.
(
℃.
)