Datasheet

Down to
-15 ºC in
cooling mode
OUTDOOR
TEMPERATURE
Down to
-15 ºC in
heating mode
OUTDOOR
TEMPERATURE
Complete line-up with high efficiency even at -15 °C
This wall-mounted air conditioner is especially designed for professional applications such as
computer rooms where cooling inside the room is necessary even when the outside temperature
is low. Furthermore this air conditioner has an automatic changeover system, in order to maintain
the inside temperature even when sharp outside temperature changes occur.
WALL MOUNTED
PROFESSIONAL
INVERTER -15 °C
ON COOLING MODE
KIT KIT-E9-PKEA KIT-E12-PKEA KIT-E15-PKEA KIT-E18-PKEA
Indoor CS-E9PKEA CS-E12PKEA CS-E15PKEA CS-E18PKEA
Outdoor CU-E9PKEA CU-E12PKEA CU-E15PKEA CU-E18PKEA
Cooling capacity Nominal (Min - Max) kW 2.50 (0.85-3.00) 3.50 (0.85-4.00) 4.20 (0.98-5.00) 5.00 (0.98-6.00)
Nominal (Min - Max) kCal/h 2,150 (730-2,580) 3,010 (730-3,440) 3,610 (840-4,300) 4,300 (840-5,160)
EER
1)
Nominal (Min - Max) Energy Saving
4.85 (4.23-5.00)
A
4.02 (3.57-5.00)
A
3.50 (3.50-3.16)
A
3.47 (3.50-3.02)
A
SEER Nominal Energy Saving
7.1
A++
6.7
A++
6.3
A++
6.9
A++
P Design at -10 °C kW 2.5 3.5 4.2 5.0
Power input Cooling Nominal (Min - Max) kW 0.515 (0.17-0.71) 0.87 (0.17-1.12) 1.20 (0.28-1.58) 1.44 (0.28-1.99)
Annual Energy Consumption (cooling) kWh 123 183 233 254
Heating capacity Nominal (Min - Max) kW 3.40 (0.85-5.40) 4.00 (0.85-6.60) 5.40 (0.98-7.10) 5.80 (0.98-8.00)
Nominal (Min - Max) kCal/h 2,920 (730-4,640) 3,440 (730-5,680) 4,640 (840-6,110) 4,990 (840-6,880)
Heating capacity at -7°C Nominal kW 3.91 4.78 5.14 5.80
COP
1)
Nominal (Min - Max) Energy Saving
4.86 (4.12-5.15)
A
4.35 (3.63-5.15)
A
3.75 (2.88-3.24)
A
3.82 (2.88-3.11)
A
SCOP Nominal Energy Saving
4.4
A+
4.1
A+
3.9
A
4.2
A+
P Design at -10 °C kW 2.8 3.6 3.6 4.4
Power input Heating Nominal (Min - Max) kW 0.7 (0.165-1.31) 0.92 (0.165-1.82) 1.44 (0.34-2.19) 1.52 (0.340-2.57)
Annual Energy Consumption (heating) kWh 891 1229 1292 1467
Indoor Unit
Power source V 230 230 230 230
Recommended Fuse A
Recommended power cable section mm
Connection indoor / outdoor mm 4 x 1.5 4 x 1.5 4 x 1.5 4 x 2.5
Current (Nominal) Cooling / Heating A 2.5 / 3.3 4.0 / 4.2 5.4 / 6.5 6.4 / 6.8
Max. Current A 7.8 8.4 9.6 11.3
Air Volume Cooling / Heating m³/h 798 / 876 816 / 882 846 / 900 1074 / 1158
Moisture removal volume l/h 1.5 2,0 2.4 2.8
Sound pressure Level
2)
Cooling (Hi / Lo / S-Lo) dB(A) 39 / 26 / 23 42 / 29 / 26 43 / 32 / 29 44 / 37 / 34
Heating (Hi / Lo / S-Lo) dB(A) 40 / 27 / 24 42 / 33 / 30 43 / 35 / 32 44 / 37 / 34
Sound power Level Cooling (Hi) dB 55 58 59 60
Heating (Hi) dB 56 58 59 60
Dimensions
3)
H x W x D mm 295 x 870 x 255 295 x 870 x 255 295 x 870 x 255 295 x 1070 x 255
Net weight Kg 10 10 10 13
Air purifier filter
Outdoor Unit
Air Volume Cooling / Heating m³/h 1878 / 1782 1974 / 1926 2052 / 1980 2352 / 2274
Sound pressure Level
2)
Cooling / Heating (Hi) dB(A) 46 / 47 48 / 50 46 / 46 47 / 47
Sound power Level Cooling / Heating (Hi) dB 61 / 62 63 / 65 61 / 61 61 / 61
Dimensions 3) H x W x D mm 622 x 824 x 299 622 x 824 x 299 695 x 875 x 320 695 x 875 x 320
Net weight Kg 36 36 45 46
Piping connections Liquid pipe inch (mm) 1/4" (6.35) 1/4" (6.35) 1/4" (6.35) 1/4" (6.35)
Gas pipe inch (mm) 3/8" (9.52) 3/8" (9.52) 1/2" (12.70) 1/2" (12.70)
Refrigerant Loading R410A Kg 1,100 1,100 1.060 1.240
Elevation difference (in/out) 4) Max m 5 5 15 15
Piping length Min / Max m 3-15 3-15 3-15 3-20
Piping length without
refrigerant increase
Max m 7.5 7.5 7.5 7.5
Additional gas g/m 20 20 20 20
Operating range Cooling Min / Max °C -15 / +43 -15 / +43 -15 / +43 -15 / +43
Heating Min / Max °C -15 / +24 -15 / +24 -15 / +24 -15 / +24
Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb)
This model is not suitable to use in heating mode below -5 °C with continuous operation (24 h operation).
1) EER and COP classification is at 230 V in accordance with EU directive 2002/31/EC. 2) The annual consumption is calculated by multiplying the input power at 230 V by an avarage of 500 hours per year in cooling mode. 3) The Sound pressure level of the units shows
the value measured of a position 1 meter in front of the main body and 0,8 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification. 4) Add 70 mm for piping port. 5) When installing the outdoor unit at a higher position
than the indoor unit.
Specifications subject to change without notice.
A class
energy saving
Easy
control
by BMS
CONNECTIVITY
5 year
compressor
warranty
Internet
Control
Ready
INTERNET CONTROL
OPTIONAL