18.1.5 CS-XE24WKUAW CU-XE24WKUA
Rated frequency (compressor speed is fixed during forced heating or cooling for capacity measurement and
diagnosis purpose)
Indoor (°C / °F) Outdoor (°C / °F)
DB WB -20 (-4.0) -10 (14.0) 0 (32.0) 5 (41.0)
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
27
(80.6)
19 (66.2) 29537 24727 1583 29508 24702 1564 29471 25145 1517 29389 24589 1504
22 (71.6) 33883 20211 1383 33849 20191 1366 32267 19752 1584 30096 18519 1580
23
(73.4)
16 (60.8) 25994 25734 1746 25968 25708 1725 27606 27330 1436 26318 26055 1592
18 (64.4) 29060 19023 1599 29031 19004 1579 32347 21043 1250 30137 17932 1662
20
(68.0)
13 (55.4) 22882 22653 1733 22859 22631 1711 22712 22485 1137 21891 21672 1359
16 (60.8) 2876 2000 2000 2876 2000 1976 2876 2000 1182 2876 2000 1167
Indoor (°C / °F) Outdoor (°C / °F)
DB WB 16 (60.8) 25 (77.0) 35 (95.0) 46 (114.8)
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
27
(80.6)
19 (66.2) 29275 24910 1483 25617 22148 2022 23973 22055 2200 16455 15139 1978
22 (71.6) 30286 19813 1488 27857 17528 2044 26454 13778 2229 18158 9457 2004
23
(73.4)
16 (60.8) 27145 26874 1483 23702 23465 1983 21938 21719 2323 15058 14908 2088
18 (64.4) 29627 18928 1487 26054 16870 2005 24151 16362 2365 16577 11231 2127
20
(68.0)
13 (55.4) 23731 23493 1241 22199 21977 1982 20229 20027 2282 13885 13746 2052
16 (60.8) 2876 2000 2012 2876 2000 2544 2876 2000 2486 2876 2000 2235