ORDER NO. RAC0602010C2 Multi Air Conditioner CS-ME7EB1E CS-ME10EB1E CS-ME12EB1E CS-ME14EB1E Please file and use this manual together with the service manual for Model No. CU-3E23CBPG, CU4E27CBPG, Order No. RAC0209005C2 and CU-3E18EBE, Order No. RAC0503011C2. CONTENTS Page Page 1 Safety Precautions 3 10.1. Simultaneous Operation Control 18 2 Features 5 10.2. Airflow Direction Control 19 3 Functions 6 10.3. Indoor Fan Control 20 3.1. REMOTE CONTROL 6 10.4. Drain Pump Control 22 3.2.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 13.1. OPERATION CHARACTERISTICS 14 Exploded View & Replacement Parts List 40 14.1. Exploded View 45 45 14.2. Replacement Parts List 46 Operating instructions of this product can be referred at following Web site. http://phaam.panasonic.com.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 1 Safety Precautions 3
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 4
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 2 Features · Product − A single OUTDOOR unit enables air conditioning of up to four separate rooms Remarks: 1. At least two indoor units must be connected. 2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within connectable capacity range of outdoor unit. (Shown in the above table) Example: The below indoor units combination is not possible to connect CU-3E23CBPG.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 3 Functions 3.1.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 3.2.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 8
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 4 Product Specifications Model Item Power Source Air Volume Cooling Heating Cooling (Power) Heating (Power) Noise Level Moisture Removal Refrigeration piping Connection Liquid Gas Type of pipe Type of Indoor/Outdoor connecting cable Drain opening Dimensions Net Weight Fan Type Motor Type Output Heat exchanger Adjustments Switches Timer Temperature Air filter CS-ME7EB1E m3/min. m3/min.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 5 Dimensions 5.1.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 11
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 5.2.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 6 Refrigeration Cycle Diagram 13
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 7 Block Diagram CS-ME7EB1E/ME10EB1E/ME12EB1E/ME14EB1E 14
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 8 Wiring Diagram 15
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 9 Electronic Circuit Diagram CS-ME7EB1E CS-ME10EB1E CS-ME12EB1E CS-ME14EB1E 16
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 17
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 10 Operation Details (Functions & Protection) 10.1. Simultaneous Operation Control 1. Operation modes which can be selected using the remote control unit: Automatic, Cooling, Soft Dry, Heating, Fan operation mode. 2.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 10.2. Airflow Direction Control The following shows how louver operation changes depending on the direction set with the AIR SWING button and other operating conditions. Cooling and Dry Heating · The louver stops at the CLOSE position when the power switch or breaker is ON. · The louver stops at their current position when the power switch or breaker is OFF. · Move the horizontal airflow direction control louver manually.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 10.3. Indoor Fan Control · The following shows how fan speed changes depending on the setting made with the FAN SPEED button and other operating conditions. · Actual fan speed may differ from that you set with remote control.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 21
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 10.4. Drain Pump Control Basic operation · The drain pump starts 50 seconds after the indoor unit starts or the thermostat comes on (i.e., 10 seconds after the fan motor starts). The drain pump stops 30 seconds after the indoor unit stops or the thermostat turns off. · The drain pump repeats a cycle of on for 30 seconds then off for between 50 and 90 seconds as long as the unit is operating.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 10.5. Auto Restart Control · if there is a power failure, operation will automatically be restarted when the power is resumed. It will start with the previous operation mode and airflow direction. (Time Delay Safety Control is valid) 1. Control start conditions <1> The 24-hour timer must not be set. <2> The sleep timer must not be set. Auto restart control is not available when timer or sleep mode is set. 2.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 10.6. Other Indoor Unit Operation Functions 10.6.1. Auto button Proceed with operation when the air conditioner is stopped. (When the auto button is pressed during operation, the air conditioner is stopped.) 1. Emergency operation Press the auto button and release it within 5 seconds to perform emergency operation. Under normal condition (failure is not occurred) automatic operation is performed.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 10.6.2. Drain Test When installing the unit and you want the drain pump to operate independently, press the DRAIN TEST switch to operate it for about 5 minutes.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 10.6.3. Self Diagnosis display 10.6.3.1. BreakDown Self Diagnosis Function (Three Digits Alphanumeric Code) · Once abnormality has been detected during operation, the unit will immediately stop its operation. (Timer LED blinks.) · Although timer LED goes off when power supply is turned off, if the unit is operated under a breakdown condition, the LED will light up again. · In operation after breakdown repair, error code is not displayed.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 10.6.3.2. Error Code Symbol Diagnosis H11 Indoor / Outdoor abnormal communication H12 Indoor unit capacity unmatched H14 Intake air temp. sensor H16 Outdoor Current Transformer Diagnosis method This error occurs when indoor/outdoor unit communication fails to be established after 30 seconds or more. 1.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E Symbol Diagnosis H30 Outdoor discharge pipe temp. sensor Diagnosis method Disconnected discharge sensor When the condensation temperature is higher than the discharge temperature + (plus) 6°C, a sensor disconnection is detected, operation stops, and the error occurs (the timer lamp blinks). 1. This error occurs when a temperature which is impossibly high or low from a normal standpoint has been detected.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E Symbol Diagnosis H99 Indoor operating unit freezing Diagnosis method The restriction on the compressor frequency is started when the indoor unit heat exchanger temperature is between 8°C and 12°C. Operation stops if a temperature below 0°C continues for 6 minutes. Three minutes later, operation is started up at a temperature from 3°C to 8°C. The restriction on the compressor frequency is released at a temperature between 13°C and 14°C.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E Symbol Diagnosis Diagnosis method F97 Compressor high This error occurs and operation stops when this happens on 6 occasions (it is cleared when the operation is discharge temperature normal for 20 minutes). 1. Check the refrigerating cycle: Gas may be leaking (The amount of refrigerant is low). The stopping of the outdoor unit from time to time is a symptom of this error. 2.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 11 Installation Instructions 31
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 32
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 33
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 34
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 35
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 12 Disassembly of Parts High voltages are generated in the electrical parts area by the capacitor, Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 12.1. Detaching the fan motor and cross flow fan 36 1) Open the air inlet section of the front grille.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 8) Detach the air guide and unscrew the screw on the heat exchanger. 9) Detach the float switch and unscrew the 3 screws and disengage the 2 catches on the fan motor holder. 10) Loosen the screw fixing the shaft between the cross flow fan and the fan motor and detach the fan motor. 11) Remove the cross flow fan. 12.2. Detaching the drain pump 8) Unscrew the screw on the drain pump holder and detach it.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 3) Loosen the screw on the cover and detach the cover. 4) Unscrew the 2 screws on the control section cover and detach all connectors. 5) Disengage the catch on the control board and remove it.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 12.4. Detaching the louver motor 3) Loosen the screw on the cover and detach the cover. 4) Unscrew the 2 screws on the control section cover and detach the connector for the louver motor. 5) Unscrew the screw and disengage the 2 catches on the air outlet grille. 6) Unscrew the 2 screws on the louver motor on the back of the air outlet grille and remove the louver motor.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 13 Technical Data 13.1.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 41
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 42
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 43
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 44
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 14 Exploded View & Replacement Parts List 14.1. Exploded View Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E 14.2. Replacement Parts List Ref. No.