Datasheet
KIT KIT-E9-PD3EA KIT-E12-PD3EA
Indoor CS-E9PD3EA CS-E12PD3EA
Outdoor CU-E9PD3EA CU-E12PD3EA
Cooling capacity Nominal (Min-Max) kW 2,50 (0,85 - 3,00) 3,40 (0,85 - 4,00)
Nominal (Min-Max) kCal/h 2.150 (731 - 2.580) 2.920 (730 - 3.440)
SEER W/W
5,80 h 5,60 a
Pdesign (cooling) kW 2,50 3,40
Power input cooling Nominal (Min-Max) kW 0,590 (0,240 - 0,760) 0,880 (0,240 - 1,160)
Annual electricity consumption (cooling)
1)
kWh/a 151 213
Heating capacity Nominal (Min-Max) kW 3,20 (0,85 - 4,60) 4,00 (0,85 - 5,10)
Nominal (Min-Max) kCal/h 2.752 (731 - 3.960) 3.440 (730 - 4.390)
SCOP Nominal Energy Saving
4,20 h 3,80 a
Pdesign at -10°C kW
2,60 2,90
Power input heating Nominal (Min-Max) kW 0,860 (0,230 - 1,380) 1,130 (0,230 - 1,550)
Annual electricity consumption (heating)
1)
kWh/a 867 1.068
Indoor Unit
Power source V 230 230
Recommended fuse A 16 16
Recommended power cable section mm² 1,5 1,5
Connection mm² 4 x 1,5 to 2,5 4 x 1,5 to 2,5
Current (Nominal) Cooling / Heating A 2,8 / 4,00 4,1 / 5,15
External static pressure
2)
S-Hi / Hi / Me / Lo Pa 110 / 60 / 30 / 20 80 / 50 / 25 / 10
Air volume Cooling / Heating m³/h 414 / 486 540 / 630
Moisture removal volume l/h 1,50 2,30
Sound pressure level
3)
Cooling (Hi / Lo / S-Lo) dB(A) 33 / 27 / 24 33 / 27 / 24
Heating (Hi / Lo / S-Lo) dB(A) 35 / 28 / 25 35 / 28 / 25
Sound power level Cooling (Hi) dB 49 49
Heating (Hi) dB 51 51
Dimensions H x W x D mm 235 x 750 x 370 235 x 750 x 370
Net weight kg 17 17
Dust filter No No
Outdoor Unit
Power source V 230 230
Air volume Cooling/Heating m³/h 1.878 / 1.782 2.052 / 1.836
Sound pressure level
3)
Cooling / Heating (Hi) dB(A) 47 / 47 46 / 47
Sound power level Cooling / Heating (Hi) dB 62 / 62 61 / 62
Dimensions
4)
H x W x D mm 622 x 824 x 299 695 x 875 x 320
Net weight kg 36 45
Piping connections Liquid / Gas pipe Inch (mm) 1/4 (6,35) / 3/8 (9,52) 1/4 (6,35) / 3/8 (9,52)
Refrigerant loading R410A kg 1,10 1,14
Elevation difference (in/out) Max m 15 15
Piping length Min / Max m 3 / 20 3 / 20
Precharge length Max m 7,5 7,5
Additional charge g/m 20 20
Operating range Cooling Min/Max °C -10 / +43 -10 / +43
Heating Min/Max °C -10 / +24 -10 / +24
4,20 A+
SCOP
SEASONAL COEFFICIENT
OF PERFORMANCE
Down to
-10 ºC in
heating mode
OUTDOOR
TEMPERATURE
Designed for homes, offices, retail and restaurants, this Duct is ideal for small rooms where the air
conditioning and the heating should be nicely integrated and where high comfort and efficiency is needed.
The new 9 and 12kW duct can also be connected to KNX, Modbus, EnOcean interfaces for easy integration with
your BMS systems. This interfaces have dry contacts (ON/OFF, error message) for easy integration.
With the new Intesishome interface, you can control the Duct also from your smartphone and internet very
easily!
LOW STATIC PRESSURE
HIDE AWAY
INVERTER
5,80 A+
SEER
SEASONAL ENERGY
EFFICIENCY RATIO
Energy
saving
Down to
-10 ºC in
cooling mode
OUTDOOR
TEMPERATURE
Rating Conditions: Cooling Indoor 27°C DB / 19°C WB. Cooling Outdoor 35°C DB / 24°C WB. Heating Indoor 20°C DB. Heating Outdoor 7°C DB / 6°C WB. (DB: Dry Bulb; WB: Wet Bulb)
1) The annual energy consumption is calculated in accordance with the ErP directive. 2) The specification listed on the table indicates values under the condition of 29 Pa (3,0 mmAq) which are applied for factory default setting. Change switch on PCB from Hi to Shi to
have more than 6,0 mmAq. 3) The Sound pressure level of the units shows the value measured of a position of 1.5 m below the unit with 1 m duct on the suction side and 2 m duct on the discharge side. The sound pressure is measured in accordance with Eurovent
6/C/006-97 specification. 4) Add 100 mm for indoor unit or 70 mm for outdoor unit for piping port.
Specifications subject to change without notice.
For detailed information about ErP, please visit our page http://www.ptc.panasonic.eu
INTERNET CONTROL READY: Optional. SEER and SCOP: For KIT-E9-PD3EA.
Internet
Control
Ready
INTERNET CONTROL
OPTIONAL
Easy
control
by BMS
CONNECTIVITY
Possible
to use on
R22 pipings
R22 RENEWAL
5 year
compressor
warranty
58