Datasheet

Possible
to use on
R22 pipings
R22 RENEWAL
Etherea with enhanced Econavi sensor and new Nanoe-G air-purifying system: outstanding
efficiency, comfort and healthy air combined with state-of-the-art design.
Econavi features an in-built human activity sensor and a new sunlight detection technology to adjust output
thereby giving you the best comfort at anytime whilst saving energy. Econavi not only optimizes air flow
orientation and volume according to human presence, it also reduces cooling power automatically by no/less
sunshine. With Econavi, energy savings of up to 38% are possible, whilst increasing your comfort.
Furthermore, the Nanoe-G revolutionary air-purifying system utilises nano technology fine particles to remove
and deactivate 99% of both airborne and adhesive micro-organisms like bacteria, viruses and mould.
WALL MOUNTED ETHEREA
INVERTER+
SILVER PLATED / WHITE
INTERNET CONTROL READY: Optional. SEER and SCOP: For KIT-XE18-QKE and KIT-E18-QKE. MILD DRY: Maintains a Relative Humidity up to 10% higher than cooling operation. Ideal when sleeping with the air conditioner on.
Energy
saving
Easy
control
by BMS
CONNECTIVITY
5 year
compressor
warranty
Up to 38%
energy savings
(cooling)
Air purifier
99%
removal
bacteria · virus · mold
Perfect
humidity
control
MILD DRY
Improved
comfort
AUTOCOMFORT
Internet
Control
Ready
INTERNET CONTROL
OPTIONAL
Kit Silver Plated KIT-XE18-QKE
Kit Silver Plated / with Smartphone Control KIT-XE18-QKE-WIFI
Kit White KIT-E18-QKE KIT-E21-QKE KIT-E24-QKE KIT-E28-QKE
Kit White / with Smartphone Control KIT-E18-QKE-WIFI KIT-E21-QKE-WIFI KIT-E24-QKE-WIFI KIT-E28-QKE-WIFI
Indoor Silver plated CS-XE18QKEW
Indoor White CS-E18QKEW CS-E21QKEW CS-E24QKEW CS-E28QKES
Outdoor CU-E18QKE CU-E21QKE CU-E24QKE CU-E28QKE
Cooling capacity Nominal (Min - Max) kW 5,00 (0,98 - 6,00) 6,30 (0,98 - 7,10) 6,80 (0,98 - 8,10) 7,65 (0,98 - 8,60)
Nominal (Min - Max) kCal/h 4.300 (840 - 5.160) 5.420 (840 - 6.110) 5.850 (840 - 6.970) 6.580 (840 - 7.400)
SEER Nominal Energy Saving
6,90 i 6,50 i 6,10 i 6,00 h
Pdesign (cooling) kW 5,0 6,3 6,8 7,7
Power input cooling Nominal (Min - Max) kW 1,440 (0,280 - 1,990) 2,180 (0,280 - 2,500) 2,080 (0,380 - 2,650) 2,520 (0,380 - 2,920)
Annual electricity consumption (cooling)
1)
kWh/a 254 339 390 449
Heating capacity Nominal (Min - Max) kW 5,80 (0,98 - 8,00) 7,20 (0,98 - 8,50) 8,60 (0,98 - 9,90) 9,60 (0,98 - 11,00)
Heating capacity at -7°C Nominal (Min - Max) kW 4.990 (840 - 6.880) 6.190 (840 - 7.310) 7.400 (840 - 8.510) 8.260 (840 - 9.460)
SCOP Nominal Energy Saving
4,20 h 4,00 h 3,90 a 3,80 a
Pdesign at -10°C kW 4,4 4,6 5,5 6,0
Power input heating Nominal (Min - Max) kW 1,520 (0,340 - 2,570) 2,090 (0,340 - 2,730) 2,580 (0,450 - 3,100) 3,240 (0,450 - 3,650)
Annual electricity consumption (heating)
1)
kWh/a 1.467 1.610 1.974 2.211
Indoor Unit
Power source V 230 230 230 230
Recommended fuse A 16 20 20 20
Recommended power cable section mm² 1,5 2,5 2,5 2,5
Connection indoor / outdoor mm² 4 x 2,5 4 x 2,5 4 x 2,5 4 x 2,5
Current (Nominal) Cooling / Heating A 6,4 / 6,8 9,7 / 9,4 9,5 / 11,7 11,5 / 14,5
Maximum current A 11,3 11,9 14,4 15,5
Air volume Cooling / Heating m³/h 1074 / 1158 1.134 / 1.200 1.188 / 1.272 1.266 / 1.314
Moisture removal volume l/h 2,8 3,5 3,9 4,5
Sound pressure level
2)
Cooling (Hi / Lo / Q-Lo) dB(A) 44 / 37 / 34 45 / 37 / 34 47 / 38 / 35 49 / 38 / 35
Heating (Hi / Lo / Q-Lo) dB(A) 44 / 37 / 34 45 / 37 / 34 47 / 38 / 35 48 / 38 / 35
Sound power level Cooling / Heating (Hi) dB 60 / 60 61 / 61 63 / 63 65 / 64
Dimensions H x W x D mm 295 x 1.070 x 255 295 x 1.070 x 255 295 x 1.070 x 255 295 x 1.070 x 255
Net weight kg 13 13 13 13
Air purifier filter Nanoe-G Nanoe-G Nanoe-G Nanoe-G
Outdoor Unit
Air volume Cooling / Heating m³/h 2.352 / 2.274 2.502 / 2.424 3.012 / 3.012 3.270 / 3.270
Sound pressure level
2)
Cooling / Heating (Hi) dB(A) 47 / 47 48 / 49 52 / 52 53 / 53
Sound power level Cooling / Heating (Hi) dB 61 / 61 62 / 63 66 / 66 67 / 67
Dimensions
3)
H x W x D mm 695 x 875 x 320 695 x 875 x 320 795 x 875 x 320 795 x 875 x 320
Net weight kg 46 47 67 67
Piping connections Liquid pipe / Gas pipe inch (mm) 1/4" (6,35) / 1/2" (12,70) 1/4" (6,35) / 1/2" (12,70) 1/4" (6,35) / 5/8" (15,88) 1/4" (6,35) / 5/8" (15,88)
Refrigerant loading R410A kg 1,24 1,32 1,80 1,80
Elevation difference (in/out) Max m 15 15 20 20
Piping length Min / Max m 3 / 20 3 / 20 3 / 30 3 / 30
Precharge length Max m 7,5 7,5 10 10
Additional charge g/m 20 20 30 30
Operating range Cooling Min / Max °C -10 / +43 -10 / +43 -10 / +43 -10 / +43
Heating Min / Max °C -15 / +24 -15 / +24 -15 / +24 -15 / +24
Rating Conditions: Cooling Indoor 27°C DB / 19°C WB. Cooling Outdoor 35°C DB / 24°C WB. Heating Indoor 20°C DB. Heating Outdoor 7°C DB / 6°C WB. (DB: Dry Bulb; WB: Wet Bulb)
Connectivity restriction: JKE units are not compatible with QKE units.
1) The annual energy consumption is calculated in accordance with the ErP directive. 2) The Sound pressure level of the units shows the value measured of a position 1 metre in front of the main body and 0,8 m below the unit. The sound pressure is measured in
accordance with Eurovent 6/C/006-97 specification. Q-Lo: Quiet mode. Lo: The lowest fan speed. 3) Add 70 mm for piping port.
Specifications subject to change without notice.
For detailed information about ErP, please visit our page http://www.ptc.panasonic.eu
Awarded with the
prestigious IF Design
Award 2013
6,90 A++
SEER
SEASONAL ENERGY
EFFICIENCY RATIO
4,20 A+
SCOP
SEASONAL COEFFICIENT
OF PERFORMANCE
44