Data Sheet
Panasonic North America
Air Conditioning Division
1690 Roberts Blvd., NW, Suite 110
Kennesaw, GA 30144
us.panasonic.com/aircon
Features
Controls Microprocessor
Remote Controller LCD Wired Type, Temp. Sensor
Built in
Temperature Control IC Thermostat
Timer 72 Hr. On/Off
Night Setback Built-In
Air Louver, Horizontal Manual
Air Louver, Vertical Automatic
Power Failure Automatic
Changeover
Built-In
Heating/Cooling Automatic
Changeover
Built-In
Self-Diagnosis Built-In
Air Filter Washable, Anti-Mold
Operating Range
Indoor Air Intake Temp
Outdoor Air Intake Temp
Cooling (Max) 95F DB/71F WB 115F DB
Cooling (Min) 67 DB/57F WB 0F DB
Heating (Max) 80F DB/67F WB 75F DB/65F WB
Heating (Min) -DB/-WB 5F DB
Performance Data @ ARI Standard Conditions (230V)
Cooling
Total Capacity (BTU/H) 24,400 (9,500 - 24,400)
Sensible Capacity (BTU/H) 14,330
Latent Capacity (BTU/H) 10,070
SEER 14.5
Dehumidification (Pints/H) 7.7
Amps (A) 15.6/17.3
Power Inputs (W) 2,880/2,880
Outdoor Sound Rating (dB-A) 49
Heating
Total Capacity (BTU/H) 30,800 (8,000 - 30,800)
HSPF 10.3
Amps (A) 16.4/18.1
Max Amps (A) 16.4/18.1
Power Inputs (W) 3,000/3,000
Back-up Strip Heather (KW) 0.00/0.00
Outdoor Sound Rating (dB-A) High 49
Option
Refrigerant Line Set Available
Fresh Air Intake Knock-out
Airduct Extension N/A
Indoor Frame Extension N/A
Condensate Drain Pump Available
Non-Removeable Remo-con
Bracket
Available