User Manual

Packet Power Monitoring Module Users Manual
Copyright 2009-2013 Packet Power, LLC.
26
Environmental
Operating conditions
All versions
Operating temperature
-7 to +45 C (+20 to +113F)
Humidity
5% to 95% non-condensing
Max. operating altitude
2000m (6561ft)
Pollution degree
2
Communication
Information gathered by the PMM is transmitted via a Packet Power radio network operating
in a subset of the range between 860 and 930MHz (the exact frequencies vary with region
please contact Packet Power for details). The network operates in a mesh topology. Each
device in the network must be within range of at least one other device in the network. The
effective range of the radio in the PMM varies depending on several factors, including the
environment in which the product is used. Typically, the device has an effective range of 50
to over 100 feet. The PMM will not transmit effectively if it is installed in an enclosure that
blocks radio signals.
Every site where the PMM is deployed must have installed at least one compatible Packet
Power Gateway device and associated software to collect data and prepare it for
transmission to approved monitoring and analysis applications.
The frequency with which monitoring information is gathered from a PMM depends primarily
on the ratio of the number of PMMs to the number of gateways. It can range from every
few seconds to 100 seconds or more.
Note: In the event of a loss of power to the PMM, energy consumption information
(Wh) for all three channels and the total is retained in non-volatile memory and will be
transmitted when power is restored.
Sample Label
Note the PMM is manufactured in two different models with different input power source
requirements. The required type of input power is indicated on the product safety label.