User Manual
Packet Powerâ„¢ Wireless Current Monitoring Module Manual
Copyright 2009-2013 Packet Power, LLC.
7
Figure 5. CMM wiring diagram
Wiring the CMM
FOLLOW ALL OF THE FOLLOWING SAFETY PRECAUTIONS BEFORE WIRING THE
CMM.
1. Place the CT interface board and power supply in the optimal locations using
adhesive tabs or using the holes provided (use PCBA stand offs when mounting the
CMM interface board). The CMM, power supply and all connections must be fully
enclosed.
2. Connect the ribbon cable from the interface board to the CMM module. Note that
Packet Power offers ribbon cables in different lengths.
3. Connect the 5 VDC power source to the interface board. If using the 5 VDC
universal micro power supply make sure to provide a disconnect and over current
protection (1.0 A fused recommended) at the supply source. Refer to the wiring
diagram for details.
4. Connect the CTs to the Interface Board observing the polarity of the CT wires as
well as the proper orientation of the CT on the conductor. The indicator marker on
the CT shall always face the source of the current. Refer to figure 3 below as well as
the Packet Power current transformer data sheet for detailed information. Failure to
observe the correct polarity will result in negative or incorrect current readings.