User Manual

©2014PacketPowerLLCwww.packetpower.comEM31.2 17
E306LCDDisplay
DRYCONTACTSENSING
BoththeE306andE312monitorscanbeusedtosensethestatusofdrycontactcircuits(i.e.openor
closedstatus)usinganyofthetemperatureprobeports.ConsultwithPacketPoweronhowtoconfigure
yourdevicesfordrycontactclosure.ConsultPacketPowerwhenusingthedevice
fordrycontacts.
DISPLAYANDCOMMUNICATIONS
LCDDISPLAY(E306Monitor):TheE306monitorincludesalocalLCDdisplaythatwillindicatethedevice
status,andinputmeasurementsinarotationindicatedinthechartbelow:
Display Description Display
COM: Communicationsstatus(indicatesifthe
deviceisproperlycommunicationwith
thegateway)
[NONE]/[OK]
0: Internaltemperaturesensor [XX.XC]…[XX.XF]
16: Probe16status;eithertemperature
measurementordrycontactstatuswhen
usedasdrycontactinput
[XX.XC]…[XX.XF]
OR[OPEN]OR
[CLOSED]
RH: Relativehumidity(onlyonmonitors
equippedwithrelativehumidity)
[XX%]
DP: Differentialpressure(onlyonmonitors
equippedwithdifferentialpressure)
[XXXP]
LEDDISPLAYANDCONTROLBUTTON(E312Monitor)
TheE312monitorincludesalocalLEDdisplaythatwillindicatethedevicestatusaswellasbattery
status.
Function Description Display
GreenLED
RedLED
Button
OPEN(NONCONNECTED)ANDCLOSED(SHORTED)PORTS:Whenthereisnoprobeinthepluggedinto
aprobeport,theLCDdisplayandthetemperaturereadingwillread48C”.48C”canbeusedasa
finitenumbertoindicateanunpluggedprobeport.Likewiseareading
of“+75C”willbecausedfroma
deadshortontheprobeorcontactclosure.Thesevaluescanbeusedtogeneratealarmconditionsfor