User Manual

©2014PacketPowerLLCwww.packetpower.comEM31.2 11
DETERMINGPROBELENGTH:Thechartbelow(PROBELENGTHCONFIGURATIONCHART)liststhecable
lengthsrequiredforatypical4248RUrack.Lengthsarelistedbyplacementlocations(i.e.top1/3,
middle1/3orbottomthirdsectionsoftherack).Pro bes canbepurchasedindividuallyoraskitsetsfor
monitoringonetosixrackspermonitor.
Thehighlightednumbersineachsectiondenotetheprobelengthsincludedwiththeprobekits.Probe
kitsprovidethesixprobesneededformonitoringonetosixcabinets.
Typicalcableroutingisalongtheinsideperimeteroftherackwiththecablesecured
usingwiretiesor
adhesivecabletabs.Itisassumedthatthemonitorwillbelocatedontheoutsidetopsectionofthe
centeroftheroofoftherack.
PROBELENGTHCONFIGURATION
CHART
Top Middle Bottom
11(Front) 2m 2m 3m x
1(Back) 2m 2m 3m x
2 1 2m 2m 3m x
22m3m4mx
3 1 2m 3m 4m
22m2m3mx
32m3m4m
4 1 2m 3m 4m
22m2m 3m x
32m3m4mx
43m4m4m
5 1 3m 4m 4m
22m3m4m
32m2m3mx
42m3m4m
53m4m4m
6 1 3m 4m 4m
22m3m4m
32m2m3mx
42m3m4mx
53m4m4m
63m4m5m
ProbePlacement(sectionof
cabinet)andLength(m)NumberofRacks
perMonitor Cabinet
Monitor
Location