User Manual

Packet Power™ Wireless DC Monitoring System Manual
Copyright 2016 © Packet Power, LLC.
9
Technical Specifications
COMMUNICATIONS
Operating frequency From 860, 930MHz and 2.4 GHz (specific frequency used varies by
region)
Wireless protocol Proprietary frequency hopping, self-configuring, load-balancing mesh
network
Wired network
protocol (Gateway)
TCP/IP (one IP address needed per Gateway) with SNMP and
Modbus TCP/IP options
Firmware updates Wireless
Typical transmission
range
10 to 50 meters indoors from any one device to any other
Antenna Fully enclosed, fixed configuration
Monitoring Unit to
Gateway Ratio
From 100 to 300 monitoring units per gateway depending on desired
data collection rate and Gateway model
Gateways per site Unlimited
Multi-site support Yes
Encryption Optional 128-bit
Compatible devices All Packet Power modules may be combined in the network
OPERATING ENVIRONMENT
Operating
temperature
0° to +40° C (+32° to +104°F)
Operating humidity 10% to 90% non-condensing
Environmental rating Indoor use / NEMA 1
Mounting Typical: on top of server cabinet, under a cable raceway, under a
raised floor
DISPLAY
LCD LCD display for status and configuration details
LED Indicates general device status
SIZE AND WEIGHT
Ethernet Gateway 76mm x 94mm x 31mm; Weight: 65g (3 oz)