M68333 Rev. A Tel-Link PMP - Sector Terminal Installation & Maintenance Manual 8-7
For DC operations, 16 AWG, 2-conductor twisted pair cable is supplied. The cables for carrying DC power
to the ODU Power Supply chassis should be routed to a DC distribution panel preferably installed in the
same rack. The DC distribution panel should provide individual fuse protection to each chassis. The DC
receptacle is found on the rear of the ODU Power Supply chassis (refer to Figure 8-5). The DC power to the
ODU Power Supply chassis should be protected with a 5.0 Amp fuse.
Figure 8-5 - Sector ODU Power Supply DC Input (Rear View)
8.2.5.2 Sector IDU Chassises
For DC operations, 12 AWG, 2-conductor cable is supplied. The cables for carrying DC power to the Sector
IDU should be routed to a DC distribution panel preferably installed in the same rack. The DC distribution
panel should provide individual fuse protection to each chassis. The DC receptacle is found on the rear of
the IDU (refer to Figure 8-6). The DC power to the Sector Terminal should be protected with a 5.0 Amp
fuse.
Chassis Ground Stud
Cooling Fan
Primary DC Power
Supply Input Port
Secondary DC Power
Supply Input Port
Secondary DC Power
Supply Output Port
Primary DC Power
Supply Output Port
Cooling Fan