Table 5. Blower Data for J801X100C Models
HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
MODEL NAME/
HEATING INPUT
J801X*U
RETURN
AIR VIA:
MOTOR
SPEED
TAP
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.1 0.2 0.3 0.4 0.5
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
J801X100C
100,000 BTU/Hr
Bottom
5 - High*
4 - Med-High
3 - Med-Low** 1,580 47 1,530 48 1,480 50 1,420 0 1,360 54
2 - Alternate 1,500 49 1,450 51 1,400 53 1,340 55 1,280 58
1 - Low*** 1,390 53 1,320 56 1,260 59 1,200 62 1,130
Side
Only
5 - High*
4 - Med-High
3 - Med-Low** 1,540 48 1,490 50 1,440 51 1,380 54 1,330 56
2 - Alternate 1,470 50 1,420 52 1,360 54 1,310 57 1,260 59
1 - Low*** 1,310 57 1,250 59 1,190 62 1,150 64 1,080
Side + Bottom
or
2 sides
5 - High*
4 - Med-High
3 - Med-Low** 1,600 46 1,530 48 1,460 51 1,400 53 1,340 55
2 - Alternate 1,525 49 1,455 51 1,390 53 1,330 56 1,265 59
1 - Low*** 1,370 54 1,300 57 1,230 60 1,150 64 1,090
COOLING AIRFLOW (CFM)
MODEL NAME/
HEATING INPUT
J801X*U
RETURN
AIR VIA:
MOTOR
SPEED
TAP
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM CFM CFM CFM CFM CFM CFM CFM
J801X100C
100,000 BTU/Hr
Bottom
5 - High* 2,310 2,260 2,200 2,150 2,100 2,040 1,990 1,940
4 - Med-High 1,870 1,820 1,760 1,720 1,670 1,610 1,560 1,490
3 - Med-Low** 1,580 1,530 1,480 1,420 1,360 1,290 1,230 1,155
2 - Alternate 1,500 1,450 1,400 1,340 1,280 1,210 1,130 1,050
1 - Low*** 1,390 1,320 1,260 1,200 1,130 1,060 970 890
Side
Only
5 - High* 2,160 2,100 2,060 2,020 2,050 1,990 1,950 1,880
4 - Med-High 1,810 1,750 1,710 1,660 1,620 1,560 1,510 1,440
3 - Med-Low** 1,540 1,490 1,440 1,380 1,330 1,270 1,210 1,150
2 - Alternate 1,470 1,420 1,360 1,310 1,260 1,200 1,130 1,070
1 - Low*** 1,310 1,250 1,190 1,150 1,080 1,000 950 880
Side + Bottom
or
2 sides
5 - High* 2,280 2,220 2,170 2,120 2,090 2,080 2,020 1,950
4 - Med-High 1,880 1,820 1,770 1,720 1,670 1,610 1,560 1,490
3 - Med-Low** 1,600 1,530 1,460 1,400 1,340 1,270 1,200 1,120
2 - Alternate 1,525 1,455 1,390 1,330 1,265 1,190 1,120 1,045
1 - Low*** 1,370 1,300 1,230 1,150 1,090 1,000 920 860
*NOTES:
1. Special consideration should be taken in duct design, evaporator coil selection / pressure drop, and air filter selection to achieve 350 CFM/
ton at 0.5” external static pressure.
2. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
3. Data is shown without filter.
4. Temperature rises in the table are approximate. Actual temperature rises may vary.
5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
6. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
7. *Denotes the factory cool setting, **denotes the factory heat setting, and *** denotes factory fan setting. If the Alternate speed is to be used,
the speed tap must be adjusted at the blower motor plug.