Install Instructions

9
4.4 ELECTRICAL DATA
4.5 ELECTRIC KIT MCA/MOP DATA
* Heat kit suitable for AHU 4-way position installation.
Ampacities for MCA and Fuse/breaker including the blower motor.
HEATER MODEL NUMBER DIGITS '*' : A, B
Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450
cubic feet of air per minute (CFM) or 400 CFM nominally.
HEATER MODEL NUMBER DIGITS ‘*’: A , B
Electric Heater Kits
24
208/230 60 1/3 5 2.6
15(A)
36
208/230 60 1/2 5 3.0
15(A)
60,61
208/230 60 3/4 5 4.5
15(A)
MA XIMUM CIRCUIT
PROTECTOR
VOLTAGE HERTZ HP SPEEDS
MODEL
CIRCUIT
AMPS.
JAYHTR1A05BKR *
JAYHTR1A08BKR*
JAYHTR1A10BKR*
JAYHTR1A15BKR*
JAYHTR1A20BKR*
NO .
Kit# Description Ref. Air Handler use
1
5kW Heat Strip
24,36,60,61
24,36,60,61
24,36,60,61
2
7.5kW Heat Strip
3
10kW Heat Strip
4
5
15kW Heat Strip, double Breaker panel
20kW Heat Strip, double Breaker panel
36,60,61
36,60,61
240 208 240 208
5 29.9 26.4 30 30
7.5 42.9 37.7 45 40
10 55.9 49 60 50
5 31.8 28.3
7.5 44.8 39.6
10 57.8 50.9
15 57.8/26.1
20 57.8/52.1
15 55.9/26.1 49/22.6 60/30 50/25
20 55.9/52.1 49/45.2 60/60 50/50
60,61
36
MIN.Circuit Ampacity
MAX.Fuse or Breaker
(HACR) Ampacity
Heat Kit
Model
Air Handler
Model
Electric
Heat(kW)
JAYHTR1A05BKR*
JAYHTR1A08BKR*
JAYHTR1A10BKR*
JAYHTR1A05BKR*
JAYHTR1A08BKR*
JAYHTR1A10BKR*
JAYHTR1A15BKR*
JAYHTR1A20BKR*
JAYHTR1A05BKR*
JAYHTR1A08BKR*
JAYHTR1A10BKR*
JAYHTR1A15BKR*
JAYHTR1A20BKR*
5 29.4 25.9 30 30 Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
7.5 42.4 37.2 45 40
10 55.4 48.5 60 50
24
35 30
45 40
60 60
60/30 60/25
60/60 60/50
Minimum Heating
Blower Speed
(AC/HP)
50.9/22.6
50.9/45.2