J4AC6 Installation Manual
16
Adjust refrigerant level to attain proper gage pressure.
5.
Add refrigerant if the design liquid line pressure is lower than the
chart value.
Connect gages to refrigerant bottle and unit as illustrated (Figure 40).
Purge all hoses.
Open bottle.
Stop adding refrigerant when liquid line pressure matches the
Refrigerant Charging Chart.
Recover refrigerant if the design liquid line pressure is lower than
the chart value.
Figure 41
Stabilize the system.
Wait 20 minutes for the system condition to stabilize between
adjustments.
Remove gages.
Replace service port caps to prevent leaks. Tighten finger tight plus
an additional 1/6 turn.
6.
Record system Information for reference (Table 8).
Record system pressures and temperatures after charging is
complete.
7.
When the liquid line pressure match the chart, the system is
properly charged.
20 MIN.
Figure 42
Description Value
Outdoor model number
Measured Outdoor Ambient °F
Measured Indoor Ambient °F
Liquid Gage Pressure PSIG
Suction Gage Pressure PSIG
Table 8
55 60 65 70 75 80 85 90 95 100 105 110 115
165 249 265 281 302 324 345 365 385 412 438 465
161 247 263 279 300 322 343 363 383 410 437 463
157 245 261 277 298 320 341 361 381 408 435 461
153 228 243 259 275 296 318 339 359 379 406 433 459
149 226 241 257 273 294 316 337 357 377 404 431 457
145 234 239 255 271 292 314 335 355 375 402 429 455
141 209 223 237 253 269 290 312 333 353 373 400 427 453
137 207 221 235 251 267 288 310 331 351 371 398 425 451
133 205 219 233 249 265 286 308 329 349 369 396 423 449
129 203 217 231 247 263 2
84 306 327 347 367 394 421 447
125 201 215 229 245 261 282 304 325 345 365 392 419 445
121 197 212 227 243 259 280 302 323 343 363 390 417 443
117 194 210 225 241 257 278 300 321 341 361 388 415 441
113 190 207 223 239 255 277 298 320 340 360 387 414 439
109 188 205 221 237 253 275 296 318 338 358 385 412 437
105 186 203 219 235 251 273 294 316 336 356 383 410 435
Cooling
Mode
16 SEER R410A HP Charge Chart 4 TON(Cooling mode)
Outdoor Ambient Temperature(
o
F )
Liquid Pressrue at Small Service Value(psig)
Suction Pressure
at Large Service Valve(psig)
55 60 65 70 75 80 85 90 95 100 105 110 115
165 254 274 291 309 329 350 370 398 421 447 472
161 252 271 289 306 327 348 368 396 419 445 470
157 250 268 287 304 325 346 366 394 417 443 468
153 229 248 266 285 302 323 344 364 392 415 441 466
149 227 246 264 283 300 321 342 362 390 413 439 464
145 225 244 262 281 298 319 340 360 388 411 437 462
141 205 224 242 260 279 296 317 338 358 386 409 435 460
137 202 222 240 258 277 294 315 336 356 384 407 433 458
133 199 220 238 256 275 292 313 334 354 382 405 431 456
129 197 218 236 254 273 2
90 311 332 352 380 403 429 454
125 195 216 234 252 271 288 310 330 350 378 401 427 452
121 193 214 232 250 269 286 308 328 348 376 399 425 450
117 191 212 230 248 267 284 306 326 346 374 397 423 448
113 189 210 228 246 265 282 304 324 344 372 395 421 446
109 187 208 226 244 263 280 302 322 342 370 393 419 444
105 185 206 224 242 261 278 300 320 340 368 391 417 442
Cooling
Mode
16 SEER R410A HP Charge Chart 5 TON(Cooling mode)
Outdoor Ambient Temperature(
o
F )
Liquid Pressrue at Small Service Value(psig)
Suction Pressure
at Large Service Valve(psig)