e agsstate screen displays a numeric value
corresponding to why the generator is or is not
running. is is a diagnostic feature for OutBack
troubleshooting purposes. Press the <DOWN>
sokeytoviewthenextTIMERscreen.
e agsgenfault screen displays three states:
• 0ornogeneratorfault
• 1indicatesthegeneratordidnotstartandthere
is no AC input aer ve minutes
• 2indicatesthegeneratorstarted,butthen
stopped(e.g.,itranoutoffuel)
Press the <DOWN> so key to proceed.
e 24 hr vs time screen counts down the minutes,
startingat1440,ofthe24-hourvoltagestartset
point. Aer the battery voltage has fallen below its
24-hoursetpoint,thetimerstartsandisdisplayed
here. Pressing the <DOWN> so key brings up
the 2hr vs time screen.
ADV/MATE/AGS/TIMERS------------
agsstate 0
DOWN AGS
ADV/MATE/AGS/TIMERS
agsgenfault 0
DOWN UP
ADV/MATE/AGS/TIMERS
24 hr 1440 min
vs time
DOWN UP
ADV/MATE/AGS/PG3---------------
choose category
%SOC
PG2 START TIMERS PG4
Press the <TIMERS> so key to view the
variousAGStimer-relatedscreens.
AGS state can be one or more of the following numbers:
128—Manual Start
64—Exercise
32—Time of Day
16—Load Start
8—Voltage 24 hr/2 hr
4—Voltage 2 min
2—State of Charge (SOC) Start
AnAGSstateof128meansthatAGSisactivebecauseofamanualstart.Morethenonereason
canbetrueatanyonetime(e.g.,AGSstateof20wouldbeloadstartand2minvoltagetimer).
egeneratorwillberunninganytimeAGSstateisgreaterthen0.
Seepage104foratableofgeneratorstartandstopcondtions.