Installation Guide
88
ADV/MATE/AGS/LS-----------------
load stop 0 kw
DOWN UP INC DEC
ADV/MATE/AGS/LS----------------
load stop 1 min
delay
DOWN UP INC DEC
ADV/MATE/AGS/LS---------------
end of the LOAD
START menu
UP TOP AGS
Load Stop Delay
Load Stop KW
AnAGSstopcommandwillbeissuedwhenthe
totalACloadofalltheFXsconnectedtothe
MATE falls below this setting for the amount of
time set with load stop delay (nextscreen)aslong
asthegeneratorwasstartedduetoLoadStart.
issettingexcludesanyFXchargercurrent
for its AC load calculation. e setting can be
changed using the <INC> and <DEC> so keys.
Pressing the <DOWN> so key leads to the load
stop delay screen.
is setting is the delay time the total system AC
loadmustremainbelowtheLoadStopkwbefore
thegeneratorisstopped.Itisadjustablefrom1to
240minutesusingthe<INC> and <DEC> keys.
Pressing the <DOWN> so key leads to the end of
the VOLTAGE START menu screen.
Pressing the <AGS>sokeyreturnstheADV/
MATE/AGS/PG2screen