Installation Guide

86
2-Minute Voltage Set Point
Ifthebatteryvoltagefallsbelowthissetpoint,a
2-minutetimerstartstocountdown.Uponreach-
ingzero,astartcommandissenttothegenerator
evenifitiscurrentlyQuietTime.Usethe<INC>
and <DEC> so keys to change the default set-
tings. When nished, press the <DOWN> so key
to go to the end of VOLTAGE START menu.
Press the <AGS>sokeytoreturntoADV/
MATE/AGS
ADV/MATE/AGS/VSTART-----------
volt start 22.0 vdc
2 min setting
DOWN UP INC DEC
ADV/MATE/AGS/VSTART-----------
end of VOLTAGE START menu
UP TOP AGS
Why you might want it:Insteadofthegeneratorstartingonlyatpresettimesoraccordingto
batteryvoltageconditions,LoadStartallowsittostartbecausethedemandforelectricityis
high. is should prevent the batteries from being depleted. As soon as the demand decreases
andthebatteriescanadequatelyfulllit,thegeneratorwillshuto.
LoadStartwillstartageneratorwheneverthetotalsystemACLoadexceedsthesetpointfor
the programmed amount of time. e generator will then be stopped when the AC load has
droppedbelowaLoadStopsetpointforaprogrammedamountoftime.
WhenthegeneratorisrunningbecauseofLoadStart,theFXsystemwillchargethebatteries.
ischargemightnotbecompletedifthegeneratorisdisconnectedbecauseofLoadStop.
NOTE:Largeinstantaneousloadscanstillovercurrenttheinverterpriortothegenerator
starting and getting in sync with the inverter.
Load Start