Installation Guide

85
ADV/MATE/AGS------------------------
Choose category:
QUIET VOLT
SETUP TIME START PG2
ADV/MATE/AGS/VSTART-----------
volt start 24.4 vdc
24 hr setting
DOWN AGS INC DEC
ADV/MATE/AGS/VSTART------------
volt start 23.6 vdc
2 hr setting
DOWN UP INC DEC
erearethreevoltagestartsetpointsinAGSModethattheusercanadjust.Aeragenerator
isstartedduetoaVoltageStartsetting,itwillbestoppedwhentheFXcompletestheabsorb
chargeorbasedontheVDCGenstopsettingintheAGSSetupmenupreviouslyexplained.
Voltage Start
NOTE:IftheDCGensetissettoYES,thegeneratorwillonlystopaerthebatteryvoltagehas
reachedtheVDCGenstopvoltagefor15minutes.
24-Hour Voltage Set Point
2-Hour Voltage Set Point
TogettotheVoltageStartscreen,pressthe
<VOLT START>sokeyontheADV/MATE/
AGSscreen.
Ifthebatteryvoltagefallsbelowthissetpoint,a24
hourtimerstartscountingdown.Uponreaching
zero,astartcommandissenttothegenerator
unlessitiscurrentlyQuietTime.Tochangethe
default settings, use the <INC> and <DEC> so
keys. When nished, press the <DOWN> so key
to go to the volt start 2 hr setting screen.
Ifthebatteryvoltagefallsbelowthissetpoint,a2
hour timer starts to count down. Aer reaching
zero,astartcommandissenttothegenerator
unlessitiscurrentlyQuietTime.Tochangethe
default settings, use the <INC> and <DEC> so
keys. When nished, press the <DOWN> so key
to go to the volt start 2 min setting screen.