Installation Guide

78
DC Genset
Inthisscreen,YESmeansaDCgeneratoris
presentandtheAGSroutine,whichnormally
stopsthegeneratorupontheFXgoingtoFloator
Silent, will instead stop the generator when the
vdc genstop setting is reached.
isvoltagesettingwillterminateaVoltageStart
command when the battery voltage remains above
itfor15minutesregardlessoftheDCGenset
setting. e setting can be adjusted using the
<INC> and <DEC> so keys. Press the <DOWN>
sokeytoviewtheAGSfaulttimescreen.
AGSFaultTimeistheperiodthegeneratoris
giventoconnecttotheFXsystemaertheAUX
outputhasbeenactivated.Ifthegeneratorfails
to connect and provide AC current, the MATE
displaysanAGSerror.eusercansetthistime
anywherefrom5-30minutesbypressingthe
<INC> and <DEC> so keys. Press the <DOWN>
so key to reach the cool down time screen.
ADV/MATE/AGS/SETUP
dc genset NO
DOWN UP NO YES
NOTE:IfyouhaveageneratorthatproducesAC
voltage,maintaintheNOstatusshownonthis
screen.
ADV/MATE/AGS/SETUP-----
AGS fault time 17
minutes
DOWN UP INC DEC
VDC Genstop
ADV/MATE/AGS/SETUP-----
vdc genstop: 38.0 vdc
DOWN UP INC DEC
NOTE:evdc genstop will turn o a generator
even if the dc genset on the previous screen says
<NO>.
Press the <DOWN> so key to go to the vdc
genstop screen.