Installation Guide

56
NOTE:EQ(EQUALIZE)isnotanautomatic
partoftheFX’schargecycle.WiththeACinput
alreadyconnectedtotheFXsystem,anEQcharge
must be manually started from this menu. e
EQcycleendsaerthetimeittakestochargethe
batteriestotheEQvoltageandtheEQtimelimit
orbymanuallystoppingtheEQchargefromthis
menu.
Pressing <EQ>ontheCHARGERMODE
CONTROLscreenbringsuptheEQUALIZE
CONTROLscreen
When <STOP>hasbeenselected,theEQcharge
has stopped.
When <START> has been selected, two
informational screens are displayed. e user
must push the <MORE> so key before an
equalizingcyclecanbegin.
EQUALIZE CONTROL
eq enabled
START STOP OK
NOTE:Startthegeneratororcheckthatthegrid
isconnectedbeforestartinganEQcycle.eAC
INstatusLEDontheFXmustbesolidyellow.
eEQENABLEDscreenallowsanequalize
chargingcycleoranexit.Pressthe<YES> so key
to enable and then press <EXIT>.
EQ parameters must be set in
ADV/FX menu. follow manuf.
recommendations
MORE
For EQ settings ac source must be
connected to start EQ cycle
MORE
EQ ENABLED: No
are you sure you wish to start an
EQ cycle?
YES EXIT
EQUALIZE CONTROL
eq charge stopped
OK MAIN