Installation Guide
107
eMATEfeaturesover400screensforviewingpowersystemstatusandadjustingitsvalues.escreensareaccessiblein
aseriesofcategorizedmenus(forexample,METERS,WARNING,BATTERY,etc.).Byknowingthecategories,it’seasierto
nd a specic screen. Screens display locations within the system, values and set points, some of which can be changed using
<DEC> and <INC> commands; ports, to which components are connected; on/o and yes/no options; and initiating or
stoppingcertainfunctionsandactivities.efollowingmenuguideoersquickaccesstotheMATEscreens.
MAIN----------------------------------
8:04:21A
SUMSTATUSSETUPADV
STATUS
choose device:
FXCCDCMAIN
e FX screens
include MODES,
METER, BATT(ery),
ERROR, WARNING,
DISCON(NECT), and
SELL.
An ERROR will shut
down the FX(s). e
FX(s) can DISCON-
NECT if the incoming
AC is not acceptable. A
WARNING indicates a
condition that should be
corrected. SELL pertains
to grid-tied FXs.
MODES screens:
u inverter control
u AC in control
u charger control
uAUXcontrol
uEQenabled
METERscreens:
u inverter and charger
watt and kilowatt read-
ings
u AC output voltage
u AC input voltage
u AC inverter current
u AC charger current
u AC input current
u AC sell current
uFXrmware(so-
ware)versionnumber
BATT(ery):
u actual battery voltage
u temperature-com-
pensated voltage
u absorb setpoint
MAIN SCREEN
Pressing the rst two so keys on the MATE will
always return to the MAIN screen
BATT(continued)
u remaining absorb time
u oat setpoint
u remaining oat time
u reoat setpoint
uequalizesetpoint
uremainingequalizetime
u battery temperature
ERRORscreens:
u low AC output voltage
u stacking error detected
u inverter overtemp
u low battery voltage
u phase loss
u high battery voltage
u AC output shorted
u AC output backfeed
WARNINGscreens:
uACinputfrequencytoo
high or too low
uAC input voltage too
high or too low
DISCON(nect)
(eFXwilldisconnect
due to incoming AC cur-
rentirregularities)
uACinfrequencyistoo
high or too low
u AC in voltage is too
high or too low
SELL
u displays reasons a grid-
tie unit cannot sell power
back to a utility; a number
is displayed for each reason
and this number is used by
OutBack technical support
to diagnose the problem
e CC screens include MODE,
METER, and SETP(oint).
MODE screens:
u charger mode
uAUXrelay
uAUXrelaystate
METERscreens:
uPVandbatteryvoltageand
current
u charger watts
u charger kilowatt hours
u charger DC amps
u charger amp hours
u battery and panel voltages
uFirmwareRev
SETP(oint)screens:
u absorb
u oat
ulogs/stats(FLEXmax80)
e SETUP menus allow the
user to establish certain values
for how the FX and MATE
operate.
e FX screens include SRCH
(search) and INPUT.
FXSEARCHscreens:
u search sensitivity
u search pulse length
u pulse spacing
FXINPUTscreensforboth
GRIDandGEN(erator)set-
tings:
u AC transfer
uAC grid limit
u AC generator limit
eMATESETUP
screensincludeCLOCK,
CNT(contrast),GLOW,
SUMRY(summary),and
COMM(communica-
tion)
CLOCKscreens:
u date and time
CONTRASTscreens:
u percentage values for
contrast
GLOWscreens:
u percentage of backlight
and whether the back-
lightisinON,OFF,or
AUTOmode
u amount of time the
backlight is on
SUMMARYscreens:
u type of summary
displayed(FX,CC,DC)
and display time
COMMUNICATION
screens:
uREPOLL
u connect with a PC
uDEBUG
As components are added
or removed and rein-
stalled for maintenance,
theMATEmustREPOLL
to nd the components.
e PC function allows
the system to be moni-
tored via a computer. e
DEBUGfunctionresets
the MATE if any commu-
nication errors occur.
SETUP--------------------------
choose product:
FXMATE
eADV(anced)
menu allows more
precise adjustment
of the inverter and
charger functions, the
generator function and
grid-tie setpoints. e
ADVmenurequires
thepassword141be
entered before access-
ingthescreens(see
nextpage).
FX Total 12.6V 97%
Inverting 0.000kW
AC Loads 0.000kW
Buying $ 0.000kW
FLEXnet DC screens in-
clude METER, STATS,
BATTERY, SHUNT and
AUX
METERscreens
uinstantaneous amp
hours running through
shunts
uaccumulated amp
hours and kilowatt
hours
unumber of removed
amp hours and kilowatt
hours
unumber of charged
amp hours and kilowatt
hours
ueach shunt's charged
status
urmware revision
STATUSscreens
uamps and kilowatts
removed and charged
unumber of days the
battery has been at
100%stateofcharge,
fully charged, and its
maximumchargesince
last reset by user
udays passed since
the charge parameters
were met
uminimumandmaxi-
mum battery values
utemp compensated
battery set point
ucycle charging factors
utotal kilowatt and
amp hours removed