Installation Manual and Specifications
Installation
44
900-0123-01-01 Rev A
Bypass Assembly
Bypass switching can be used when the inverter is shut down for maintenance. This topic is
discussed more beginning on page 47. The GSLC can be equipped with the GS-IOB-230VAC
bypass assembly. The instructions on this page are for making external connections to the
bypass assembly after installation. (The installation wiring for the GS-IOB-230VAC is described
on page 47.)
If the GSLC has no bypass assembly, connections should be made directly to each TBB from
the circuit breakers for the inverter, AC sources, and loads. These connections are designated
in Figure 35.
Wiring diagrams for an assembled 230 Vac system are shown beginning on page 54.
Figure 36 Inverter AC Connections (single-phase)
To make the connections to the
Radian inverter:
1. Designate the topmost AC circuit breaker
as the inverter AC output disconnect.
Install a wire from the AC output circuit
TBB (as shown in Figure 36) to that
disconnect as marked by 1.
2. Install a wire on the left side of the
disconnect as marked by 2. Connect the
wire to the appropriate output terminals
on the Radian inverter.
3. Designate the third AC circuit breaker as
the disconnect for one AC source (G
RID
or G
EN). Install a wire from the TBB of
the appropriate source circuit (as shown
in Figure 35) to the left side of that
disconnect as marked by 3.
4. Install a wire on the right side of the
source disconnect as marked by 4.
Connect the wire to the appropriate input
terminal on the Radian inverter (the
terminal labeled either G
RID or GEN).
5. If a second AC source is present, repeat
steps 3 and 4.
6. Install a wire on the inverter’s N
EU
terminal and c
onnect it to the GSLC’s
neutral TBB (as shown in Figure 36).
Only one neutral connection is required.
Disconnects
2
4
1
3
GRID and GEN inputsAC Output