Single-Phase Wiring
The GSLC allows multiple terminal bus bars (TBB) for multiple AC connections. Because the
Radian inverter possesses two sets of AC input connections and one set of output connections,
three terminal bus bars are available for hot connections, as well as one neutral bus bar. The
hot bus bars use brown insulators in 230 Vac models. The neutral bus bar uses blue insulators
in 230 Vac models.
The TBB on the left is generally used for the inverter’s AC output connections. The central TBB
is for utility grid connections and the right TBB is for a generator. The preassembled GSLC
models follow this convention.
Each TBB accepts conductors from 70 mm
2
(1/0 AWG) to 2.5 mm
2
(#14 AWG). See Table 2
on page 33 for required torque values.
If steps are inappropriate for a given system (such as instructions for a generator when none is
present), they can be ignored.
Figure 35 AC Terminal Bus Bars (single-phase)
AC Output
Grid
Generato
r
Neutral
To make external AC connections to
the single-phase GSLC:
1. Connect the hot wire from the AC load
panel to brown TBB 1 (AC Output).
2. Connect the neutral wire from the AC
load panel to neutral TBB 2.
3. Connect the hot wire from the utility grid
panel (if present) to brown TBB 3 (Grid).
4. Connect the neutral wire from the utility
grid panel (if present) to neutral TBB 2.
5. Connect the hot wire from the generator
(if present) to brown TBB 4 (Generator).
6. Connect the neutral wire from the
generator (if present) to neutral TBB 2.
NOTE: Remove the neutral-ground bond
if necessary. See page 34.
The neutral insulator in Figure 35 is in the
position which opens the bond.