Installation Manual and Specifications

Installation
42
900-0123-01-01 Rev A
Bypass Assembly
Bypass switching can be used when the inverter is shut down for maintenance. This topic is
discussed more beginning on page 47. The GSLC can be equipped with the GS-IOB-
120/240VAC bypass assembly. The instructions on this page are for making external
connections to the bypass assembly after installation. (The installation wiring for the GS-IOB-
120/240VAC is described on page 45.)
If no bypass assembly is used, connections should be made directly to each TBB from the
circuit breakers for the inverter, AC sources, and loads. These connections are designated in
Figure 33.
Wiring diagrams for an assembled 120/240 Vac system are shown beginning on page 49.
Figure 34 Inverter AC Connections (split-phase)
To make the connections to the Radian inverter:
1. Designate the top AC circuit breaker as the
inverter AC output disconnect. Install a wire from
the black AC output TBB (as shown in Figure 33)
to the disconnect marked by 1.
2. Install a wire from the red AC output TBB to the
disconnect marked by 2.
3. Install wires on the left side of the disconnect as
marked by 3 and 4. Connect these wires to the
appropriate L1 and L2 output terminals on
the Radian inverter.
4. Designate the third AC circuit breaker from the
top as the disconnect for one AC source (G
RID
or G
EN). Install a wire from the black source
circuit TBB (as shown in Figure 33) to the
disconnect marked by 5.
5. Install a wire from the red source circuit TBB to
the disconnect marked by 6.
6. Install wires on the right side of the disconnect
as marked by 7 and 8. Connect these wires to
the appropriate L1 and L2 input terminals on
the Radian inverter (the terminals labeled either
G
RID or GEN).
7. If a second AC source is present, repeat steps 4
through 6 using the bottom circuit breaker.
8. Install a wire on the inverter’s NEU terminal
and connect it to the GSLC’s neutral TBB
(as shown in Figure 33). Only one neutral
connection is required.
GRID and GEN inputs AC Output
Disconnects
8
2
3
4
5
6
7
1