Quick Start Guide
Setup and Programming
900-0162-01-01 REV A Sheet 3 of 3
©2014 OutBack Power Technologies. All Rights Reserved.
Monitoring
CAUTION: Equipment Damage
These procedures should be done by a qualified installer who is trained on programming inverter power systems. Failure to set accurate
parameters for the system could potentially cause equipment damage. Damage caused by inaccurate programming is not covered by the
limited warranty for the system.
IMPORTANT
Ensure all settings are correct for the system. The Profile Wizard can be used for rapid setup. For Grid Support functions it may be
necessary to load a .GIP file. This requires the MATE3s System Display.
Verify the firmware revision of all OutBack devices before use. The Radian inverter and system display may not communicate or
operate correctly unless their firmware is above a specified revision number.
For full functionality, the MATE3s must be the system display used when installing Radian inverters with firmware revision
001.006.061 or higher.
For firmware and .GIP file installation, see the Installation Manual. For settings and functions, see the Operator’s Manual.
!
In a MATE3-class system display, the Profile Wizard allows quick setup of parameters that apply to all systems. The Profile Wizard is
reached from the Main Menu as shown in .
The Profile Wizard is useful for rapid setup of multiple parameters including date, time, battery charging, AC source size and limits, and
System Type. It can also configure functions such as High Battery Transfer and Grid Use times. Note that the last two items are not
available if the System Type is set to Off Grid.
NOTE: The Wizard does not configure the entire system. It does not select AC input modes for the FXR inverter, parameters for
automatic generators, or “fully charged” parameters if the FLEXnet DC battery monitor is in use. If settings are made in the wrong order,
the Wizard can overwrite some customized settings. See the system display literature for more information.
Profile Wizard
B
A
The firmware revision of all devices can be confirmed by navigating from the Main Menu as shown in . Upgrades to the firmware
revision can be downloaded from the OutBack website www.outbackpower.com.
The FLEXnet DC (FN-DC) is a battery monitor which measures DC current flow
on one or more shunts. It provides battery state-of-charge (SoC) information.
Exact measurements and programming are performed with the system display.
(See the system display and FLEXnet DC literature.) The LED indicators
shown below provide approximate measurements of the battery state of charge.
FLEXnet DC Battery Monitor
Green
Color
Red
Yellow
Yellow
Yellow ≥ 80%
≥ 70%
≥ 60%
≥ 60% off, < 60% solid, < 50% blinks
Battery State of Charge
FN-DC LED Indicators
> 90% (blinks if charge parameters are met)
After commissioning and programming the FXR system, perform a full battery charge.
Reset the FN-DC by unplugging the communications cable and then plugging it back
in. (The system must be energized at the time.) The FN-DC will reset to 100% SoC
to match the batteries.
NOTE: The FN-DC must be programmed with correct values for battery capacity and
charging requirements. The factory default values may not be correct. If not
programmed accurately, the FN-DC readings and LED indicators will not be accurate.
The same is true if the shunt(s) are not wired correctly.
A
B
Profile Wizard
New Profile Initialized
Back Continue
Wizard Date & Time
16:56
13 Oct 2017 Fri
Back Continue
Wizard System Type
System Type Grid Tied
System Voltage 48 VDC
Array Wattage 1000
Battery Type FLA Capacity 500 Ah
Back Continue
Grid Tied
Main Menu
Settings >>
Profile Wizard >>
Device Data Logs >>
Event Logs >>
Firmware Update >>
Profile Wizard
Profile Wizard
New Profile >>
Existing Profile >>
Restore Profile >>
New Profile
System Configuration
System Information >>
Save / Store Configuration >>
Firmware Version >>
Date and Time >>
LCD Display >>
Firmware Version
Firmware Versions
MATE3 003.013.000
1:VFXR3648A ????
2:VFXR3648A ????
Main Menu
Settings >>
Profile Wizard >>
Device Data Logs >>
Event Logs >>
Firmware Update >>
Profile Wizard
Settings Menu
System >>
Inverter >>
Charge Controller >>
Battery Monitor >>
MATE3s >>
System
A
Wizard AC Configuration
AC Output Voltage 240 VAC
AC Phase Split
AC Input Breaker Size 60 A
Maximum Output Load 33 A
Back Continue
120
Wizard AC Input Limits
Grid Lower Voltage Limit 105 VAC
Grid Upper Voltage Limit 132 VAC
Gen Lower Voltage Limit 108 VAC
Gen Upper Voltage Limit 140 VAC
Back Continue
105
Wizard Generator Configuration
Generator Installed N
Generator Type AC Size 5.0 kW
Generator Start Manual
AUX Output Device Port 1
Back Continue
N
Wizard Battery Charging
Absorb Voltage 57.6 VDC Time 1.0
Float Voltage 54.4 VDC Time 1.0
Equalize Voltage 60.0 VDC Time 3.0
Re-Float Voltage 44.0 VDC
Back Continue
A
This advances the display to the Setup
Complete screen.
B
If the FLEXnet DC
is installed, the
disp
lay advances to the Shunt screens.
If the FLEXnet DC is not installed, see .
C
If the System Type is Grid Tied or Backup, the
display advances to the Grid Use Schedule
screens. If the System Type is Off Grid, see .
B
C
If FN-DC
is installed...
If
System Type
is
Grid Tied
or
Backup
...
B
C
A
Wizard Grid Use Schedule
Period 1 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00
Back Continue
N
Wizard Grid Use Schedule
Period 2 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00
Back Continue
N
Wizard High Battery Transfer
Mode Disabled
Grid Connect 48.0 VDC Delay 60 Min
Grid Disconnect 52.0 VDC Delay 60 Min
Grid Connect SOC 60% Disconnect SOC 95%
Back Continue
Disabled
Wizard Grid Use Schedule
Period 3 Enable N
Weekday Use 0:00 Drop 0:00
Weekend Use 0:00 Drop 0:00
Back Continue
N
Wizard Battery Monitor
Shunt A
Connection Inverter
Back Continue
A
Wizard Battery Monitor
Shunt A
Connection Inverter
Back Continue
B
Wizard Battery Monitor
Shunt A
Connection Inverter
Back Continue
C