Product Manual
Specifications
900-0198-01-00 Rev A 57
Table 26 48-Volt Inverter Settings (MATE3)
Field Item Default Minimum Maximum
INVERTER
Hot Key
Inverter Mode
Off On, Off, or Search
CHARGER
Hot Key
Charger Control
On On or Off
AC Input
Hot Key
AC Input Mode
Use Drop or Use
Search
Sensitivit
y
(see page 14 for increments)
6 0 50
Pulse Length
8 AC Cycles 4 AC Cycles 20 AC Cycles
Pulse Spa
c
ing
60 AC Cycles 4 AC Cycles 120 AC Cycles
AC Input and
Current Limit
Input Type Gri
d
Grid or Gen
Grid Input AC Limit
28 Aac 5 Aac 30 Aac
Gen Input AC Limit
28 Aac 2 Aac 30 Aac
Charger AC Limit
FX3048MT 12Aac 0 Aac 14 Aac
VFX3648M 18 Aac 0 Aac 20 Aac
Grid AC Input
Voltage Limits
Voltage Limit Lower
108 Vac 40 Vac 115 Vac
(Voltage Limit) Upper
140 Vac 130 Vac 150 Vac
Transfer Delay
0.1 second 0.12 seconds 4.0 seconds
Gen AC Input
Voltage Limits
Voltage Limit Lower
108 Vac 40 Vac 115 Vac
(Voltage Limit) Upper
140 Vac 130 Vac 150 Vac
Transfer Delay
1.0 second 0.12 seconds 4.0 seconds
Connect Dela
y
0.5 minutes 0.2 minutes 15.0 minutes
AC Output
Output Voltage
120 Vac 110 Vac 125 Vac
Low Battery
Cut-Out Voltage
42 Vdc 36 Vdc 48 Vdc
Cut-In Voltage
50 Vdc 44 Vdc 52 Vdc
Battery Charger
Absorb Voltage
57.6 Vdc 52 Vdc 64 Vdc
(Absorb) Time
1.0 hours 0.0 hours 24.0 hours
Float Voltage
54.4 Vdc 48 Vdc 60 Vdc
(Float) Time
1.0 hours 0.0 hours 24.0 hours
Re-Float Voltage
50 Vdc 44 Vdc 52 Vdc
Battery Equalize
Equalize Voltage
57.6 Vdc 56 Vdc 34 Vdc
(Equalize) Time
1.0 hours 0.0 hours 24.0 hours
Auxiliary Output
Aux Control Auto Off, Auto or On
Aux Mode
Cool Fan Cool Fan, DivertDC, DivertAC, AC Drop, Vent Fan,
Fault, GenAlert, LoadShed, or Remote
(Load Shed) Enable Voltage
44 Vdc 40 Vdc 56 Vdc
(Gen Alert) ON Voltage
44 Vdc 40 Vdc 56 Vdc
(Gen Alert ON) Dela
y
4 minutes 0 minutes 240 minutes
(Gen Alert) OFF Voltage
56 Vdc 48 Vdc 72 Vdc
(Gen Alert OFF) Dela
y
9 minutes 0 minutes 240 minutes
(Vent Fan) Enable Voltage
52 Vdc 40 Vdc 64 Vdc
(Vent Fan) Off Perio
d
5 minutes 0 minutes 30 minutes
(Divert DC or AC) Enable Voltage
58.4 Vdc 48 Vdc 64 Vdc
(Divert DC or AC) Off Dela
y
30 seconds 0 seconds 240 seconds
Inverter Stacking
Stack Mode Master
1-
2
phase Master, Classic Slave, OB Slave L1,
OB Slave L2, 3phase Master, 3phase Slave
Power Save
Ranking
Master Adjust Onl
y
0 0 7
Slave Adjust Only
1 1 15
Grid-Tie Sell
Grid Tie Enable
— Inoperative
Sell Voltage
— Inoperative
Grid Tie Windo
w
— Inoperative
Calibrate
Input Voltage
27
-1 -3 1
Output Voltage
27
-1 -3 1
Battery Voltage
28
0.0 -0.8 0.8
27
These values represent an adjustable setting with a total range of 4 Vac. The default value of -1 means the calibration will subtract 1 volt from the measured value.
The range of settings allow up to 1 volt to be added to the measured value, or up to 3 volts to be subtracted from it. The result is also displayed.
28
These values represent an adjustable setting with a range of ± 0.8 Vdc from the measured value. The range of settings allows up to 0.8 volts to be either added or
subtracted from the measured value (in increments of 0.4 Vdc). The result is also displayed.