Product Manual

Specifications
52 900-0198-01-00 Rev A
Table 21 48-Volt Inverter Settings (MATE)
Field Item Default Minimum Maximum
Search
search sensitivit
y
(see page 14 for increments)
6 0 50
search pulse length
8 2 20
search pulse spacing
60 AC cycles 4 AC cycles 120 AC cycles
Input
ac transfer control Gri
d
Gri
d
or Gen
ac1/grid limit
28 Aac 5 Aac 30 Aac
ac2/gen limit
28 Aac 2 Aac 30 Aac
Inverter
low battery cut-out (LBCO)
42 Vdc 36 Vdc 48 Vdc
low battery cut-in (LBCI)
50 Vdc 30 Vdc 52 Vdc
adjust output voltage
120 Vac 110 Vac 125 Vac
Charger
charger limit
FX3048MT 12 Aac 0 Aac 14 Aac
VFX3648M 18 Aac 0 Aac 20 Aac
absorb voltage
57.6 Vdc 52 Vdc 64 Vdc
absorb time limit
1.0 hours 0.0 hours 24.0 hours
float voltage
54.4 Vdc 48 Vdc 60 Vdc
float time perio
d
1.0 hours 0.0 hours 24.0 hours
refloat voltage
50 Vdc 44 Vdc 52 Vdc
equalization voltage
57.6 Vdc 56 Vdc 68 Vdc
equalization time perio
d
1.0 hours 0.0 hours 24.0 hours
Grid
ac1/grid lower limit
108 Vac 40 Vac 115 Vac
ac1/grid upper limit
140 Vac 130 Vac 150 Vac
ac1/grid input limit
28 Aac 5 Aac 30 Aac
ac1/grid transfer delay
6 AC cycles 0 AC cycles 240 AC cycles
Generator
(Gen)
gen input connect dela
y
0.5 minutes 0.2 minutes 15 minutes
ac2/gen lower limit
108 Vac 40 Vac 115 Vac
ac2/gen upper limit
140 Vac 130 Vac 150 Vac
ac2/gen input limit
28 Aac 2 Aac 30 Aac
ac2/gen transfer delay
60 AC cycles 0 AC cycles 240 AC cycles
Auxiliary
(AUX)
aux output control AUTO ON, OF
F
, or AUTO
aux output function
Cool Fan Cool Fan, DivertDC, DivertAC, AC Drop, Vent
Fan, Fault, GenAlert, LoadShed, or Remote
genalert on voltage
44 Vdc 40 Vdc 56 Vdc
genalert on dela
y
4 minutes 0 minutes 240 minutes
genalert off set point
56 Vdc 48 Vdc 72 Vdc
genalert off dela
y
9 minutes 0 minutes 240 minutes
load shed off voltage
44 Vdc 40 Vdc 56 Vdc
vent fan on set point
52 Vdc 40 Vdc 64 Vdc
vent fan off perio
d
5 minutes 0 minutes 30 minutes
diversion on voltage
58.4 Vdc 48 Vdc 64 Vdc
diversion off dela
y
30 seconds 0 seconds 240 seconds
Stacking
stack phase Master
1-
2
ph Master, Classic Slave, OB Slave L1,
OB Slave L2, 3ph Master, 3ph Slave
Power Save
master adjust onl
y
0 0 7
slave adjust onl
y
1 1 15
Sell
sell re volts
— Inoperative
grid tie windo
w
— Inoperative
grid tie authorit
y
— Inoperative
Calibration
(Cal)
vac input adjustment
17
236 220 254
vac output adjustment
11
236 220 254
battery vdc adjustment
18
2 0 4
17
These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower voltages. One count equals approximately 1 Vac.
The range of adjustment is 15 Vac above nominal and 17 Vac below nominal.
18
These values are in digital counts, not volts. One count equals 0.4 Vdc. The range of adjustment is 0.8 Vdc above or below nominal.