FLEXpower Radian Quick Start Guide

Energize/Startup
Procedures
Pre-startup Procedures:
1. Double-check all wiring connections.
2. Inspect the enclosure to ensure no
debris or tools have been left inside.
3. Disconnect all AC loads at the backup
(or critical) load panel.
4. Disconnect the AC input feed to
the GSLC at the source.
De-energize/Shutdown
Procedures
To de-energize or shut down the OutBack devices:
1. Turn off (open) the AC circuit breakers.
2. Turn off (open) the DC circuit breakers for the battery.
Wait 5 minutes for the devices to internally discharge themselves.
3. Turn off (open) the PV (input) circuit breakers.
4. Turn off (open) the PV (battery) circuit breakers.
5. Verify 0 Vdc on the first DC bus of the inverter by placing the
voltmeter leads on and .
6. Verify 0 Vdc on the second DC bus by placing the voltmeter leads
on and .
7. Verify 0 Vdc on one PV circuit by placing the voltmeter leads
on and .
8. Verify 0 Vdc on the other PV circuit by placing the voltmeter leads
on and .
9. Verify 0 Vac on the AC output circuit breakers by placing the
voltmeter leads on and . Repeat this step for and .
1
2
3
4
3a
3c
FP Radian
3a
3b
3c
1
2
3
4
WARNING: Lethal Voltage
Review the system configuration to identify
all possible sources of energy. Ensure ALL
sources of power are disconnected before
performing any installation or maintenance on
this equipment. Confirm that the terminals are
de-energized using a validated voltmeter (rated
for a minimum 1000 Vac and 1000 Vdc) to verify
the de-energized condition.
WARNING: Lethal Voltage
The numbered steps will remove power
from the inverter and charge controllers.
However, sources of energy may still be present
inside the GSLC and other locations. To ensure
absolute safety, disconnect ALL power
connections at the source.
1
1b
1c 1d
1b
1c
1b 1d
2f
Test points 2e and 2f refer to the
right terminal of each circuit breaker.
2e 2d
2f 2c
WARNING: Burn Hazard
Internal parts can become hot during
operation. Do not remove the cover
during operation or touch any internal
parts. Be sure to allow them sufficient
time to cool down before attempting to
perform any maintenance.
Functional
Test Points
Battery Voltage Test Points
AC OUT Voltage Test Points
(Terminal bus bar = TBB)
PV Voltage Test Points
1a 1b 1c 1d
3a 3b 3c
3b
3c
CAUTION: Fire Hazard
Before energizing, confirm that all hardware
is installed as shown on the Installation
page. Stacking battery terminal hardware in
any other order can overheat the terminals.
4
To energize or start the OutBack devices:
1. Using a digital voltmeter (DVM), verify 48 Vdc
on the DC input terminals by placing the DVM leads
on and .
Confirm that the battery voltage is correct for the
inverter and charge controller models.
Confirm the polarity.
2. Turn on (close) the PV (battery) circuit breaker
for each charge controller.
3. Verify that the PV input for each charge controller
is in the correct range of open-circuit voltage and
confirm the polarity by:
a) placing the DVM leads on and , and
b) placing the DVM leads on and .
4. Turn on (close) the PV (input) circuit breakers.
5. Turn on (close) the DC circuit breakers from the battery bank to the inverter.
6. If the inverter is in the Off state, turn it On.
7. Turn on (close) the AC output circuit breakers.
8. Verify 120 Vac on the AC Output L1 TBB by placing the DVM leads on and .
9. Verify 120 Vac on the AC Output L2 TBB and .
10. Verify 240 Vac between the AC Output TBBs by placing the DVM leads on and .
11. Start the generator if appropriate. Verify 120/240 Vac on the terminals of the AC input sources.
12. Turn on the AC input feed to the GSLC at the source.
11. Verify 120 Vac on the GRID IN L1 TBB by placing the DVM leads on and .
12. Verify 120 Vac on the GRID IN L2 TBB and .
13. Verify 240 Vac between the GRID IN TBBs by placing the DVM leads on and .
14. Verify 120 Vac on the GEN IN L1 TBB by placing the DVM leads on and .
15. Verify 120 Vac on the GEN IN L2 TBB and .
16. Verify 240 Vac between the GEN IN TBBs by placing the DVM leads on and .
17. Turn on (close) the AC input circuit breakers.
CAUTION: Equipment Damage
Incorrect polarity will damage the equipment.
!
!
NOTE:
The MATE3s system display
retains factory default settings.
Configuration for this system
may be necessary before
commissioning.
See Setup and
Programming
for more information.
Functional
Test Points
Battery Voltage Test Points
GRID IN Voltage Test Points
(Terminal bus bar = TBB)
AC OUT Voltage Test Points
(Terminal bus bar = TBB)
PV Voltage Test Points
4a 3c4b
GEN IN Voltage Test Points
(Terminal bus bar = TBB)
1a 1b
3a 3b 3c
5a 3c5b
1
2
3
4
5
3a 3c
3b 3c
3a 3b
4a 3c
4b 3c
5a
5b
3c
3c
4a 4b
5a 5b
1a 1b
6
2d2a
2c2b
2e
18. Turn on the AC disconnects at the backup (or critical) load panel and test the loads.
900-0226-01-00 REV C