FLEXmax 100 Datasheet

2
OutBack reserves the right to make changes to the products and information contained in this document without notice.
Copyright © 2017 OutBack Power. All Rights Reserved. OutBack is a registered trademark of The Alpha Group. 980-0035-01-00 REV A
FLEXmax 100 SPECIFICATIONS 10/2017
Model:
FLEXmax 100
Nominal Battery System Voltage
24VDC / 36VDC / 48VDC
Maximum Continuous Output Current
100A
Maximum Input Current (Short-Circuit)
64A
Maximum Array (STC Nameplate)
3000W / 4500W / 6000W (charging output limited to 100A at battery voltage)
Maximum PV System Voltage
1
300VDC
Operating Input Voltage Range
2
30VDC to 290VDC
Standby Power Consumption
~2.5W
Power Conversion Eciency
24V: 96% 48V: 97%
Peak Eciency
24V: 97.5% 48V: 98.8%
Charging Regulation
Three-stage
Voltage Regulation Set Points
Absorption, oat, silent and equalization
Equalization Charging
Programmable start time, voltage set point and duration, automatic termination when completed
Battery Temperature Compensation
Adjustable from 2mV/cell/°C to 6mV/cell/°C
Voltage Step-Down Capability
Down convert from any acceptable array voltage to any battery voltage (example: 72VDC array to 24VDC battery)
Programmable Auxiliary Control Output
12VDC output signal which can be programmed for dierent control applications (maximum of 0.25ADC)
Status Display
LED indicators
Remote Display and Controller
MATE3s compatible
Network Cabling
Proprietary network system using RJ-45 modular connectors
Data Logging
128 days
Operating Temperature Range
3
Ambient, -25°C to 60°C (-13°F to 140°F), output power reduced above 25°C
Ingress Protection Rating
IP54
Enclosure Type
3R
Maximum Altitude Rating
10,000ft
Conduit Knockouts
Bottom and sides
Warranty
5 years
Weight (lb/kg)
Unit: 18.3 / 8.3 Shipping: 22 / 10
Dimensions H x W x D (in/cm)
Unit: 22 x 8.8 x 6 / 55.9 x 22.4 x 15.2 Shipping: 25.5 x 12 x 10 / 64.8 x 30.5 x 25.4
Options
Remote Temperature Sensor (RTS), HUB4, HUB10.3, MATE3s
Certications
UL 1741, CSA C22.2 No. 107.1, IEC 62109-1
Minimum Battery Bank Size
100Ah
Charging Range (Output)
20VDC to 68VDC
Additional Features
Built-in GFCI, eld-replaceable cooling fan
1
Highest open-circuit voltage before equipment damage.
2
Operational limits.
3
Derates to 50A at 60°C in a 48VDC system with 220VDC input. Lower input voltage improves thermal performance.